Loading…
Loading…
Tender Value
₹6.1 L
EMD Value
₹12,200
Closing Date
28 Aug 2026, 6:00 pm4d left
GE (AF) TA GWALIOR
GE (AF) TA GWALIOR-474020
REQUIREMENT OF 10 KVA UPS FOR STABLIZED POWER SUPPLY AT AF STN GWALIOR
2026_MES_781774_1
8900/1643/GWL/E8
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
Gwalior
Please ref tender documents
7 documents required · 7 mandatory
₹500
GE (AF) TA GWALIOR
₹12,200
Yes
28 Aug 2026
30 Jul 2026
4 Sept 2026
30 Jul 2026
28 Aug 2026
14 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply ,Install testing and commisioning of 10 KVA IGBT - based Online UPS system with 3 phase input and 1 phase output ,with inbuilt isolation transformer providing a minimum back up of 60 minutes at full load with Exide EP 100 /12 VAH Battery with rack with connecting wire
INPUT
1.Nominal Voltage : 320V~480V AC
2.Operating Frequency Range: 50 / 60 Hz ± 10% (Auto Sensing)
3.Power Factor >0.99
OUTPUT
1.Output Voltage/Power Factor : 220V / 230V / 240V AC / ±1% / 0.8 Std., 0.9 Optional
2.Output Frequency : Auto Sensing 50 / 60 Hz ± 1~10% Sync Mode (Configurable), 50/60 Hz ± 0.1 Hz Battery Mode
3.Harmonic Distortion (THDv): ≤1%
4.Crest Factor: 3:1
5.Efficiency : 94.0% Dual Conversion Mode, 99.0% ECO Mode
BATTERY
1.DC Voltage : 192-240V Configurable
2.Charge Current 6.5 A Configurable
3.Typical Recharge Time 4-5 Hours (90% of full capacity)
SYSTEM FEATURES
1.LCD Indication : Input Voltage/Frequency, Output Voltage/Frequency, Battery Voltage, Load Watt/VA and %, Inverter Temperature, Operation Mode such as “On Line”, “ON Batt” or On “Bypass”, Fault Codes, Battery & Load Bar graph
2.LED Indication: Normal Operation, Bypass, Abnormal, Fault and Battery Mode
3.Alarms / Protection : Batt. Low, DC High, Inverter Under/Over Voltage, UPS Over Load, 4.Short Circuit, Fan Failure and UPS Fault.
5.Overload Capability: ≤ 125% for 10 min, >125-150% for 1 min, >150% for 200 ms
Transfer Time: AC to Battery : 0ms, Inverter to Bypass : 4ms (Typical) | 1 | Each job | - | - |
| 2 | M&L for flame proof sub main wiring concealed using Four single core PVC insulated, FRLSH, stranded copper conductor cable any height ( 4m to 16m ) of size 4 Sqmm for sub main wiring, along with one run of 4 Sqmm PVC insulated, FRLSH, Stranded copper conductor cable for earth continuity conductor in and including 25 mm dia medium grade steel conduit fixed on wall/ceiling complete all as specified and directed by Engineer-in-Charge.
Note: Four run of single core PVC cable with one run of earth wire and one run of steel conduit together shall be measured as one unit. | 50 | RM | - | - |
| 3 | Supplying & fixing of flame proof, switch socket & plug combined made of aluminum alloy LM-6 having 2 pole + earth suitable for 250 volts supply and current rating of 25 Amps complete all as specified and directed by Engineer-in-Charge. | 2 | Each | - | - |
| 4 | M&L for Chemical earthing with copper earth plate 90cmx60cmx5mm & copper earth strip 32x6 mm complete buried directly in ground vertically to a depth not less than 3.10 meter below normal ground level (with top edge of earth plate not less than 2.10 mtr below ground level), connecting to copper strip 32mm x 6mm thick main earth lead by means of tinned copper / brass bolts , nuts, check nuts and washers besides brazing at all joints all as directed and connected to earth test point all as specified and testing on completion with and including necessary excavation and earth work in any type of soil, earth electrode, earthing lead from electrode to test point, made of phosphorous brongze/gun metal of size 75mmx75mmx25mm dril and screwed including 03 Nos 8mm dia 25mm long hexagonal head screwed, adequate quantity of charcoal dust & common salt in alternate layers of 100mm thick all around the plate, under and above the plate and returning, filling of earth spread levelled, watered and compacted to required level, PCC (1:3:6) type C-1 (using 20mm graded stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, pre cast 40mm thick RCC cover of (1:2:4) type B-1 (using 20mm graded stone aggregate), reinforced with 8mm dia TMT bars 3 Nos both way with 12mm dia MS round bar handle, GI medium watering pipe 25mm dia with funnel and wire mesh and 40 mm bore GI light grade earth lead protection pipe complete all as specified and directed .
Note :- (i) copper strip 32mm x 6mm and GI pipe medium grade, up to 7.5mtr shall be deemed to be included in the rates quoted for earthing.
(ii) Excavation and earth work in any type of soil strata shall be deemed to be included in rates quoted for earthing. | 1 | Each | - | - |
| 5 | Supply and laying of Copper earth strip 32x6 mm from existing point to the test bench including necessary connections with nut &bolt complete all as specified and directed. | 65 | RM | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.42 MB
tender1643.pdf
Tender Documents • 0.86 MB
BOQ_875768.xls
BOQ • 0.25 MB
amdt1643.pdf
PDF • 0.09 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].