| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.4 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹41.0 L+₹3.5 L (9.41%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | L3₹42.4 L+₹5.0 L (13.4%)Rejected-Finance | L3 | Rejected-Finance L3 | |
| 4 | L4₹44.6 L+₹7.2 L (19.2%)Rejected-Finance | L4 | Rejected-Finance L4 |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
24 Dec 2024, 6:00 pmClosed
Major S K Yadav
GE(S)Bathinda Bathinda Mil Stn
GE(S) BTD 91 OF 2024-25 REPAIR AND MAINTENANCE TO LIGHTENING CONDUCTOR OF SHED BUILDINGS AND REPAIR RENEWAL OF EARTHING TO BUILDING AND OTHER MISC WORKS AND BUILDING SECURITY LIGHTS AND PANEL LIGHTS UNDER AGE EM IV UNDER GE (SOUTH) BATHINDA AT BATHIN
2024_MES_686770_1
GE(S) BTD- 91 OF 2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
GE(S)Bathinda
Class D
Category b(i)
10 documents required · 10 mandatory
₹500
GE(S)Bathinda
₹90,000
Yes
1 Feb 2025
3 Dec 2024
26 Dec 2024
3 Dec 2024
24 Dec 2024
10 Dec 2024
Amount
Dismantling and taking down the existing defective building security light /panel light/flood light /post top latern fitting of any type and any capacity fixed at any height by replacing UNSV part including perpex cover checking loose connection etc, restroration of electric supply, detecting and repair of UG cable fault whenever required round the clock all as directed at site on daily complaint basis.
Supply and fixing of Building Security light LED type of capacity 25 W comprising with Pressure die cast aluminium housing IP 66 protection with all accessories internally prewired and including connecting up with twin core twisted copper conductor cable of suitable size including bracket made of 40mm dia GI light grade pipe of 1.2m long bent to shape fixed with suitable MS clamps, bolts, nuts and washers duly painted complete all as specified and as directed by the Engineer-in-Charge.
Supply and fixing of Building Security light LED type of capacity 35/36 W comprising with Pressure die cast aluminium housing IP 66 protection with all accessories internally prewired and including connecting up with twin core twisted copper conductor cable of suitable size including bracket made of 40mm dia GI light grade pipe of 1.2m long bent to shape fixed with suitable MS clamps, bolts, nuts and washers duly painted complete all as specified and as directed by the Engineer-in-Charge.
Supply and fixing of LED panel light fitting, recessed mounted, square shaped of size 2'x2' area, 36(±10%)watts efficacy not less than 90 lumen/watt, extruded Aluminium/ polycarbonate, PC diffusor, module and inbuilt driver complete including making connection complete all as specified and directed.
Supply and fixing of LED panel light fitting, Surface mounted, square shaped of size 2'x2' area, 36(±10%)watts efficacy not less than 90 lumen/watt, extruded Aluminium /polycarbonate, PC diffusor, module and inbuilt driver complete including making connection complete all as specified and directed.
Supply and fixing of LED downlighter/spot light fitting, recessed mounted, round shaped of ceiling cut outφ160mm, 12 watts efficacy not less than 90 lumen/watt, 6500K extruded Aluminium/polycarbonate, PC diffusor, module and inbuilt driver complete including making connection complete all as specified and directed.
Supply and fixing of LED Slim surface mounting LED panel light 12 W , 3000K/6500K , Square shape with premium diffuser to ensure glare free complete including electrical connection with PVC three core copper flexible wire & all necessary fixing accessories complete all as specified and directed
Supply and fixing of LED flood light fitting sqaure shape 150 Watt 230V AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp, bracket with impact and corrossion resistant complete with IP 65/66 protection with suitable bolt and nuts, fixing at any height upto 15m complete with making connection complete all as specified and directed
Supply and fixing in replacement of post top lantern LED type 20 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistance complete with driver and lamp complete all as specified and directed
Material and labour for repair to existing LED Building security light fitting 25 Watt to 40 Watt of any make including supply and replacement of driver, LED Strips and other minor allied items required at site to make the light fitting serviceable complete all as specified and directed by Engineer-in-Charge.
Material and labour for repair to existing LED Panel light recessed/ surface mounted of any type and any wattage , any make including supply and replacement of driver, LED Strips and other minor allied items required at site to make the light fitting serviceable complete all as specified and directed by Engineer-in-Charge.
Taking down carefully existing copper/Aluminum point wiring (light,fan, socket or power) complete including fixture and fittings such as switches, bell pushes, ceiling roses, pendents, regulators, sockets, light fitting, call bells etc removiing materials to store for keeping in safe custody or for deposit at Store of AGE E/M -IV and making good disturbed surfaces of walls, floors etc. to match existing color complete all as specified and directed.
Material and labour for one light / fan point controlled by one, one way switch 06 Amp wiring with 2.5 Sq mm nominal cross sectional area, single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed FRLS copper conductor cable with and including continuous earth wire of size 2.5 Sq mm nominal cross sectional area, single core, 1100 Volts grade, multi-stranded, PVC insulated, unsheathed, FRLSH copper conductor cable and connected to common earth and earth dolly with suitable copper lugs and drawing into and including rigid non-metallic PVC conduit of 25 mm dia in medium grade complete with and including all PVC conduit accessories concealed into wall by cutting of chases in wall /open conduit for false ceiling complete and including modular metal flush boxes not less than 1.6mm thick alongwith modular cover plate with frame of any size for mounting of any type modular switches/sockets/bell switch /fan regulator and brass screws, cup washers etc complete, making good the distributed surfacess completely matched and finished with existing surfacess including painting of walls etc complete all as specified and directed.
S & F in repairs Modular switch 1 way 6A/10A 1 module single pole complete all as specified and directed.
S & F in repairs ceiling rose surface bake lite with 3 terminals complete all as specified and directed.
S&F in repair Switch piano, flush type single pole, one way 6 Amp complete all as specified and directed
Taking down old complete and Material and labour sub main wiring with 2.5 Sq mm nominal cross sectional area, two single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable with and including continuous earth wire of size 2.5 Sq mm nominal cross sectional area, single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable and connected to common earth and earth dolly with suitable copper lugs and drawing into and including rigid non-metallic PVC conduit of 20 mm dia, medium grade complete with and including all PVC conduit accessories concealed into wall by cutting of chases in wall and making good to the disturbed surfaces to matched and finised with existing surface are included in the ratecomplete all as specified and directed. Note:- (i) 2 run of 2.5 Sqmm main cable, one run of 2.5 Sqmm earth wire and one run length of PVC conduit of size 20 mm shall be considered as one running length. (ii) The wiring shall be done in proper color coding using Red,Yellow, Blue for phases, Black for neutral and Green for earth.
supply and fixing in replacement of sheet metal enclosure MCB board, 02 way, with IP - 43 & IK 09 protection along with cable end box for above DB and flush to wall including DP MCB 16 Amp alongwith l cutting etc in wall and making good to the disturbed surfaces to match the existing complete all as specified & directed.
Taking down old complete and supply and fixing of sheet metal enclosure distribution board, double door, single pole and neutral, AC, 240 volt, 08 way, with 200 Amp rated copper bus bar and metal door with IP - 43 & IK 09 protection along with cable end box for above DB and flush to wall including all cutting etc in wall and making good to the disturbed surfaces to match the existing complete all as specified & directed.
Taking down old complete and supply and fixing of SP MCB 6-32 Amp ,240Volt 10 KA ‘C’ series complete all as specified and directed.
Taking down old complete and supply and fixing of SPN MCB 40-63 Amp ,240Volt 10 KA ‘C’ series complete all as specified and directed.
Taking down old complete and M&L labour for earthing complete with galvanised mild steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried vertically in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of the plate not less than 1.5 metre below normal ground level steel earth plate connected with GI wire 04 mm dia by means of lug, bolts, nuts, check nuts, washers of galvanised iron or steel GI protection pipe 15 mm bore light grade all as shown in elect plate No 3 on serial page No 497 of SSR part I - 2009 and connecting to main switch board / Main DB’s including excavation, earth work, salt and charcoal dust mixed and packed 150 mm thick around GI earth plate, GI pipe medium grade 20 mm nominal bore watering pipe GI sheet funnel wire mesh, concrete pit, RCC cover 40 mm thick in PCC 1:2:4 type B1 duly reinforced with MS Bars 6 mm dia at the rate of 75 mm centre to centre both way with 12 mm dia lifting handle and pit / chamber in PCC 1:3:6 type C1, Angle iron 40 mm x 40 mm x 3 mm frame for pit cover including testing on completion complete all as specified and directed.
Supplying and fixing in replacement 1100 volts grade heavy duty cable PVC insulated aluminium solid conductor, served with inner sheathing of PVC tape and overall PVC sheathed twin core cable flat or circular of size 4.0 sqmm complete all as specified and as directed.
Supply and fixing Rigid non-metallic PVC conduit 20 mm dia (Heavy duty) in concealed exclusive of boxes (junction/terminal) but inclusive of all tees, bends,elbows, reducers, junction box ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. including taking out old conduit complete all as specified and directed.
Supply and fixing in repair of surface Modular metal flush box 2 modules including mounting on wall complete as specified and directed
Supply and fixing in repair of Modular cover plate with frame for 2 modules including mounting on surface and complete concealed into wall by cutting of chases in wallall as specified and directed
Supply and fixing in repair of surface Modular metal flush box 4 modules including mounting on wall complete as specified and directed
Supply and fixing in repair of Modular cover plate with frame for 4modules including mounting on surface and complete concealed into wall by cutting of chases in wallall as specified and directed
M&L for earthing with galvanized steel earth plate electrode 600x600x6mm size burried directly in ground to depth not less than 2.25m below ground level with top edge of the plate not less than 1.5 mtr below normal ground level surrounded with char coal and common salt filling in alternative layers of 15cm thick and connected to aluminium earth strip 25x4 mm by means of nuts/bolts and washers etc made out of galvanized iron including 40mm dia GI pipe light grade for protection of earth strip from earth electrode to test point 20mm dia GI pipe medium grade connected to funnel heavy wire mesh for watering purpose including necessary excavation and earth work PCC (1:2:4) type B1 for earth pit 10mm thick cast iron cover with angle iron frame all as specified and shown in electric plate Nos 3 SSR Pt-I connected to earthing test point all as specified or indicated including testing on completion and taking down old earthing. Note:- (i) Cost of GI earth strip/wire and GI protection pipe upto 7.5 Mtr length shall abe deemed to be included in the rate quoted for this item.
M&L for earthing with copper earth plate electrode 600x600x3.15mm size burried directly in ground to depth not less than 2.25m below ground level with top edge of the plate not less than 1.5 mtr below normal ground level surrounded with char coal and common salt filling in alternative layers of 15cm thick and connected to copper earth strip 25x3 mm by means of nuts/bolts and washers etc made out of galvanized iron including 40mm dia GI pipe light grade for protection of earth strip from earth electrode to test point 20mm dia GI pipe medium grade connected to funnel heavy wire mesh for watering purpose including necessary excavation and earth work PCC (1:2:4) type B1 for earth pit 10mm thick cast iron cover with angle iron frame all as specified and shown in electric plate Nos 3 SSR Pt-I connected to earthing test point all as specified or indicated including testing on completion and taking down old earthing. Note:- (i) Cost of GI earth strip/wire and GI protection pipe upto 7.5 Mtr length shall abe deemed to be included in the rate quoted for this item.
Supply and fix in Replacement test point terminal block made of gun metal or phosphorus bronze size 75x75x25 mm, drilled and screwed including 3 nos. 8 mm dia 25 mm long hex. Head screw all as specified and as directed incl taking down oldtest point all as specified and directed..
Supply and fix in Replacement air termination, single pointed aluminium rod 12 mm dia and 300 mm long incl taking down old aluminium rod all as specified and directed..
Supply and fixing Aluminium strip 25 x 3mm with and including ceramic/porcelain vitreous insulator (at not more than 100cm c/c) for base of suitable size and saddles and fixing screws, nut bolts with washer etc. for fixing the strip on roof surface/along wall surface or drawn through pipe as earth grid and down conductor of lightening protection system of building/ESHs at any height complete all as specified and as directed by Engineer-in-Charge.
Supply and fix in Replacement copper strip 20 x3.15 mm including ceramic/porcelain vitreous insulator (at not more than 100cm c/c) for base of suitable size and saddles and fixing screws, nut bolts with washer etc. for fixing the strip on roof surface/along wall surface or drawn through pipe as earth grid and down conductor of lightening protection system of building/ESHs at any height complete all as specified and as directed by Engineer-in-Charge.
Supply and fix in Replacement GI strip 25X4 mm with saddles and fixing screws etc. for main earth lead above ground level incl taking down old strip all as specified and directed.
Supply and fixing white porcelain ceramic insulator with nut, bolt and washers for fixing eathing strip on wall/ceiling/roof all as directed incl taking down old unserviceable insulator.
M&L for New earthing pit by making cement concrete pit PCC 1:3:6 type C2 with RCC precast slab 80mm thick with handle for lifting made out of 8 mm dia MS rod specified in plate No -02 of SSR part-I after dismantling of brakon pit one complete all as specified and directed.
S&F light grade GI tubing size of 40mm bore including bend , socket , tee with proper MS clamp, screw fixed to wall for pipe complete to all as specified and directed
Note:- (i) Necessary safety measures to be taken by the contractor while taking down and fixing the materials. (ii) Any damage to govt property while executing the work is to be make good by the contractor. (iii) The cost of scaffolding arrangement laddars,safety belt,lifting ,Nut bolt, drilling , rowl plug and T&P in all respect used while fixing the materials will borne by the contractor himself. (iv) Taking down all materials will be deposited at the E/M store of AGE E/M-IV (v) The above said work based on daily complaint based work and contractor as to take daily complaint from MES complaint cell and concern JE (E/M) on daily basis. (vi) Contractor has to attand the complaint within 24 hours after received complaint from from JE (E/M).
m/s s.n. builders (BID ID -3196541)
Aman Enterprises (BID ID -3186778)
NISHTHA BUILDERS (BID ID -3195616)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .