| Sl No | Description | Qty | Unit | T.D.K. ENTERPRISE L2 | MAHESWAR ELECTRICAL INDUSTRIES L1 | TAPAN ELECTRICS L3 |
|---|---|---|---|---|---|---|
| 1.00 | Dismantling the existing old single panel HT gear with OCB and one no LT panel with HT Cable ,LT cable and same to be deposited to the concern authority. | 1 | item | 1,000 ₹1,000 | 2,500 ₹2,500 | 500 ₹500 Lowest |
| 2.00 | Supply, Installation, testing & commissioning of 6.6 KV, 800 A, short-circuit capacity of 26.3 KA for 3 sec, Single-panel HT Gear with VCBs as per Specification [Make - Schneider Electric/SIEMENS/ABB/ Crompton Greaves /Pascal )as approved by E.I.C] below:- | 1 | item | 6,20,050 ₹6,20,050 | 5,90,400 ₹5,90,400 Lowest | 6,10,000 ₹6,10,000 |
| 2.01The Vacuum Circuit Breaker should comply as per IS:13118 & IEC:62271-100 for Circuit Breaker & IS:3427 & IEC:62271-200/IEC 694, IEC-61850 for Indoor panel. | ||||||
| 2.02PANEL The HT panel is rated at 6.6 KV, 3-Phase 800A, Breaking Current/short-circuit capacity of 26.3kA for 3 sec, 50c/s and shall be of floor-mounting, sheet steel clad, free-standing metal enclosed air insulated switchgear cubicle with VCB inside. The Vacuum Circuit Breaker (Make - Schneider Electric/SIEMENS/ABB/ Crompton Greaves/Pascal as approved by E.I.C) is horizontal isolation & horizontal drawout/Vertical isolation & horizontal drawout with 3 compartments and is made of 2mm CRCA sheet for load bearing members with vermin & moisture proof along with automatic shutter arrangement for complete isolation of bars, cable sockets & other live parts etc. when the removable portion is withdrawn. The breaker is arranged for hand operation through front of the panel push buttons & spring charging mechanism and also electrical motor which will be energizied by 230V AC. Closing and tripping coils are rated for 110V DC to be made available from local power supply 230 V, 50 Hz, A.C. with remote operation compatibility. All trip coils shall be of shunt trip type energized from a suitable rectifier condenser source.supply is required. There is a remote operation through multicore arrangement for closing & tripping. The shutter shall be gravity operated. | ||||||
| 2.03The switchgear and controlgear should have the minimum degree of protection (in accordance with IEC-60529 or as per Indian Standard IS 3427, as applicable( IP-4X for the enclosure and - IP-2X for the partition between compartments). | ||||||
| 2.04The provision for cable entry & size shall be bottom entry and suitable for upto 1Rx3Cx300 sq.mm 11KV HT power Armoured AL. cable | ||||||
| 2.05FRONT DOOR The front door of the breaker seting as panel door is not acceptable. High-Voltage door During switching operations, the high-voltage door should remain closed and mechanical interlock should prevent opening of door when the switching device is in service and is switched ON. The position of the withdraw-able section, the CLOSED/OPEN switch position of the switching device, the operating cycle counter and the “spring charged” indication should be visible through pressure-resistant inspection windows in the high-voltage door. The panel front door can be closed with the breaker in isolated position. | ||||||
| 2.06BUSBAR The spacious bus bar compartment is provided on the top of the cubicle. The main bus bar can carry current upto 1000A and are made of electrolytic grade copper & shall be vertically placed one after another. The bus bars should be air insulated but must be HT PVC sleeved & color coded for R-Y-B. No live parts should be accessible. All joints should be covered with monoplast compound and color coded for easy identification. The feeder connection to the busbars are preffered to be encapsulated. . | ||||||
| 2.07BREAKER The vacuum circuit breaker is mounted on a truck and is of horizontal isolation and horizontal drawout/Vertical isolation & horizontal drawout type having a robust motorized mechanism. The spring charge cycle duty of mechanism is O-C-O. The vacuum circuit breaker is single break design and have one vacuum interrupter per phase. The vacuum interrupter should not be of pinch tube type design, it should be sealed by brazing in a vacuum oven & all the vacuum interrupters must be segregated in a cast resin housing. The minimum operational life of the vacuum interrupter is 30,000 mechanical, 10,000 electrical at rated current & 100 at rated short circuit. The breaker is having auxiliary switch 6NO+6NC.. [OEM Certificate to be provided] | ||||||
| 2.08EARTHING A continous copper earth bus runs across the entire length of the switchboard. All doors partitions, covers and non current carrying metallic parts are earthed to achieve earth potential for the entire enclosure. Terminals are provided at each end of the earth bus to connect the grid earthing. If integral earthing facility is not available separate earthing truck shall be provided for earthing. | ||||||
Tender Value
Refer Docs
EMD Value
₹40,851
Closing Date
29 Jun 2026, 1:00 pmClosed
The Executive Engineer PWD,ECD
New office Complex Building(5th Floor) Bhabani Bhawan Alipore, Kolkata 700027
Replacement of the existing old HT single OCB panel and LT panel board with new one and allied Electrical installation work for existing Substation at State Poultry Farm, Tollygunge
2026_WBPWD_5014387_1
WBPWD/EE-ECD/e-NIQ-11/2026-27
Open Tender
ELECTRICAL WORKS ORG
Item Rate
60 days
Tollygunge
please refer tender documents
5 documents required · 5 mandatory
₹40,851
O/O The Executive Engineer PWD ECD
27 Aug 2026
22 May 2026
1 Jul 2026
22 May 2026
29 Jun 2026
4 Jun 2026
22 May 2026 - 2 Jun 2026
2 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Dismantling the existing old single panel HT gear with OCB and one no LT panel with HT Cable ,LT cable and same to be deposited to the concern authority. | 1 | item | 1.25 | ₹1.25 |
| 2 | Supply, Installation, testing & commissioning of 6.6 KV, 800 A, short-circuit capacity of 26.3 KA for 3 sec, Single-panel HT Gear with VCBs as per Specification [Make - Schneider Electric/SIEMENS/ABB/ Crompton Greaves /Pascal )as approved by E.I.C] below:- | 1 | item | 2.25 | ₹2.25 |
| - | The Vacuum Circuit Breaker should comply as per IS:13118 & IEC:62271-100 for Circuit Breaker & IS:3427 & IEC:62271-200/IEC 694, IEC-61850 for Indoor panel. | - | - | - | - |
| - | PANEL
The HT panel is rated at 6.6 KV, 3-Phase 800A, Breaking Current/short-circuit capacity of 26.3kA for 3 sec, 50c/s and shall be of floor-mounting, sheet steel clad, free-standing metal enclosed air insulated switchgear cubicle with VCB inside. The Vacuum Circuit Breaker (Make - Schneider Electric/SIEMENS/ABB/ Crompton Greaves/Pascal as approved by E.I.C) is horizontal isolation & horizontal drawout/Vertical isolation & horizontal drawout with 3 compartments and is made of 2mm CRCA sheet for load bearing members with vermin & moisture proof along with automatic shutter arrangement for complete isolation of bars, cable sockets & other live parts etc. when the removable portion is withdrawn. The breaker is arranged for hand operation through front of the panel push buttons & spring charging mechanism and also electrical motor which will be energizied by 230V AC. Closing and tripping coils are rated for 110V DC to be made available from local power supply 230 V, 50 Hz, A.C. with remote operation compatibility. All trip coils shall be of shunt trip type energized from a suitable rectifier condenser source.supply is required. There is a remote operation through multicore arrangement for closing & tripping. The shutter shall be gravity operated. | - | - | - | - |
| - | The switchgear and controlgear should have the minimum degree of protection (in accordance with IEC-60529 or as per Indian Standard IS 3427, as applicable( IP-4X for the enclosure and - IP-2X for the partition between compartments). | - | - | - | - |
| - | The provision for cable entry & size shall be bottom entry and suitable for upto 1Rx3Cx300 sq.mm 11KV HT power Armoured AL. cable | - | - | - | - |
| - | FRONT DOOR
The front door of the breaker seting as panel door is not acceptable. High-Voltage door During switching operations, the high-voltage door should remain closed and mechanical interlock should prevent opening of door when the switching device is in service and is switched ON. The position of the withdraw-able section, the CLOSED/OPEN switch position of the switching device, the operating cycle counter and the “spring charged” indication should be visible through pressure-resistant inspection windows in the high-voltage door. The panel front door can be closed with the breaker in isolated position. | - | - | - | - |
| - | BUSBAR
The spacious bus bar compartment is provided on the top of the cubicle. The main bus bar can carry current upto 1000A and are made of electrolytic grade copper & shall be vertically placed one after another. The bus bars should be air insulated but must be HT PVC sleeved & color coded for R-Y-B. No live parts should be accessible. All joints should be covered with monoplast compound and color coded for easy identification. The feeder connection to the busbars are preffered to be encapsulated. . | - | - | - | - |
| - | BREAKER
The vacuum circuit breaker is mounted on a truck and is of horizontal isolation and horizontal drawout/Vertical isolation & horizontal drawout type having a robust motorized mechanism. The spring charge cycle duty of mechanism is O-C-O. The vacuum circuit breaker is single break design and have one vacuum interrupter per phase. The vacuum interrupter should not be of pinch tube type design, it should be sealed by brazing in a vacuum oven & all the vacuum interrupters must be segregated in a cast resin housing. The minimum operational life of the vacuum interrupter is 30,000 mechanical, 10,000 electrical at rated current & 100 at rated short circuit. The breaker is having auxiliary switch 6NO+6NC.. [OEM Certificate to be provided] | - | - | - | - |
| - | EARTHING
A continous copper earth bus runs across the entire length of the switchboard. All doors partitions, covers and non current carrying metallic parts are earthed to achieve earth potential for the entire enclosure. Terminals are provided at each end of the earth bus to connect the grid earthing. If integral earthing facility is not available separate earthing truck shall be provided for earthing. | - | - | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.17 MB
Tendernotice_2.pdf
PDF • 0.51 MB
BOQ_5082452.xls
BOQ • 0.49 MB
1stdatecorrigendum.pdf
PDF • 0.85 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .