Director IISER Pune
IISER Pune, DR Homi Bhabha Road Pashan Pune 411008
HT Cable Shifting and feeder installation works at IISER Pune.
2021_IISRP_654784_1
23/IISERPUNE/2021-22
Open Tender
Electrical Works
Works
90 days
IISER Pune
As per NIT
2 documents required · 2 mandatory
₹590
Director IISER Pune
₹86,000
18 Nov 2021
28 Oct 2021
8 Nov 2021
28 Oct 2021
5 Nov 2021
28 Oct 2021
Amount
Please note that Quoted rates are inclusive of all taxes, labour, transportation,royalties,lead,lift etc. Nothing extra shall be paid separately.
HT Cable : - Supply,Transportaion , taking delivery ,unloading of HT Cable at site,Supply, Transportation, taking delivery ,unloading at site,testing & commissioning of HT XLPE insulated, E grade, cables (The testing shall including High Voltage T test at site before commissioning of the system & Test voltage shall be as per IS 7098) 3Cx240 Sq.mm 11kV Aluminum XLPE-E- Cable ( Round armored) Make: Polycab/Finolex/KEI
HV CABLE JOINTING & END TERMINATION : Supplying and making indoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 3Cx240 Sq.mm 11kV Aluminum XLPE-E- Cable ( Round armored)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 120 sq. mm and upto 400 sq. mm
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 120 sq. mm and upto 400 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required..Upto 35 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required..Upto 35 sq. mm
Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
MV Cable Jointing & End Termination Supplying and making indoor end termination with brass compression gland and aluminum lugs for following size of PVC insulated and PVC sheathed /XLPE aluminum conductor cables of 1.1kV grade as required. 3½ X 35 sq. mm (70mm)
Supply Of M.V. Cables M.V. AL Cable supply : Supply, loading, transportation unloading at site, storages at site ,shifting from storage place to site, of 1100 Volts grade XPLE insulated over all FRLS outersheathed , Aluminium conductor, armoured LT power cables as per IS 7098(Part 1) of following sizes.( Note :- Cable shall be considered flat armoured type ) 3 1/2 x 35 sq.mm ALuminium ,XLPE Armourd Cable Make: Polycab/Finolex/KEI
SITC with cement concrete foundation HT feeder pillar 630Amp,three phase with base frame made out of 50x50x6mm MS angle & of suitable height. Body of feeder pillar made out of 14SWG thick MS sheet with suitable dimension to accommodate all the electrical accessories. Aluminum Bus bar of suitable size of 630A with epoxy HT insulators. FP should be provided with 2 nos of earth terminals, heavy duty hinges with brass insert to give smooth operation of doors. 6mm thick Asbestos/Bakelite sheet lining, MS protective mesh should be provided in inner side of door & inside the pillar compartment ( Main feeder for Innovation Park Feeder near metering & for Academic HT consumer cable separation)
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 50 mm X 6 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FR PVC insulated copper conductor single core cable etc as required.Group B
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
Supply, loading ,transportation, unloading at site, storages at site of following type light fittings including required integral control gears, lamps,& other accessories etc to complete the work as per Engineer -In -charge. Supply of LED 4ft Batten with a nominal system lumen output of 2000 lumens and a minimum system efficacy of 105 lm/W. The luminaire shall have a rated system lifetime of 40,000 burning hours at L70. The luminaire should have a color temperature of 6500K and CRI>80. The luminaire shall meet IP20 rating with THD < 10% and PF > 0.95. The luminaire housing should made of CRCA with a PC glossy diffuser. The total power consumption should not exceed 40W (including driver). equivalent to Philips Cat No :-.BN308C LED40S-6500 L120 PSU WH (Make Philips/Wipro/Crompton/ Havells)
Supply, loading ,transportation, unloading at site, storages at site of following type light fittings including required integral control gears, lamps,& other accessories etc to complete the work as per Engineer -In -charge. Supply of LED based Flood light, housing made up of Pressure Die Cast Housing LM 6 Alloy/ Anti Dust Exposed Lens,sturdiness and embossed brand name/logo name of manufacturer. The fixture should have a minimum system efficacy of 100 lumen/Watt and a minimum system lumen output of 4000 lumens and maximum system wattage of 40 Watts.The fixture shall have a CRI of minimum 70. The fixture shall be designed for a system life of 50,000 hours @70% lumen maintenance. Ingress Protection of IP66 (lamp and gear Compartment) and Mechanical Impact Resistance Rating of IK >=05.The fixture driver should have an operating voltage range of 140-270 V, surge protection of >=3KV, PF >0.9 , THD<20% and SDCM<5. The driver should be BIS approved, fully potted and encapsulated Euivalent to Philips Cat No :- BRP409 LED CW 040 MR FG S1 (Make Philips/Wipro/Crompton/ Havells)
Supply, loading ,transportation, unloading at site, storages at site of following type light fittings including required integral control gears, lamps,& other accessories etc to complete the work as per Engineer -In -charge. Street light Brackets:- Supply and installation of Galvanised 1000mm long with 20⁰ Angle Single bracket type with FRP dome and ball suitable for street light poles/ exterior wall approximately mounting height of brackes will be 6 mtr all necessary clamps & fixing accessories & weather proof Junction box (IP65) four terminal with single pole MCB & 4 wire loop in loop out connectores sutaible for connection upto 10Sqmm AL Cable etc.
First aid chart made of cloth for electricall shock treatment printed in English ,& Hindi duly framed with front glasses.
Supply, of Exhaust fan 150mm light duty 230 V AC 50 Hz 450 mm 1400 RPM with condenser complete erected in position with n/c materials Fan motor with moisture treatment and class E insulation & With bird protective screen
Supplying and spreading graded stone aggregate 20 mm nominal size in layers of 200mm in tarnsformer yard etc complete as per the direction of Engineer in charge.
Supplying & erecting LED 40 W street light fitting with specificatios : Temperature 3000 to 4500 K, IP65 Protection, -20 to +40 degree celcius operating temeperature, Pressure die cast aluminium material, CRI>80, Operating voltage 100 to 270 V AC, Lumens > 3000, minimum 1 year warranty, MS powder coated mounting bracket which is suitable for mounting new fitting on existing bracket. Heat resistance, EPR gasket bonded to housing shell render the luminaries dust proof & jet proof to IP 65/IP 66. (Make Philips/Wipro/Crompton) Warranty minimum 12 months from date of commissioning.
Supplying & erecting PVC flexiblae cable, 4 core 2.5 sqmm copper conductor, ISI mark, Polycab/Finolex/KEI make, on wall / trussed/ pole or laid in provided trench, pipe etc in approved manner.The rate is inclusive of the cost of material, labour, hoisting, all taxes & levies, octroi etc complete as per direction of Engineer in charge.
Supply and fixing of outdoor type PVC pole mounted box having 4 pole 16 A connector strip for termination of 2 nos 4 sqmm cable, bottom cable entry with gland termination, DIN rail for SP MCB, mounting clamps for pole, earthing termination , MV danger plate on its door, Hinged door with panel lock, dust and water free design, gray or white colour. Transport, handling, labour etc are included, as complete.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of Single poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Make L&T/ Legrand/Schneider/Siemens
Supply and laying of HDPE PLB 40 mm OD pipe , suitable for LT cable with required duct coupler
Supply and fixing of 70 / 72 W LED flood light ,( Specifications : Cool day light , IP 66, with internal driver, mounting brackets, 230 V, 50 Hz, efficiency min 100 L/w, housing material - Aluminium dia cast, Beam angle 60 dregree for light source ) on surface/ 7 to 16 m height pole with required tools, plant, labours, manpower, transport, taxes, handing, etc included, as required. Make Wipro / Crompton / Philips
Laying and fixing of one number LT cable armoured direct in ground including excavation, refilling as required, with existing PLB/DWC pipe of suitable size for said cable ( 35 mm dia ), protective covering refilling the trench etc, depth min 700 mm as required. PLB/DWC pipe is not considered in this item. upto 35 sqmm
Laying and fixing of one number LT cable armoured of approved make in the existing trenches/pipes/trays/on surface with existing protective covering of DWC/PLB pipe of suitable size of cable as required. as complete as per direction of Engineer in charge. PLB/DWC pipe is not considered in this item. Upto 35 sqmm
Supplying and laying 12 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required.
MV Cable Jointing & End Termination : Supplying and making indoor end termination with brass compression gland and copper lugs, for following size of PVC insulated and PVC /XLPE sheathed , copper conductor cables of 1.1kV grade as required. : Size - 4 C X 2.5 sq.mm Copper ,XLPE Armourd Cable
Supply, installation, testing and commissioning of Chemical earthing using electrode of size 76 mm minimum diameter, minimum 03 meter long and connected with 50x5 mm copper internal strip, material of conustruction COPPER, complete with existing excavation / bore, civil work for chamber, cast iron cover size 450 x 450 mm, with backfill compound as requred to fill earth pit up to mark. the earth resistance shall be as per IS 3043 Make Erico/Aslok/Nimbus
Providing boreing / drilling bore well of 150mm dia for casing / strainer pipe , by suitable method, including drilling in all strata, including hiring & running charges of all equipments, tools, plants and machinenaries required for the job, all complete as per direction of Engineer in charge.
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut , bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Supplying & erecting street light bracket as per drawing for mounting street light LED fitting on 7 meter height pole , suitable for LED 40 W street light light fitting made from suitable dia. Class B. 40 mm dia nominal bore G. I. pipe, 1.0 meter horizontal distance as per drawing, mounted on existing pole with nuts and bolts or G I clamps fabricated from 25 mm x 5 mm M.S. strip & using appropriate S.S. nuts & bolts etc as per manufacturer specifications. The rate is inclusive of the cost of material, labour, hoisting, all taxes & levies, octroi etc complete as per direction of Engineer in charge. Approval ny Engineer in charge is compulsary before execution of work.
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge.: External work -25 mm nominal outer dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge.: External work -40 mm nominal outer dia Pipes
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. : All kinds of soil.
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:5:10 (1 cement : 5 coarse sand (zone-III) derived from natural sources : 10 graded stone aggregate 40 mm nominal size derived from natural sources)
Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources)
Centering and shuttering including strutting, propping etc. and removal of form for Foundations, footings, bases of columns, etc. for mass concrete
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. : Thermo-Mechanically Treated bars of grade Fe-500D or more.
Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm made of G.I. wire of dia. 4 mm, PVC coated to achieve outer dia not less than 5 mm in required colour and shadeincluding strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge.
Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work
Filling the available debries in the campus by lifting, transportation, spreading and compacting in layesrs of 20cm average depth within the premises to the locations as approved by the engineer in charge including all other incidental charges, & all necessary lead and lift complete.
Supplying and filling moorum / disintegrated rock of size not more than 100mm brought from out side in trenches, plinth, under floors and basement etc. in layers not exceeding 20cm in depth consolidating each deposited layer for the required proctor density by ramming, mechanical earth compactors and watering including all leads and lifts etc. as directed by the Engineer in charge. The rate shall includes the cost of the materials, labour and all the operations and nothing extra shall be payable.( The payment shall be made for the compacted thickness of filling based on the levels or actual depth of compacted filling at site.)
Hiring Charges of Vibratory road roller with minimum 10 tonne capacity on daily basis with minimum 8 Hours per day actual working including the charges of driver/skilled operator having minimum five years experience and one number helper, required diesel and oil etc. ( Quoted Rate shall includes the cost towards carting/shifting of the roller to actual site of work, all taxes , GST, duties and allowances to the operator and nothing extra shall be payable over quoted rates). The make and model of road roller need to be got approved from the Engineer in charge before bringing the roller to the site of work.
Surface dressing of the ground including removing vegetation and inequalities not exceeding 15 cm deep and disposal of rubbish, lead up to 50 m and lift up to 1.5 m. : All kinds of soil
BBP Electricals
Surendra Infrastructure Pvt. Ltd.
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .