MS
MS OFFICE SSH UDAIPUR
SITC OF ESE TYPE 03 LIGHTING ARREST0R
2026_RNTMC_599988_1
63
Open Tender
Electronics Equipment
Item Wise
90 days
MS OFFICE
SITC OF ESE TYPE 03 LIGHTING ARREST0R
3 documents required · 3 mandatory
₹500
MS RMRS SSH
₹23,000
Yes
MS OFFICE SSH UDAIPUR
24 Sept 2026
24 Sept 2026
6 Oct 2026
24 Sept 2026
5 Oct 2026
27 Sept 2026
25 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1SITC OF ESE TYPE 03 LIGHTING ARRESTORS | |||||
| 1.01 | Plate Earthing as per IS:3043 with copper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying 3 mtr. Below the ground level with 20 mm dia. G.I. ‘B’ class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 Kn of round / square size 250 mm, and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required. | 1 | PER SET | - | - |
| 1.02 | Supply & Laying following size’ B ‘ class , G.I. Pipe confirming to IS : 1239 P – 1 ( 2004 ) with accessories like bend, socket etc. for laying earth conductor/ strip / cable in ground/ surface/ recess as required. (Earth Excavation will be Paid Extra) 25 mm dia. | 1 | PER SQMTR | - | - |
| 1.03 | Lightning Surge Counter designed to record and display lightning strike events. The counter shall feature a 3 digit LCD screen (0-999 events) for clear event tracking and operate on a battery powered system. | 1 | Each | - | - |
| 1.04 | Supply, installation, and testing of an Early Streamer Emission (ESE) Air Terminal, designed and tested in accordance with NFC 17-102 standards, with Delta T ( Initiation Advance ) time tested and certified by an ILAC-accredited high-voltage test laboratory. The air terminal shall be constructed from corrosion-resistant materials to ensure durability and long-term performance. It shall be installed at the highest point of the structure and mounted on a mast of minimum 5.5 meters or as determined by the initiation advance time (ΔT) calculations, ensuring the required protection radius. The protection radius shall be determined as per NFC 17-102, based on the level of risk protection required (Levels I to IV), with proper Earthings integration for effective lightning dissipation. ES-60 Triggering Advance Time (ΔT) -60µs, Protection Radius (meters) as per Highest Risk 79 Mtr. | 1 | Each | - | - |
| 1.05 | Supply, fabrication, and installation of a galvanized iron (GI) pipe support structure ( Lightning Mast ) with a 350 mm × 350 mm base plate and 10 mm thickness for secure mounting. The mast shall support the ESE air terminal and include provisions for a guy wire clamping system to ensure stability. It shall provide a secure arrangement for fixing the air terminal and have appropriate termination point / arrangement for connection to the down conductor. Total Mast height : 8-10 meter | 1 | Each | - | - |
| 1.06 | Supply and installation of an 8 mm aluminum down conductor, designed for efficient dissipation of lightning currents. The conductor shall be securely fixed using corrosion-resistant clamps at appropriate intervals, ensuring a continuous, low-resistance path from the air terminal to the earthing system. The conductor length shall be determined based on actual site conditions, with all necessary accessories, including clamps, connectors, and fasteners. | 1 | PER SQMTR | - | - |
| 2SPECIFIACATION AS PER TENDER DETAILS ( technical specation sheet page no 23 to 25) | |||||
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.64 MB
BOQ_1063497.xls
BOQ • 0.28 MB
aresster_merged.pdf
Tender Documents • 2.94 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .