SE EUDC MEERUT
SE EUDC MEERUT
For Replacement of Damaged Gaskets and Oil Seals Along with Packing, Repairing, Maintenance and Centrifuging of Moisturized and Old Transformer Oil for Removal of Moisture Under Electricity Urban Distribution Division-V, Meerut.
2023_PVVNL_872131_1
E-Tender No.-204/EUDC/MEERUT/2023-2024
Open Tender
Electrical Works
Lump-sum
SE EUDC MEERUT
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,540
SE EUDC MEERUT
₹12,000
2 Feb 2024
20 Dec 2023
26 Dec 2023
20 Dec 2023
26 Dec 2023
20 Dec 2023
Amount
Making the 10 MVA & 5 MVA T/F free after opening the 33 kv TPMO from 33 KV side jumpers/11 KV side jumpers/cables etc before the work and making connections after the completion of the work.
Providing of rubberised corck sheet for 10 MVA & 5 MVA gasket set of Good make/Kotika of size 10 mm thickness,/neoprine oil seal ,top cover rubberized gasket packing, radiator gasket packing etc.
Replacement of damaged packings for 10 MVA & 5 MVAof gasket set, oil seal invloving the following works along with help of crane services for lifting and fixing of radiators etc. I. Draining out the T/F oil upto the proper level into empty and dry oil drums safely. II. Replacement of packings of conservator tanks after opening the same safely and re-fitting after the works. III. Replacement of packings of bucchols relay and other associates parts after the opening the same and refitting etc. IV. Opening the packings/gaskits of the vent pipe and others along with opening and fitting etc. V. Replacement of packing and the gaskets of other side of T/F including inspection of the window etc complete. VI. Opening the 33 kv side bushings and replacement of the damaged gasket and oil seals of all Terminal bushings. VII. Opening the 11 kv side bushings and replacement of the damaged gasket and oil seals of all Terminal bushings. VIII. Cleaning of the oily and dusty surface of the T/F body, radiators, conservator tank and part etc. IX. Filling of T/F/oil into the T/F tank including the extra oil for top up the T/F.
Reparing,reconditioning of 33 KV isolatar with removal of carbon & rust after opening of jaws and blads,cleaning with thinner & scrapping of the carbon deposits by emery paper,refixing the same including oiling, greesing & replacement of MS bolts with checking to provide smooth operations.
Replacement of porcelain bushing of good quality of HT side for 10 MVA & 5 MVA.
Replacement of HT side terminal rod made for 10 MVA & 5 MVA of electrolytic copper as per original design of terminal rod.
Replacement of porcelain bushing of good quality of LT side
Replacement of LT side terminal rod for 10 MVA & 5 MVA made of electrolytic copper as per original design of terminal rod.
Repairing & reconditioning for 10 MVA & 5 MVA of Fuse set with cleaning by thinner & cotton cloth,reconditioning/replacement of accessories & re binding of fuse wire etc.
Water level earthing of neutral and body of 10 MVA & 5MVA transformer by boaring of earth upto water level (15 to 20 Mtr.) and lowering of GI Pipe 32 mm dia upto water level and connecting the same by ms flate of size 40x4 mm with transformers. The transformer will be earthed properly including/cutting, jointing, welding etc. of ms earth strip and connecting one earthing with the neutral bushing of transformer and other to the body of transformer at several points. The GI Pipes will be connected to each other with the help of GI Sockets and a cap will be provided on the upper part of the GI Pipe for pouring of water during summer season.
Centrifusing of Moisturized & old 10 MVA & 5 MVA T/F oil for removal of moisture,dirt etc of 10 MVA at site 33/11 KV S/S madhavpuram with providing of centrifusing machine with accessories along with all labour & T& P & making completion of work by centrifusing oil properly .
Replacement of copper connecting clamps of 33 KV side of 10 MVA & 5 MVA T/F.
Water level earthing of neutral and body of 10 MVA transformer by boaring of earth upto water level (15 to 20 Mtr.) and lowering of GI Pipe 32 mm dia upto water level and connecting the same by ms flate of size 40x4 mm with transformers. The transformer will be earthed properly including/cutting, jointing, welding etc. of ms earth strip and connecting one earthing with the neutral bushing of transformer and other to the body of transformer at several points. The GI Pipes will be connected to each other with the help of GI Sockets and a cap will be provided on the upper part of the GI Pipe for pouring of water during summer season.
Providing & Replacement 33 KV connecting clamps of jumpers fixed on 33 KV isolaters / fuse set /L.A/33 KV CT & other equipements made of Aluminium Allow with MS bolt / nuts & spring washers etc,
M/s Sigma Electricals
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .