Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.6 LAccepted-AOC | ₹9.6 L Quoted ₹10.2 L | L1 | Accepted-AOC Being L1 |
| 2 | L2₹11.1 L+₹95,330.52 (9.36%)Rejected-Finance | ₹11.1 L+₹95,330.52 (9.36%) | L2 | Rejected-Finance Being not L1 |
| 3 | Rejected-Technical | - | - | Rejected-Technical VALIDITY OF DD EXPIRED |
| Sl No | Description | Qty | Unit | Pathania Builders L2 | J M Builders And Engineers L1 |
|---|---|---|---|---|---|
| 1.00 | M&L for dismantling of existing panel including disconnecting connected cables, etc. and supplying, installing, testing and commissioning of factory made LT cubical double door panel with roof canopy, outdoor type, of Suitable to accomodate the following accessories made out of CRCA sheet 3 MM thick duly powder coated with Seimens Grey Shade, totally enclosed, dust and vermin proof outer cubicle. Inner cubicle should be made out of 2 MM thick CRCA sheet with working voltage of 415V, 50 Hz, 3 phase 4 wire fully compartmentalised with single door system for each compartment. Outer cubicle having both sides door openable and should be provided with suitable louvers for ventilation. Bus bars provided shall be adequately supported on insulators to withstand dynamic stresses due to short circuit current and shall be suitably colour coded with heat shrinkable sleeve for phase indication. The standard phase arrangement when facing the switchgear shall be R-Y-B from left to right. Internal wiring should be done with 2.5 sqmm multi-stranded copper conductors and shall be properly bunched, tied, ferruled for proper identification, crimped and shall be connected with suitable lugs and PVC sleeves, etc.Threaded earthing studs - 02 Nos shall be provided at the bottom. The cubicle incomer MCCB as well as outgoings shall have copper TPN/TP extension links of current rating not less than 1.5 times the rated capacity. The cubicle should be inclusive of following : Location : Main LT Panel 1 for Transformer Sub Stn No 4 (A) INCOMING -(a) MCCB -DPX3 160 thermal & magnetic type 4 pole 415 volt 25 kA breaking cap. adjustable thermal release range 160 Amps – 01 Nos.(B) OUTGOING -(a) MCCB -DPX3 160 thermal & magnetic type 4 pole 415 volt 25 kA breaking cap. adjustable thermal release range 40 Amps – 05 No. (b) MCCB -DPX3 160 thermal & magnetic type 4 pole 415 volt 25 kA breaking cap. adjustable thermal release range 25 Amps – 01 No. (c) MCCB -DPX3 160 thermal & magnetic type 4 pole 415 volt 25 kA breaking cap. adjustable thermal release range 16 Amps – 02 No. (d) Multi function meter having LCD Display,96 x 96 sq.mm -01 No (e) Current transformer of suitable ratio, Accuracy - 5VA, Class - 1. MAKE AE/NSDA/PRINZ (f) LED INDICATORS RIBBED LENS WITH TRIMMED COLLAR - Red, Yellow and Blue - 1 Each, Make TEKNIK/SELECT/L&T (g) Aluminium bus bar of size 250 Amps rating for R-Y-B phases and Neutral. (h) Base frame for cubical mounting made out of 40x40x6mm equal angle iron duly painted. (j) Foundation for the panel should provided with PCC 1:4:6 at a depth of 150 MM below G.L. and 100 MM above the G.L. with slot openings for I/C and O/G cables. | 1 | Each | 58,000 ₹58,000 Lowest | 60,000 ₹60,000 |
| 2.00 | M&L for dismantling of existing panel including disconnecting connected cables, etc. and supplying, installing, testing and commissioning of factory made LT cubical double door panel with roof canopy, outdoor type, of Suitable to accomodate the following accessories made out of CRCA sheet 3 MM thick duly powder coated with Seimens Grey Shade, totally enclosed, dust and vermin proof outer cubicle. Inner cubicle should be made out of 2 MM thick CRCA sheet with working voltage of 415V, 50 Hz, 3 phase 4 wire fully compartmentalised with single door system for each compartment. Outer cubicle having both sides door openable and should be provided with suitable louvers for ventilation. Bus bars provided shall be adequately supported on insulators to withstand dynamic stresses due to short circuit current and shall be suitably colour coded with heat shrinkable sleeve for phase indication. The standard phase arrangement when facing the switchgear shall be R-Y-B from left to right. Internal wiring should be done with 2.5 sqmm multi-stranded copper conductors and shall be properly bunched, tied, ferruled for proper identification, crimped and shall be connected with suitable lugs and PVC sleeves, etc.Threaded earthing studs - 02 Nos shall be provided at the bottom. The cubicle incomer MCCB as well as outgoings shall have copper TPN/TP extension links of current rating not less than 1.5 times the rated capacity. The cubicle should be inclusive of following : Location : Main LT Panel 2 for Transformer Sub Stn No 4 (A) INCOMING -(a) MCCB -DPX3 160 thermal & magnetic type 4 pole 415 volt 25 kA breaking cap. adjustable thermal release range 160 Amps – 01 No.a) MCCB -DPX3 160 thermal & magnetic type 4 pole 415 volt 25 kA breaking cap. adjustable thermal release range 100 Amps – 01 Nos (b) MCCB -DPX3 160 thermal & magnetic type 4 pole 415 volt 25 kA breaking cap. adjustable thermal release range 25 Amps – 05 No. (c) MCCB -DPX3 160 thermal & magnetic type 4 pole 415 volt 25 kA breaking cap. adjustable thermal release range 16 Amps – 03 No. (d) Multi function meter having LCD Display,96 x 96 sq.mm -01 No (e) Current transformer of suitable ratio, Accuracy - 5VA, Class - 1. MAKE AE/NSDA/PRINZ (f) LED INDICATORS RIBBED LENS WITH TRIMMED COLLAR - Red, Yellow and Blue - 1 Each, Make TEKNIK/SELECT/L&T (g) Aluminium bus bar of size 250 Amps rating for R-Y-B phases and Neutral. (h) Base frame for cubical mounting made out of 40x40x6mm equal angle iron duly painted. (j) Foundation for the panel should provided with PCC 1:4:6 at a depth of 150 MM below G.L. and 100 MM above the G.L. with slot openings for I/C and O/G cables. | 1 | Each | 58,000 ₹58,000 Lowest | 60,000 ₹60,000 |
| 3.00 | M&L for dismantling of existing panel including disconnecting connected cables, etc. and supplying, installing, testing and commissioning of factory made LT cubical double door panel with roof canopy, outdoor type, of Suitable to accomodate the following accessories made out of CRCA sheet 3 MM thick duly powder coated with Seimens Grey Shade, totally enclosed, dust and vermin proof outer cubicle. Inner cubicle should be made out of 2 MM thick CRCA sheet with working voltage of 415V, 50 Hz, 3 phase 4 wire fully compartmentalised with single door system for each compartment. Outer cubicle having both sides door openable and should be provided with suitable louvers for ventilation. Bus bars provided shall be adequately supported on insulators to withstand dynamic stresses due to short circuit current and shall be suitably colour coded with heat shrinkable sleeve for phase indication. The standard phase arrangement when facing the switchgear shall be R-Y-B from left to right. Internal wiring should be done with 2.5 sqmm multi-stranded copper conductors and shall be properly bunched, tied, ferruled for proper identification, crimped and shall be connected with suitable lugs and PVC sleeves, etc.Threaded earthing studs - 02 Nos shall be provided at the bottom. The cubicle incomer MCCB as well as outgoings shall have copper TPN/TP extension links of current rating not less than 1.5 times the rated capacity. The cubicle should be inclusive of following : Location : Main LT Panel 3 for Transformer Sub Stn No 4 (A) INCOMING - (a) MCCB -DPX3 160 thermal & magnetic type 4 pole 415 volt 25 kA breaking cap. adjustable thermal release range 63 Amps – 01 Nos. (B) OUTGOING -(a) MCCB -DPX3 160 thermal & magnetic type 4 pole 415 volt 25 kA breaking cap. adjustable thermal release range 25 Amps – 02 No. (b) MCCB -DPX3 160 thermal & magnetic type 4 pole 415 volt 25 kA breaking cap. adjustable thermal release range 16 Amps – 03 No. (c) Multi function meter having LCD Display,96 x 96 sq.mm -01 No (d) Current transformer of suitable ratio, Accuracy - 5VA, Class - 1. MAKE AE/NSDA/PRINZ (e) LED INDICATORS RIBBED LENS WITH TRIMMED COLLAR - Red, Yellow and Blue - 1 Each, Make TEKNIK/SELECT/L&T (f) Aluminium bus bar of size 250 Amps rating for R-Y-B phases and Neutral.(g) Base frame for cubical mounting made out of 40x40x6mm equal angle iron duly painted. (h) Foundation for the panel should provided with PCC 1:4:6 at a depth of 150 MM below G.L. and 100 MM above the G.L. with slot openings for I/C and O/G cables. | 1 | Each | 60,000 ₹60,000 Lowest | 60,000 ₹60,000 Lowest |
| 4.00 | Supply & fixing, jointing, connecting & testing in trenches XLPE/PVC insulated PVC sheathed cable heavy duty 1100 volts grade, aluminum conductor in trenches / ducts of following sizes including taking out cable cover & cable all as specified and directed : 4 core 16 Sqmm | 300 | RM | 185 ₹55,500 | 180 ₹54,000 Lowest |
| 5.00 | 3.5 core 25 Sqmm | 750 | RM | 235 ₹1,76,250 | 225 ₹1,68,750 Lowest |
| 6.00 | 3.5 core 50 Sqmm | 126 | RM | 335 ₹42,210 | 330 ₹41,580 Lowest |
| 7.00 | 3.5 core 95 Sqmm | 240 | RM | 500 ₹1,20,000 | 495 ₹1,18,800 Lowest |
| 8.00 | 3.5 core 120 Sqmm | 260 | RM | 600 ₹1,56,000 Lowest | 600 ₹1,56,000 Lowest |
| 9.00 | Excavation in trenches for not exc 1.5 mtr wide and not exc 1.5 mtr depth and getting out in Hard/dense soil including taking out faulty cable/cable, cable covers and GI pipe complete all as specified and directed. | 324.11 | Cum | 390 ₹1,26,402.9 | 300 ₹97,233 Lowest |
| 10.00 | Returning filling in including spreading levelling watering and well ramming in layers n.exc 25cm complete all as specified & directed. | 288.25 | Cum | 100 ₹28,825 | 55 ₹15,853.75 Lowest |
Tender Value
₹9 L
EMD Value
₹18,000
Closing Date
9 Jun 2025, 6:00 pmClosed
AGE(I) DALHOUSIE PIN-176305
AGE(I) DALHOUSIE
REPAIR AND MAINTENANCE OF US LT CABLES LT PANELS LT SWITCH GEAR PROTECTION SYSTEM OH LINES AND OTHER CONNECTED WORK AT T LINE AT BAKLOH CANTT
2025_MES_707197_1
9101/2025-26/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AGE(I) DALHOUSIE
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
AGE(I) DALHOUSIE
₹18,000
Yes
AGE(I) DALHOUSIE PIN-176305
11 Oct 2025
13 May 2025
16 Jun 2025
13 May 2025
9 Jun 2025
27 May 2025
13 May 2025 - 22 May 2025
22 May 2025
Amount
Supply & fixing, jointing, connecting & testing in trenches XLPE/PVC insulated PVC sheathed cable heavy duty 1100 volts grade, aluminum conductor in trenches / ducts of following sizes including taking out cable cover & cable all as specified and directed : 4 core 16 Sqmm
3.5 core 25 Sqmm
3.5 core 50 Sqmm
3.5 core 95 Sqmm
3.5 core 120 Sqmm
Excavation in trenches for not exc 1.5 mtr wide and not exc 1.5 mtr depth and getting out in Hard/dense soil including taking out faulty cable/cable, cable covers and GI pipe complete all as specified and directed.
Returning filling in including spreading levelling watering and well ramming in layers n.exc 25cm complete all as specified & directed.
Removing excavated materials n.exc 50m and depositing where directed at a level n.exc 1.5m above the Starting point.
Supply and laying in trench of double wall corrugated pipe of size 63 x 50mm outer and inner dia, orange colour as per IS code : 16205 (Part-24), complete all as specified and directed.
Supply and laying in trench of double wall corrugated pipe of size 90 x 76mm outer and inner dia, orange colour as per IS code : 16205 (Part-24), complete all as specified and directed.
Supply and laying in trench of double wall corrugated pipe of size 40 x 32mm outer and inner dia, orange colour as per IS code : 16205 (Part-24), complete all as specified and directed.
M&L GI pipe light grade with all fittings complete laid in trenches all as specified for 50 mm bore of pipe complete all as specified.
M&L GI pipe light grade with all fittings complete laid in trenches all as specified for 40 mm bore of pipe complete all as specified.
M & L for PCC type C2, 1:3:6 using (40 mm graded stone aggregate) in foundations ,filling and mass concrete includings necessary form work complete all as specified & directed
M&L for PCC type B-1, 1:2:4 using (20 mm gradded stone aggregate) as in coping, including form work complete all as specified & directed.
M&L for cutting/ grooving on plinth/wall/verandah in any condition for laying of cable through pipe and making good the disturbed surface by using cement concrete 1:2:4 type C-2 using 12.50mm graded stone aggregate as required complete all as specified and directed by Engr-in-charge.
M&L for outdoor type factroy made bus bar chamber of size 0.75 x 0.45 x 0.40 meter depth made out of CRCA sheet 3.15mm thick with 4 Nos aluminium busbars of capacity 200 Amps, with colour code supported on incoming and outgoing under ground cables with LED R,Y,B, indicator lamp, panel having agnle iron frame made of 40x40x 6 mm angle iron and 50 cms long legs embeded upto 20 cms in PCC & 30 cms clear above ground complete including painting with two coat of powder coated paint over a coat of red oxide primer on exterior and interior faces, errection of Bus Bar chamber duly grouted with PCC including earth work complete all as specified and directed by Engineer-in-Charge.
Earthing complete with GI earth plate electrode 60cm x 60 cm x 6 mm buried directly in ground vertically to a depth not less than 2.25 mtr below normal ground level with top edge of earth plate at a depth not less than 1.5 mtr below normal ground level connected to and including GI strip 32 x 6 mm by means of bolts, nuts and check nuts and washers etc made of GI & connected to Earthing test point and earth dolly all as shown in elect plate No 3 of SSR Pt-I incl all necessary earth work, excavation, PCC chamber, chamber cover with handle (PCC 1:2:4) including 40 mm dia protection pipe & 20 mm dia watering pipe and wire mesh funnel etc all as specified and as directed by Engr-in-charge.
Pathania Builders (BID ID -3317741)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .