SAMADHAN BUILDING IIM LUCKNOW PRABANDH NAGAR IIM ROAD LUCKNOW
NOTICE INVITING ETENDER FOR SUPPLY INSTALLATION TESTING AND COMMISSIONING OF 24 HP COLD AND HOT VRF/VRV SYSTEM IN REPLACEMENT OF EXISTING SPLIT AC AND ADDITIONAL ELECTRICAL WORK AT ANUSANDHAN OF IIM LUCKNOW
2026_IIML_895792_1
IIML/PROJ/TENDER/2025-26/4543
Open Tender
Electrical Works
Works
IIM LUCKNOW
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹28,000
Yes
SAMADHAN BUILDING
11 Apr 2026
28 Jan 2026
19 Feb 2026
28 Jan 2026
18 Feb 2026
28 Jan 2026
9 Feb 2026
ELECTRICAL WORK
Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
2 X 1.5 sq. mm
3 X 1.5 sq. mm
3 X 2.5 sq. mm
4 X 2.5 sq. mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
5/6 A switch
pin 5/6 A socket outlet
15/16 A switch
6 pin 15/16 A socket outlet
Bell push
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc.as required.
2 Module (75mmX75mm)
3 Module (100mmX75mm)
6 Module (200mmX75mm)
12 Module (200mmX150mm)
Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required.
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.
1 run of cable
2 run of cable
3 run of cable
LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt ) Supplying, installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS :10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K / 6000°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C)
Brush Less Direct Current (BLDC) Fan without Remote Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.
1050mm, service value ≥ 5.1 CM/Min/Watt, air delivery 150 CM/Min (Minimum)
Supplying, drawing, Installation, Testing and commissioning of CAT6 UTP LSZH 23AWG Twisted Pair Cable in existing conduit/ on surface, Category 6 Unshielded Twisted Pair, 4 pair should be complied as per UL/ETL verification program for compliance with ANSI/TIA-568.2-D standard. Outer diameter should be in the range of 6.1mm nominal with Operating Temperature Range : -5° to +60°C, Bending Radius :< 4 X Cable Diameter at –5°C ± 1°C and Pulling Force : 11.5Kg etc. complete as required.
4C x 35 sq mm Armour Cable
Extension Board Wooden and Mica sheet 9" x 11" with 2 switch and 6 socket having 6 meters 3C cable with top.
VRV/VRF AIR-CONDITIONING SYSTEM
OUTDOOR Supply, Installation, Testing & Commissioning of Modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for both cooling & heating having 100% hermetically sealed inverter type twin Rotary/Scroll Compressor(s), minimum two compressors (with individual seperate PCB) for above 14HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R-410-A Refrigerant or equivalent, vibration Isolators with suitable foundation etc. complete as required. To have better efficiency condensor fan shall be capable to operate at different speed with respect to load. The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and CPWD Specifications and work even at 50°C ambient temperature without tripping. The system shall be able to deliver 100% of the rated capacity upto 39 Degree Celcius. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply and BMS compatible. The unit shall be filled with first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion, and reduce the risk of degradation, thereby improving overall performance and durability. The Indian Seasonal Energy Efficiency Ratio (ISEER) of the unit shall be as per Energy Conservation and Sustainable Building Code (ECSBC) 2024 as below and complete as per CPWD specification, connections, inter connections etc. as required. (For capacity <40 kWr ISEER 5.4, Capacity > 40 and <70 ISEER 5.5, Capacity > 70 ISEER 5.6 for ECSBC Building).
10 HP to 12 HP
INDOOR Supply, Installation, Testing and Commissioning of following minimum capacity High wall type Indoor unit equipped with and comfort washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, cord less remote control, drain pan, necessary accessories etc., suitable for operation on 230 V ± 10%, 50 Hz, single phase AC supply, complete as required. The Indoor units must shut down upon receiving a singal from the BMS System/Fire Singnals. The system shall be capable to adjust air flow as per room requirement automatically. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor)
COPPER REFRIGERANT PIPING Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :
9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm
12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm
15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm
19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm
22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm
Supplying, Installation, Testing and Commissioning of Y/T/Multi Joints. Joints shall be of same Original Equipment Manufacturer (OEM) make as of ODUs and IDUs
Indoor Units
Supplying, charging & testing of additional charge of Refrigerant R410-A/R32 including Pressure Testing, Vacumising, etc. complete as required.
Cable - Supply and laying 1.5 sq mm Supply and laying, of 2C x 1.5 Sq. mm Copper conductor sheathed control cum transmission cables with PVC conduit including fixing with clamps & proper connections to equipment etc.complete as required.
Cable - Supply and laying 2.5 sq mm Supply and Laying of 4C X 2.5 sq. mm Power cable copper conductor, XLPE insulated, PVC sheathed, Armoured, 1100V grade as per IS 7098 (Part1) 1988 with upto date amendment on surface/cable tray etc.complete as required
Supply and fixing 8 SWG dia G.I. wire on surface or in recess for loop earthing as required
MS Structure Outdoor Unit Stand with double coat Painting as per Standard Colour Code.
Drain Piping Supply and fixing of UPVC SCH 80 (10Kg/ cm sq) drain water piping complete with fittings, support as per specification and insulated with 09 mm thick insulated with Nitrile Rubber insulation.
20 mm dia ID
CAMC OF THE COMPLETE VRF/VRV SYSTEM (After DLP)
First Year
Second Year
Third Year
Fourth Year
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.11 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.20 MB
TenderAnusandhanElec.pdf
Tender Documents • 1.19 MB
BOQ_941542.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .