| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.3 CrAccepted-AOC | ₹7.3 Cr | L1 | Accepted-AOC Lowest Bidder |
| 2 | L2₹7.8 Cr+₹50.6 L (6.91%)Rejected-Finance 2ND FLOOR 15 BHULLAR AVENUE ADJOINING SBI FATEHGARH CHURIAN ROAD AMRITSAR PUNJAB 143001 | AMRITSAR | AMRITSAR | PUNJAB | 143001 | ₹7.8 Cr+₹50.6 L (6.91%) | L2 | Rejected-Finance Other than lowest Bidder |
| 3 | L3₹8.1 Cr+₹77.2 L (10.6%)Rejected-Finance | ₹8.1 Cr+₹77.2 L (10.6%) | L3 | Rejected-Finance Other than lowest Bidder |
| 4 | L4₹8.9 Cr+₹1.6 Cr (21.2%)Rejected-Finance | ₹8.9 Cr+₹1.6 Cr (21.2%) | L4 | Rejected-Finance Other than lowest Bidder |
Tender Value
Refer Docs
EMD Value
₹7.1 L
Closing Date
21 Jul 2021, 6:00 pmClosed
Chief Engineer Pathankot Zone
HQ Chief Engineer Pathankot Zone
ADDN ALTN AND UPGRADATION OF 16xJCOS MD ACCN AT 34 MED REGT AREA 40xOR MD ACCN AT MMG AREA 24xOR MD ACCN AT 9 FARU AREA 80xOR MD ACCN AT ABROL NAGAR 08xOFFRS MD ACCN AT TRIVENI VIHAR AND 10x OFFRS MD ACCN AT NORTH COLONY AT MIL STN PATHANKOT
2021_MES_442297_1
CEPZ-13/2020-21
Open Tender
Civil Works
Item Rate
548 days
GE (West) Pathankot
As per Tender documents
8 documents required · 8 mandatory
₹3,000
GE (West) Pathankot
₹7.1 L
9 Nov 2021
12 May 2021
23 Jul 2021
12 May 2021
21 Jul 2021
7 Jul 2021
12 May 2021 - 19 May 2021
Amount
Demolition of brick work , built in cement mortar or cement lime mortar including all quions, arches, pillars, etc including demolition of precast RCC articles and disposal of debris out of MoD land complete all as specified and directed.
M&L Brickwork with fly ash old size bricks, straight or curved on plan exc 6m mean radius, built in CM (1:6) complete all as specified and directed.
All as per item No 02 here-in-before but except bricks. NOTE:- Old serviceable burnt clay bricks retrieved from demolition shall be used.
M&L Brickwork with fly ash old size bricks, straight or curved on plan to any radius in half brick thick walls built in CM 1:4 complete all as specified and directed.
All as per item No 04 here-in-before but except bricks. NOTE:- Old serviceable burnt clay bricks retrieved from demolition shall be used.
Demolition of cement concrete or lime concrete (unreinforced) in ground floors and Pavings not exc 15 cm thick (below or above ground level ) and removing the debris outside from defence land complete all as specified and directed .
Surface dressing not exceeding 15 cm deep in any type of soil complete all as specified and directed .
M&L for hard core of broken stones or boulders of gauge not exc 63mm, deposited, spread and levelled in layers not exc. 15 cm thick, watered and rammed to a true surface complete all as specified and directed
M&L for PCC 1:3:6, type C-1 (using 20mm graded crushed stone aggregate) as in plinth protection and paving 75mm thick, laid in slope finished even and fair including making joints at every 2.5 m and at corner filled with bitumen grade 85/25 and sand in ratio 1:2 by weight and complete all as specified.
M&L for 25mm thick Cement concrete in sub base for receiving floor tiles and mass concrete using Type B-1,1:2:4 (using 20 mm graded crushed stone aggregate) complete all as specified and directed. Note:- Finishing surfaces of concrete to be even and rough to receive the topping layer or floor tiles etc
M&L 40 mm thick PCC type B-1 , 1:2:4 (using 20 mm graded crushed stone aggregate) finished even and smooth without using extra cement as in flooring complete all as specified and directed. Note:- Glass dividing strips shall be measured & paid separately as supply only.
Supply only 38 mm wide and 3 mm thick glass dividing strips in flooring by fixing in position and making square or rectangle for casting concrete in flooring complete all as specified and directed.
Demolition of cement concrete or lime concrete (unreinforced) of any description and in any position not otherwise specifically provided for and removing the debris outside from defence land complete all as specified and directed .
M&L for PCC 1:4:8 type D-2 (1:4:8) using 40 mm graded crushed stone aggregate in foundations, filling and mass-concrete complete all as specified and directed.
M&L PCC 1:2:4, type B-0, (using 12.5 mm graded crushed stone aggregate) mixed with water proofing compound as per manufacturer’s instructions as in padding on roof, surface finished even and smooth without using extra cement all as specified and as directed. (Note:- WPC shall be measured and paid separately)
M&L PCC1:2:4, type B-1, (using 20 mm graded crushed stone aggregate) mixed with water proofing compound as per manufacturer’s instructions as in roof kerbs,bands etc or mud stops, rounded or chamfered on edges cement all as specified and as directed. (Note:- WPC shall be measured and paid separately)
M&L for PCC1:3:6 Type C-1 ,M-10 (Nominal mix) using 20mm graded crushed stone aggregate as in filling of sunken floor to receive floor top finished complete all as specified and directed.
M&L for (a) 15mm thick plaster in CM (1:4) mixed with water proofing compound (conform to IS 2645-Specifictions for integral cement water proofing compound) as approved as per manufacturer’s instructions shall be applied both on floor and wall. The surfaces then shall be cured and allowed to dry. All the joints of pipe shall be sealed properly as per the instruction of agency who is carrying out water proofing treatment. (b) Apply a coat of Moisture Cured High Tensile Elastomeric Modified Poly Urethane Based Liquid Membrane on floor as well as on wall as per manufacturer’s instructions ofmake/manufacturers. After the treatment is over, sunkenportion shall be kept full of water for atleast one week to check that no seepage is seen from the external surface. (c) Manufacturer/approved agencies for water proofing treatment to sunken slab/portion membrane shall be as per approved list
M & L for GI pipe 50 mm bore ‘medium grade’ as in spout including neccesary cutting to wall/beam etc and proper setting in cement moratr 1:3 , complete all as specified..
Dismantling Brick tiles or terracing tiles, single layer on roofs and disposal of debris out of MoD land complete all as specified and directed.
M & L for 40mm thick brick tiles laid on cement mortar & joints grouted flush in cement mortar 1:3 mixed with 5% of crude oil by weight of cement over and including 15mm thick screed bed or bedding layer of mortar in CM 1:6 etc complete all as directed.
Fixing only 40mm thick brick tiles laid on cement mortar & joints grouted flush in cement mortar 1:3 mixed with 5% of crude oil by weight of cement over and including 15mm thick screed bed or bedding layer of mortar in CM 1:6 etc complete all as directed. All as per item No 21 above but except bricks. NOTE:- Old serviceable burnt clay brick tiles retrieved from dismantling shall be used.
Demolition of existing roof treatment of any description such as worn-out tar felt, debris, mortar of any description & any thickness, surface cleaning of all foreign material such as fungus, moss, dust etc. by wire brushing and dusting including disposal of debris out of MoD land then surface levelled with a layer of 20 mm thick screed bed in CM 1:4 including mixed with water proofing admixture as per manufacturer's instructions and ensure water does not stand anywhere after Sprinkle water on the roof surface and M&L for APP modified roof treatment over existing accessible RCC roof slab / chajjah / canopy / parapet wall to be executed through approved applicator of the membrane manufacturer with following specifications complete all as specified and directed :- (a) Cleaning existing surface properly. (b) Applying oil bound bitumen primer @ 0.30 liter/Sqm manufacture by the same agency as that of APP with a density 0.87-0.89 Kg per litre at 25 degree centigrade on prepared surface. (c) Laying not less than 3mm thick APP modified water proofing membrane weighing not less than 3.60 Kg/Sqm reinforced with non woven polyster fiber weight not less than 160gram/Sqm using butane torch by torch application with 10cm side laps and 15cm end lap. Laying of membrane. (d) APP membrane shall be laid using butane torch by Torch application with minimum 10cm side overlap and 15cm end lap.
Demolition of existing roof treatment of any description such as worn-out tar felt, debris, mortar of any description & any thickness, surface cleaning of all foreign material such as fungus, moss, dust etc. by wire brushing and dusting including disposal of debris out of MoD land then surface levelled with a layer of 20 mm thick screed bed in CM 1:4 including mixed with water proofing admixture as per manufacturer's instructions and ensure water does not stand anywhere after Sprinkle water on the roof surface including Applying roof treatment on top of roof with APP modified membrane with non–woven polyster reinforcement/mat (centre core) with thermal insulation with white mineral gravel finish on upper side of weight not less than 3.60 Kg/Sqm & thickness not less than 3mm, laid by torch application method with overlap 100mm on length side and 100mm on the width side as per manufacturer’s instructions over a coat of approved cold applied bituminous oil based primer (IS-3384) @ 0.30 Litre/Sqm complete all as specified.(Note:- WPC shall be measured and paid separately) Note:- (a) Cleaning existing surface properly. (b) Applying oil bound bitumen primer @ 0.30 liter/Sqm manufacture by the same agency as that of APP with a density 0.87-0.89 Kg per litre at 25 degree centigrade on prepared surface. (c) Laying not less than 3mm thick APP modified water proofing membrane weighing not less than 3.60 Kg/Sqm reinforced with non woven polyster fiber weight not less than 160gram/Sqm using butane torch by torch application with 10cm side laps and 15cm end lap. Laying of membrane. (d) APP membrane shall be laid using butane torch by Torch application with minimum 10cm side overlap and 15cm end lap.
M&L for cutting out cracks to V-Section in existing roof or terracing, cleaning out and filling solidly with a hot mixture of bitumen and clean dry sand 1:1 by weight complete all as specified and directed.
Dismantling floor, hearth or wall tiling including cement mortar bedding ( but not backing) removing serviceable tiles to store and rubbish off the premises and removing the debris outside from defence land complete all as specified and directed .
M&L 20mm thick granite (pure black) work (table rubbed and polished) in steps, jambs pillars, window cills ,cooking platform and like including pointing in white cement (1:2) using marble dust with admixture of pigments to match with shade or granite over including 15mm thick screed bed or bedding layer in cement mortar 1:6 etc complete all as specified and directed. Note:- The stone slab shall be in one piece over kitchen plateform,window cill and making gas pipe holes 25mm dia with rounded holes and all open edges to be half rounded.
Material and labour for coloured Glazed ceramic tiles in vertical surface such as dado etc 450mmX 300mmX 7mm thick set and jointed in neat cement slurry and pointed in white or colour cement to match the shade of the tiles over and including 10mm thick rough cement plaster to receive tiles in CM 1:4 complete all as specified and as directed. Note:-The texture ,colour ,Shade of tiles & laying of tiles to any pattern & any design with one or more colours shall be approved by GE and Rates also including in this item for necessary raking circular cutting or notching and waste on tiles.
Supply and fix joint free non skid coloured Ceramic tiles 07mm to 08mm thick (square/ rectangular) polished, area of each tiles exceeding 0.11 Sqm but not exceeding 0.18 Sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match over and including 15mm thick screed bed in CM 1:4 complete all as specified and directed. Note:-The texture ,colour ,Shade of tiles & laying of tiles to any pattern & any design with one or more colours shall be approved by GE and Rates also including in this item for necessary raking circular cutting or notching and waste on tiles.
Supply and fix joint free non skid coloured Ceramic tiles 10 mm thick (square/ rectangular) polished, area of each tiles exceeding 0.18 Sqm but not exceeding 0.38 Sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match over and including 15mm thick screed bed in CM 1:4 complete all as specified and directed. Note:-The texture ,colour ,Shade of tiles & laying of tiles to any pattern & any design with one or more colours shall be approved by GE and Rates also including in this item for necessary raking circular cutting or notching and waste on tiles.
Supply and fix joint free non skid Ceramic tiles, coloured 7mm to 8mm thick (square/ rectangular) polished, area of each tiles exceeding 0.18 Sqm but not exceeding 0.38 Sqm in vertical/skirting etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match including 10mm thick backing coat/redering in cement mortar 1:4 for fixing of tiles complete all as specified and as directed. Note:-The texture ,colour ,Shade of tiles & laying of tiles to any pattern & any design with one or more colours shall be approved by GE and Rates also including in this item for necessary raking circular cutting or notching and waste on tiles.
Roughening surfaces of old concrete floor by picking, sweeping clean and washing down with water to remove dust, etc.& Brushing neat cement slurry with 3.0kg of cement per Sqm complete all as specified and directed.
Supply and fix Vitrified Ceramic tiles 10 mm thick light shade (square/ rectangular) polished, area of each tiles not exceeding 0.36 sqm in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match over and including 15mm thick screed bed in CM 1:4 complete all as specified and directed. Note:-The texture ,colour ,Shade of tiles & laying of tiles to any pattern & any design with one or more colours shall be approved by GE and Rates also including in this item for necessary raking circular cutting or notching and waste on tiles.
Supply and fix Vitrified Ceramic tiles 10 mm thick light shade (square/ rectangular) polished, area of each tiles not exceeding 0.36 sqm in vertical/skirting etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match the shade of the tiles over and including 10mm thick rough cement plaster to receive tiles in CM 1:4 complete all as specified and as directed. Note:-The texture ,colour ,Shade of tiles & laying of tiles to any pattern & any design with one or more colours shall be approved by GE and Rates also including in this item for necessary raking circular cutting or notching and waste on tiles.
M & L machine cut kota stone slab flooring 18-20mm thick over cement screed base laid and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and mirror polishing complete over screed bed or bedding layer 20 mm thick in cement mortar 1:4, complete all as specified and as directed. Note :- Rate included for all cutting ,waste including machine cutting to make it square or rectangular,cutting and polishing by machine & size of kota stone shall not be less than 550 mmx550mm .
M & L machine cut kota stone slab 14 to 16mm thick in riser of steps, skirting, dado and pillar laid over backing coat 10mm thick in CM 1:4 and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and mirror polishing complete all as specified and as directed. Note :- Rate included for all cutting ,waste including machine cutting to make it square or rectangular,cutting and polishing by machine & size of kota stone shall not be less than 550 mmx550mm .
Demolition of Roofs, floors (other than ground floors), beams staircases, landing, cooking platform ,chajjas, & similar suspended work cement concrete is reinforced (reinforcement cut as required to facilitate demolition) and disposal of debris out of MoD land complete all as specified and directed. Note:- Demolition will be done only by mechanical cutter only .
Material and labour for RCC type B-1 (1:2:4) using 20 mm graded aggregate in Slabs supported on walls, beams and columns in floors, roofs, landings, blaconies, canopies, deck slabs and in shelves and the like such as cover slab of septic tank/soak well etc complete all as specified and as directed. Note:- Reinforcement shall be measured and paid separately).
Formwork to soffits of suspended slabs such as roof slabs, floor slabs, landings & similar work; not exc. 200mm thick (Horizontal or sloping) Rough finished surfaces of concrete flat complete all as specified and as directed
Material and labour for Mild steel TMT bars 10mm dia & over,cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends & binding with & including mild steel wire (annealed) not less than 0.9mm dia or securing with clips quality complete all as specified and as directed.
Taking down cement plaster of any description and thickness on walls/ceilings etc including racking out joints, hacking for key, scrubbing down with water etc including necessary scaffolding and removing of debris out of MoD land complete all as specified and as directed.
Material and labour for rendering 15mm thick in CM 1:4 mixed with liquid water proofing compound (as per manufacturer’s instructions) on fair faces of brick work ,concrete surface of wall, fin, facia, chajjas, parapet and similar article finished surface even and smooth without using extra cement including necessary scaffolding complete all as specified and as directed. (Note:- WPC shall be measured and paid separately)
Material and labour for two coat plaster 15 mm thick (10 mm + 5 mm) on rough concrete surfaces of fin, facia, chajjas and similar article in CM 1:3 with liquid water proofing compound (as per manufacturer’s instructions) mixed in both coats, finished even and smooth without using extra cement including necessary scaffolding complete all as specified and as directed. Note:- (i) WPC shall be measured and paid separately) (ii) Two coat plaster shall be carried out as mentioned in clause 14.18 of SSR-2009, Part-I complete all as specified and directed.
Material and labour for preparation of newly plastered external surfaces of wall and applying two coats of exterior grade emulsion paint (weather proof/weather coat) without any brush marks on the surface in any colour over and including one coat of primer (as per manufacturer’s recommendations) including necessary scaffolding, Shade/colour shall be approved by GE, all painted area site to be cleaned and hand over as earlier without any extra cost to Govt complete all as specified and as directed.
Material and labour for complete removal of existing treatment surface externally of wall and applying two coats of exterior grade emulsion paint (weather proof/weather coat) without any brush marks on the surface in any colour over and including one coat of primer (as per manufacturer’s recommendations) including necessary scaffolding , Shade/colour shall be approved by GE, all painted areas site to be cleaned and hand over as earlier without any extra cost to Govt complete all as specified and as directed.
Material and labour for repairing of chajjas, roof projection and faces of exposed reinforcement surface or damaged loose RCC surface and applying one coat of cement slurry @3kg/Sqm and filling with cement concrete 1 : 2 :4 type B-0 (using 12.5 mm graded crushed stone aggregate ) mixed with liquid water proofing compound (as per manufacturer’s instructions) and finished 05mm thick rendering with cement sand mortar 1 : 3 with liquid water proofing compound (as per manufacturer’s instructions) using coarse sand in patch area not exc 1.00 sqm each and thickness of RCC member not exc 150 mm and reinforced with Welded steel wire fabric supplied and fixed of weight exc 2.00 Kg per sqm but not exc 4.00 Kg per sqm and finally applying two coats of exterior grade emulsion paint (weather proof/weather coat) without any brush marks on the surface in any colour over and including one coat of primer (as per manufacturer’s recommendations) including necessary scaffolding , Shade/colour shall be approved by GE, all painted areas site to be cleaned and hand over as earlier without any extra cost to Govt complete all as specified and as directed.
Material and labour for rendering 10 mm thick in cm 1:6 on other than fair faces of brick work , concrete surfaces of wall,finishing surfaces even and smooth without using extra cement including necessary scaffoldingcomplete all as specified and as directed.
Material and labour for preparation of newly plastered internally surfaces of wall and applying min 1.5 mm thick wall care putty on the surfaces & making the surface absolutely smooth surface and applying one coat of primer (as per manufacturer’s recommendations) on the surfaces and applying two coats of distemper oil emulsion finished without any brush marks on the surface in any colour including necessary scaffolding ,Shade/colour shall be approved by GE,all painted areas site to be cleaned and hand over as earlier without any extra cost to Govt complete all as specified and as directed.
Material and labour for preparation of newly plastered internally surfaces of wall and applying one coat of primer (as per manufacturer’s recommendations) on the surfaces and applying two coats of distemper oil emulsion finished without any brush marks on the surface in any colour including necessary scaffolding Shade/colour shall be approved by GE,all painted areas site to be cleaned and hand over as earlier without any extra cost to Govt complete all as specified and as directed.
Material and labour for complete removal of existing treatment internally surface of wall and applying min 1.5 mm thick wall care putty on the surfaces and making surface absolutely smooth and applying one coat of primer (as per manufacturer’s recommendations) on the surfaces and applying two coats of distemper oil emulsion without any brush marks on the surface in any tint including necessary scaffolding, Shade/colour shall be approved by GE,all painted areas site to be cleaned and hand over as earlier without any extra cost to Govt complete all as specified and as directed.
Material and labour for complete removal of existing treatment internally surface of wall and applying one coat of primer (as per manufacturer’s recommendations) on the surfaces and applying two coats of distemper oil emulsion without any brush marks on the surface in any tint including necessary scaffolding ,Shade/colour shall be approved by GE,all painted areas site to be cleaned and hand over as earlier without any extra cost to Govt complete all as specified and as directed.
M&L Rendering 5mm thick on fair faces of brick work or concrete surfaces in CM (1:3) in ceiling complete all as specified and as directed.
Material and labour for preparation of newly plastered surfaces of ceiling and applying three coats of white wash without any brush marks on the surface including necessary scaffolding complete all as specified and as directed.
Material and labour for complete removal of existing treatment from ceiling surface and applying two coat of white wash on undecorated surfaces without any brush marks on the surface including necessary scaffolding complete all as specified and as directed.
Material and labour for preparation of old painted steel and iron surfaces of any description over 10 centimeter width or girth and applying one coat of synthetic enamel paint in any colour finished without brush mark on surface including necessary scaffolding ,Shade/colour shall be approved by GE,all painted areas site to be cleaned and hand over as earlier without any extra cost to Govt complete all as specified and as directed.
M&L for preparation of new steel surfaces of any description over 10 cm width or girth and applying two coats of synthetic enameled paint over a coat of red oxide primer all as specified and directed.
Material and labour for writing letters or figures (block, Roman, Italic or Indian) exceeding 15 centimeter high but not exceeding 30 centimeter high etc with synthetic enamel paint including necessary scaffolding ,Shade/colour shall be approved by GE,all painted area site to be cleaned and hand over as earlier without any extra cost to Govt complete all as specified and as directed.
Material and labour for Stops, commas, short lines, dashes, hyphens, brackets, etc. including necessary scaffolding ,Shade/colour shall be approved by GE,all painted area site to be cleaned and hand over as earlier without any extra cost to Govt complete all as specified and as directed.
Material and labour for obliterating the old writing of any description, not exceeding 0.1 square meter, with paint to match with the existing work including necessary scaffolding ,Shade/colour shall be approved by GE,all painted areas site to be cleaned and hand over as earlier without any extra cost to Govt complete all as specified and as directed.
Material and labour for cutting down plants / trees of girth not exc 15 cm & surface area not exceeding 0.36 Sqm each from roof tops /sides of external walls of buildings, chajja, wall junctions, junctions of of rain water / soil /waste vent pipes including taking out roots entered in wall/slab surfaces and making good the surfaces including repairing the CI/GI/PVC joints of affected locations by applying TUFALO (herbal medicine )and making good to suit the adjoining surfaces using PCC type 1:2:4, type B-O or cement mortar 1:2 complete all as per manufacturer instructions and as specified. NOTE: Any CI/GI/PVC pipes and fittings damaged during work shall be replaced by new one to insure leakage / seepage free joint without any extra cost to the department and Unit rate quoted by tenderer shall included for use of all scaffolding, trestles, ladders, cradles etc ,hoisting, lowering and protective measures etc up to four storeys height of bldgs and removing of debris out of MoD land complete all as specified and as directed.
Supply only `Liquid Water Proofing Compound. complete all as specified and as directed .
Taking down chowkhats or frames exc 1.50 and n.exc 4 Sqm each (without taking off shutters from the frame) complete all as specified and directed.
Taking down chowkhat or frames with shutters (without taking off shutters from the frames) area not exc1.5 Sqm each and removing from site.
Taking down shutters of any description exc 1 sqm but not exc 2 sqm each and removing from site complete all as specified and directed.
S & F pressed steel frames 105 x 60 x1.25 mm with one or more rebates including necessary fixing lugs/hold fast duly tarred with bitumen and sanding with sharp clean sand, hinges, lock strike plate including one shop coat of primer complete all as spd and directed
S & F pressed steel frames 125 x 60 x1.25 mm with one or more rebates including necessary fixing lugs/hold fast duly tarred with bitumen and sanding with sharp clean sand, hinges, lock strike plate including one shop coat of primer complete all as spd and directed
M & L for cement concrete type C-0, 1:3:6 using 12.5 mm graded crushed stone aggregate as in back filling of hollow portion of frame with plain cement concrete and for fixing of hold fast complete all as specified and directed.
S&F 40mm thick factory made Flush shutters, solid core construction, with block board core and plywood face panels, commercial type on both sides, confirming to IS- 2202(Part-I-1999) , ISI Marked complete all as specified and directed
S&F 35mm thick factory made 2nd class hard wood Glazed and skeleton shutters, open rebated and prepared to receive glass, gauze, etc. (without sash bars), edges of framing plain,chamfered or rounded. fitted with cut and mitred beads for securing glass,etc.; sizes of members of shutters as specified in SSR Part I, Section 8, clause 8.24 (a); supplied and fitted to chowkats Note: wire cloth shall be measured separately
S&F stainless steel wire cloth 0.36mm nominal dia of wire and average width of aperture 1.18mm and fixed with stainless steel wire staples or using metal nut and bolts complete all as specified and directed.
M&L for preparation of new wooden surfaces of any description over 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of pink primer all as specified.
S&F Solid PVC Door Frame of size 50mm x 47mm made out of 5mm wood grain printed PVC sheet & edges will be painted to match with printed sheet ,reinforced with M.S. Square tube, suppling & fixing in opening as per specification & drawing complete all as specified and directed.
S&F Factory made solid panel PVC door shutter 30 mm thick (style) consisting of frame made out of M.S. tubes for top & bottom rails. M.S. frame shall be covered with heat moulded wood grain printed PVC sheet PVC ‘C’ channel having a PVC sheet strip of 20mm width stuck inside with solvent cement for stiles and wood grain printed PVC sheet for top rail,lock rail & bottom rail on either side & as gap insert for top rail & bottom rail;Panelling of wood grain printed PVC sheet to be fitted in the M.S. frame welded / sealed to the stiles & rails with suitable & 5mm thick x15mm wide PVC sheet beading used inside stiles and rails and decorative PVC beading of 10mm x 10mm (900 ) used instead of exposed portion of PVC sheet beading suppling & fixing in the frame at site as per specification & drawing complete all as specified and directed.
S&F Steel window/ventilator factory made, made out of mild steel box type and shutter suitable for double shutter i.e. Glazed and gauged shutter. Glazed shutter made out of hollow' section with sash bar and gauged shutter made out of hollow section without sash bar including hinges, tower bolt, handle, grill 10 mm sq bar including two coat of synthetic enamel paint over one coat of red oxide primer, tarred hold fasts, PCC bed blocks for fixing hold fast, including plain/figured glass and stainless steelwire cloth 0.36mm nominal dia of wire & average width of aperture 1.18mm & fixed with stainless steel wire staples` complete all as per details shown in drawing No CEPZ/C-TD/032/13 sheet No 1/2 & 2/2 including taking down existing spoiled and unserviceable windows/ventilators of any type ( wooden/steel) complete all as specified and directed
S&F 2nd class Hardwood Plain, solid, straight chowkats and frames, wrought, framed rebated on the solid, rounded or chamfered, put together with glue pinned at joints, supplied and fixed complete all as specified and directed.
M&L for 18 to 20 mm thick PVC prelaminated solid board with one side decorative choice laminate and other side balancing white including 3mm thick lipping and equal to thickness of board as in kitchen cabinet, cupboard etc fixed with screws to steel/timber frame work etc complete all as specified and directed.
S&F for Ball catches with 8mm dia steel ball, and brass body and striking plate including letting in and fixed complete all as specified and directed.
S&F 40mm dia, cupboard knobs fixed with nut, screw and washer of brass, polished complete all as specified and directed
S&F hasp and staple, safety type, brass with mild steel hinge pin including bolt to hinge plate and fixed with screws, Size of hasp and staple in mm 100 complete all as specified and directed.
S & F Continuous (piano) hinges 30mm Width of flaps (when open) ,mild steel, bright finish or electrogalvanised complete all as specified and directed
S&F medium weight stainless steel butt hinges of size 100mm long for fixing of pvc door shutter etc complete all as specified and directed.
S&F Aluminium, anodised, barrel tower bolts of extruded section and fixed, Length of bolt in 150mm complete all as specified and directed
S&F , anodised, barrel tower bolts of extruded section and fixed, Length of bolt in 200mm complete all as specified and directed
S&F Aluminium handles, cast type, anodised Size of handle in 150mm complete all as specified and directed.
S&F Aluminium alloy, anodised, sliding door bolt with hasp, staple (bolt type) and fixing clips of sheet, cast or extruded sections and fixing bolts and sliding bolts of extruded sections or castaluminium alloy and fixed Length of bolt in 250 mm complete all as specified.
S&F Floor door stopper of aluminium alloy body and tongue, anodised, with hard drawn steel spring. Fixed in floor Overall length of cover plate 140mm complete all as specified and directed.
S&F 300mm, mild steel ordinary rat tail rod pattern springs including roller and roller plate including welding to steel frames.complete.
S&F in repair 25mm outer dia stainless steel decorative drapery rod ( Model No- SS-25FL of Vista) of thickness 20 gauge and for every 01 RM length, provide 10 numbers stainless steel rings (Model No:- SS CRNG of Vista) with 50 mm dia and proportionate for part there off, with stainless steel brackets ( Model:- SS 25 BR, Vista) near to ends with stainless steel finials ( Model:- SS-1 of Vista with adapter) for 25mm dia drapery rod at both ends. The drapery rod shall be projecting 150 mm outer side from the clear opening of doors/ windows. ( Including necessary fittings) complete all as specified and directed.
Welding in repairs n. exc 2.5cm in length thickness of metal to be welded n exc 6mm complete all as specified and directed.
Welding in repairs exc 2.5cm but n exc 5cm in length thickness of metal to be welded exc 6mm but n exc 9mm complete all as specified and directed.
S&F peg set of 4, brass chromium plated, fancy type, superior quality and fixed with screws complete all as specified and directed.
S&F brass door magic eye: as given specification material resin lens +zinc alloy,top diameter: 31.2mm, botom diameter approx 24mm, pipe diameter approx 16mm total length approx 50mm, inner height approx 36mm application 35 to 60mm thick viewing angle 200 degree of surrounding without opening the door unique design ultra clear view and superior finish, wide angle best in class lens for all round visibility the outsider cannot hide any ware, the back cover protects you from the outsider observing any movements inside easy to instal with inbuilt screw over a wide range of door thickness from 35 mm to 60mm etc required at site complete all as specified and directed.
S&F solid chromium plated heavy door chain (weight not less than 249 gms) with brass screws to any type of door shutter and frame complete all as specified and directed.
Taking up or down 15mm bore, steel tubing and connection including cleaning for refixing or removal from site complete all as specified and directed.
S&F 15mm bore Steel water tubing 'medium grade', galvanised with all fittings like elbow, tee, socket, bend etc and fixed to wall, ceiling or laid in floor complete all as specified and directed.
Fixing only 15mm bore old Steel water tubing including all new galvanized fittings like elbow, tee, socket, bend etc and fixed to wall, ceiling or laid in floor complete all as specified and directed. Note: - Old Steel water tube/pipe any type retrieved from taking down shall be used along with all new GI fittings)
Taking up or down 20mm bore, steel tubing and connection including cleaning for refixing or removal from site complete all as specified and directed.
S&F 20mm bore Steel water tubing 'medium grade', galvanised with all fittings like elbow, tee, socket, bend etc and fixed to wall, ceiling or laid in floor complete all as specified and directed.
Fixing only 20mm bore old Steel water tubing including all new galvanized fittings like elbow, tee, socket, bend etc and fixed to wall, ceiling or laid in floor complete all as specified and directed. Note: - Old Steel water tube/pipe any type retrieved from taking down shall be used along with all new GI fittings)
Cutting chases in brick walls, pinning in, making good to facings where required and pointing in cement mortar 1:3 to ends or edges of landings, steps, cills, shelves, lintels, etc, and cutting chases for concealed water tubing or conduit wiring, etc and making good, cutting not exceeding 10cm girth complete all as specified and directed
S&F in repair Gun-metal, globe or gate valves 15mm bore, with iron wheel head, screwed both end for iron pipe complete all as specified and directed
S&F in repair Gun-metal, globe or gate valves 20mm bore, with iron wheel head, screwed both end for iron pipe complete all as specified and directed
S&F Rotational moulded polyethlene water storage tanks three layers of 500 ltrs capacity ISI marked (cylindrical vergical with closed top) hoisted and fixed in position all as specified in SSR Part I including Ball valves high pressure of PTMT with epoxy coated Aluminium rod & high-density plastic bal screwed for iron pipe and fixed. (Minimum weight 20mm-210 gms including Dismantling of old brocken water tanks and refixing of inlet, outlet & over flow pipe etc complete all as specified and as directed.
Fixing only existing Rotational moulded polyethlene water storage tanks three layers of 500 ltrs capacity ISI marked (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR Part I including Ball valves high pressure of PTMT with epoxy coated Aluminium rod & high-density plastic bal screwed for iron pipe and fixed. (Minimum weight 20mm-210 gms) including Dismantling of old brocken water tanks and refixing of inlet, outlet & over flow pipe etc complete all as specified and as directed.
S&F Rotational moulded polyethlene water storage tanks three layers of 1000 ltrs capacity ISI marked (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR Part I including Ball valves high pressure of PTMT with epoxy coated Aluminium rod & high-density plastic bal screwed for iron pipe and fixed. (Minimum weight 20mm-210 gms) including Dismantling of old brocken water tanks and refixing of inlet, outlet & over flow pipe etc complete all as specified and as directed.
Fixing only existing Rotational moulded polyethlene water storage tanks three layers of 1000 ltrs capacity ISI marked (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR Part I including Ball valves high pressure of PTMT with epoxy coated Aluminium rod & high-density plastic bal screwed for iron pipe and fixed. (Minimum weight 20mm-210 gms) including Dismantling of old brocken water tanks and refixing of inlet, outlet & over flow pipe etc complete all as specified and as directed.
S&F in repair Ball valves 20mm bore high pressure of PTMT with epoxy coated Aluminium rod & high-density plastic bal screwed for iron pipe & fixed. (min. weight 20mm-210 gms)
S&F in repair PVC tank lid/cover for water storage tank of 500 ltrs capacity with fixing arrangement complete all as specified and directed.
S & F in repair 15 mm bore long body CP Bib taps cast copper alloy fancy type with capstan heads (chromium plated),and cup screwed down , high pressure for iron pipe mpete all as spd & directed.
S&F in repair 15 mm bore Stop valves, fancy type, chromium plated cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed complete all as specified and as directed.
S&F in repair stop valves (ISI marked), 15mm dia, cast copper alloy,chromium plated fancy type with long shank and cup(concealed type) screwd down,high pressure with crutch or butter fly handle,screwed both ends for iron pipes or for unions and fixed in pipe all as specified and directed.
S&F in repairs Brass CP wash hand basin mixer for mixing hot & cold water screwed down for iron pipe and fixed for 15mm bore complete all as specified and as directed
S&F for in repairs CP Pillar taps fancy type 15 mm bore, cast copper alloy, with capstan heads screwed down high pressure, with or without lettered `Hot' or `Cold' with long screwed shanks & fly-nuts, screwed for iron pipe complete all as specified and directed.
Supply and fixed in repairs 15mm bore brass Wall Mixer 3-in-1 System with Provision for both Hand Shower and Overhead Shower Complete with 115mm Long Bend Pipe, Connecting Legs & Wall Flange mixing hot and cold water, screwd down for 15mm dia iron pipe complete all as specified and as directed . Note:- Hand shower & over head shower will be measured and paid separately. Make : CON -SOL 6281 of JAQUAR or equivalent in any of the make mentioned in Appendix 'F' here-in-After.
S&F in repair Hand Shower dia 105 mm round shape single flo wwith air effect (ABS BODY & FACE PLATE CHROME PLATED) with rubit cleaning system including shower flexible tubes 8 mm dia & 1.5 m long with nuts complete all as specified and directed. Make Jaquar CAT NO HSH-1717 & SHA 549D8 or equivalent in any of the make mentioned in Appendix 'F' here-in-After.
S&F in repairs Brass CP shower rose 125mm size including fixing to steel pipe or union complete all as specified and directed.
S&F in repair CP brass towel ring 20mm dia, fancy type, superior quality, fixed with and including chromium plated screws and wooden/plastic cleats complete all as specified and directed. Make : ACN-1121BN of JAQUAR or equivalent in any of the make mentioned in Appendix 'F' here-in-After.
S&F in repairs Tubular towel rail, ISI marked 60cm long between flanges , 20mm dia 'D' type Brass Chromium plated incl brackets, fixed with chromium plated brass screws and wooden/plastic cleats complete all as specified and directed.
S&F in repair stainleess steel towel rack 600 MM long with lower hanger, fancy type, superior quality, fixed with and including chromium plated screws and wooden/plastic cleats complete all as specified and directed. Make : ACN-1181S of JAQUAR or equivalent in any of the make mentioned in Appendix 'F' here-in-After.
S&F in repair PVC Coloured bathroom cabinet looking mirror divided into shelf overall size 622mm x 432mm complete all as specified and as directed by Engr-in-Charge. Make: Nilkamal/ Prayag/ Polytuf
S&F in repair soap dish (minimum weight 300 grams) of stainless steel fixed to wall with aluminium screw, complete all as specified and directed. Make Jaquar CAT NO ACN 1131N or equivalent in any of the make mentioned in Appendix 'F' here-in-After.
S&F in repairs Sheet glass shelf assembly consisting of 5.5mm thick sheet glass shelf 12cm wide with CP bracket guard & railing 60cm long fixed with chromium plated brass screws and wooden/plastic cleats complete all as specified and directed.
S & F in repair corner glass shelf with bracket fixed with chromium plated brass screws and wooden/plastic cleats complete all as specified and as directed by Engineer-in-charge . Make : ACN-1173 of JAQUAR or equivalent in any of the make mentioned in Appendix 'F' here-in-After.
S&F in repair Hand Shower (Health Faucet) with 8 mm dia,1.2 m long Long Flexible Tube Chrome Finish & Wall Hook for Water closet complete all as specified and directed. Make Jaquar CAT NO Health Faucet SKU ALD-573 or equivalent in any of the make mentioned in Appendix 'F' here-in-After.
S&F in repair Vitreous China wash down water closet pan including P or S trap of bore 125/110 mm (pedestal pattern), white or in matching colour of tiles (excluding flushing cistern and flush pipe) including plastic water closet seat, white or in matching colour , closed pattern with flat bottom, and cover and mild steel chromium plated or aluminised hinging device and wash down water closet complete all as specified and as directed.
S&F in repair viterous China squatting pan, `Orrisa' pattern, size 580 x440 mm white, witht integral foot rests (excluding flushing cistern and flush pipe) including connection to trap,and to flushing pipe, anti-syphonage pipe,etc. complete including making good to floor complete all as specified and as directed.
S&F in repairs 10 ltrs capacity PVC valveless, syphonic action type, flushing cistern, low level, white, with intel, ball valve, float and handle including brackets ,fush pipe of polyethylene of low or high density or PVC 32 mm dia complete all as specfied and as directed.
S&F in repairs Viterous China wash basin, white, flat back, size 550x400mm excluding taps etc but including brackets,including cutting for and pinning in ends of brackets or erecting stand but exclusive of fixing of supply and waste pipe complete all as specfied and as directed.
S&F sink with drainage board made of stainless steel 1 mm thick with plugs, washers and wastes, including bedding in cement mortar to dwarf wall or including fixing cantilever brackets of angle iron and connecting union to pipe over all size 915 mm x460 mm and bowl size 410mmx330mmx 160mm complete all as specified and directed.
M&L Stainless steel plate rack(Utensil Rack) of size (900mm x 750mmx250mm ) made out of AISl 304 stainless steel 0.63 mm thick sheet fixed with brass screw of required size including necessary fittings/nuts,bolts & washers complete all as specified and as directed.
S&F 15mm dia 600 mm long PVC connection including brass check nut at both ends screwed both end for iron pipes.
Demolition and breaking up drain pipes (Salt glazed ware, PVC/AC or Reinforced concrete) set in cement mortar,and taking out of trenches, if required, Internal dia of pipe in 75mm/100mm.
S&F PVC (SWR) pipes 75mm bore single socketed, in any length with rubber ring joints laid in trenches or in floors all as specified and directed.
S&F PVC (SWR) pipes 110mm bore single socketed, in any length with rubber ring joints laid in trenches or in floors all as specified and directed.
Taking down eaves gutter and rain water pipe any size any pattern , PVC/ AC pipe including all fittings ,heads shoes, bends etc including removal to store ,Internal dia of pipe in 75MM/110mm complete all as specified and directed.all as specified and directed.
S&F PVC (SWR) pipes 75mm bore single socketed in any length with rubber ring joints fixed to walls all as specified and directed.
S&F PVC (SWR) pipes 110mm bore single socketed in any length with rubber ring joints fixed to walls all as specified and directed.(ISI MARKED)
S&F PVC (SWR) bends any radius 75mm dia all as specified and directed.(ISI MARKED)
S&F PVC (SWR) bends any radius 110mm dia all as specified and directed.(ISI MARKED)
S & F in repairs 75mm PVC floor trap, ISI marked with cp grating with/without waste pipe hole incl jointing to waste pipe fixed with solvent cement complete all as specified and as directed.
Dismantling of cast iron or reinforced concrete drain pipes, jointed in cement mortar and taking out of trenches, if required Internal dia of pipe in 75mm/100mm complete all as specified and as directed.
S&F sand Cast iron soil, waste and vent pipes ISI marked, in any length with or without ears with cement joints, laid in trenches or in floors bore of pipe in 100mm complete all as specified and as directed.
S&F sand Cast iron soil, waste and vent pipes ISI marked, in any length with or without ears with cement joints, laid in trenches or in floors bore of pipe in 75mm complete all as specified and as directed.
S&F sand Cast iron soil, waste and vent pipes ISI marked, in any length with or without ears with cement joints, fixed to walls bore of pipe in 75mm complete all as specified and as directed.
All as per item 145 here-in-before but except pipe. Note: - Old sedrviceable Cast iron soil, waste and vent pipes any type retrieved from dismantling shall be used)
S&F sand Cast iron soil, waste and vent pipes ISI marked, in any length with or without ears with cement joints, fixed to walls bore of pipe in 100mm complete all as specified and as directed.
All as per item 147 here-in-before but except pipe. Note: - Old serviceable Cast iron soil, waste and vent pipes any type retrieved from dismantling shall be used)
M & L Cast iron bends (ISI marked) (any radius) diminishing pieces or tapers (larger bore measured), bore of pipe 100mm, complete all as specified.
M & L Cast iron bends (ISI marked) (any radius) diminishing pieces or tapers (larger bore measured), bore of pipe 75mm, complete all as specified.
S&F Articles not exceeding 5 kg each Cast iron work grade FG 150, unmachined, in brackets, gully traps, gratings, railing, frames, manhole covers, fire & soot doors, dampers, stop valve boxes, gate stops, parts of ranges, balusters & similar articles
M&L two coats of black japan painting on new iron/steel surfaces of any description over 10 cm in width or girth not otherwise described including preparation of new surface all as specified and directed.
M&L two coats of black japan painting on old iron/steel surfaces of any description over 10 cm in width or girth not otherwise described including preparation of old surface all as specified and directed.
Dismanting of plain or corrugated steel sheeting, any gauge, thickness, including nainital or similar pattern roof covering including wind ties etc complete all as specified and as directed.
S & F Pre- painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws complete all as specified and as directed.
Pre-painted galvalume aluminum zinc coating GI based Plain steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws complete all as specified and as directed.
Dismantling wall and ceiling boards or insulation boards any thickness, any description including cover fillets complete all as specified and directed
S & F for suspended false ceiling system using chicago metallic (E grid)exposed supended system, grid section size 600mm X 600mm comprising of GI powder coated Main Runner of dimensions 39 mm X 24mm X 0.8mm thick (thickness comprising of GI/0.4+ PPPCGS/0.3mm & weight of runner 1.35 kg for 3600mm length) Cross Tee of dimensions 29mm X24mmX0.8mm thick and thick wall angle 22.2mmX22.2mmX 0.65 mm thick ( thickness comprising of GI/0.35+ PPPCGS/0.3mm & weight of angle 0.70 kg for 3050mm length)with and including 4mm thick HPSC(High pressure steam cured) pre-primed , self embossed . textured designer board, water resistant termite resistant , fire resistant for insulation and acoustic purpose to be placed in the grid system duly suspended with 4mm dia GI bar hangers fixed with steel dash through fasteners from purlins of the roof with butterfly clips(Wt-0.007 Kg/clip)hold down clips (Wt-0.0035 Kg/clip) complete all as directed.
Dismantling structural steel work including doors gates but excluding framed truss etc.complete all as specified and directed.
Supplied and fixed rolled sections as in main and cross beams, hip and jack rafters; purlins where connected to a common rafters and rails and guides for sliding doors; fixed with angle cleats or other connecting plates Fe-410-W(Gde-E-250) quality B complete all as specified and directed.
S&F Hand rails, half round or other stock section or core for wooden hand-rail straight portion, drilled & countersunk for balusters running bars, for doors,balusters,nosing to steps including embeding in concrete & screwing etc. wind ties for roof including securing bolts; posts & struts in fencing/cooler stand including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., & similar work conforming to Fe 290-0 Gde E-165 complete all as specified and directed.
Cutting holes in brick walls built in cement mortar or cement lime mortar for inserting holdfasts and making good dismantled portion in cement mortar 1:3 or cement concrete 1:2:4 Type B-1 as required,Depth of embedded portion of holddfasts or lugs measured from the face of the jamb into the wall exc Half brick but not exc one brick complete all as specified and directed.
M&L for plain cement concrete 1:2:4 type B-1 using 20 mm graded stone aggregate in copings, bed plates including weathering, slightly rounded or chamfered angles and throating as directed including necessary form work complete all as specified and directed.
S& F Steel rolling shutters 1.25 mm thick without ball bearing, as specified including top cover, anchoring rod, hasp and staple and one shop coat of primer; erected in position as indicated, complete, gear operated type with bevel gear box and crank handle complete all as specified and directed.
M & L for post construction ATT treatment to points of contact of wood work by chemical emulsion (in oil or kerosene based solution) @ 0.5 litre/hole by drilling 6mm dia holes at a downward angle of 45 degree at 150mm centre to centre and sealing the same complete all as specified and directed.
M & L for providing and injecting chemical emulsion for post constructional anti-termite Treatment along the external wall below concrete or masonry apron using chemical emulsion @ 2.25 litres per linear metre including drilling 12mm dia upto 300mm deep and 300mm centre to centre and plugging holes etc in apron /plinth protection all as specified in IS Code 6313 Part-3:2001 and complete all as specified and directed.
M & L for post construction ATT treatment of soil under existing floors using emulsion @ one litre per hole, 300mm apart including drilling and plugging 12mm dia holes with cement mortar 1:2 (1 cement: 2 coarse sand) to match the existing floors complete all as specified and directed.
M&L Precast cement concrete type B0 (1:2:4) using 12.5 mm graded aggregate set in CM(1:4) louvres and jallies, 35 mm thick (measured solid), including all mouldings but excluding frame complete all as specified and directed.. Note:- demolition of the same will be measured under demolition of brick
Material and labour for chicken wire mesh galvanised steel wire 0.91 mm dia fixed with tinned tacks or wire staples and size of mesh 25 mmx 25 mm complete all as specified and as directed.
M & L for rectify Surface cracks on plastered walls in following sequence through manufacturer / authorised applicator of the manufacturer complete :- (a) Chip off the damaged portion to obtain a sound surface with straight edges (b) Wash the area with water & fill the masonry joints (c) Apply cement slurry on the surface (d) Plaster with CM 1:3 with water proofing compound recron fiber 3S from reliance Ltd (Mixing & application as per manufactures intructions) (e) Allow the repaired patch to cure adequately Make incorporated: Sikacim
M & L for rectify the dampness on internal walls where dampness occur in following sequence through manufacturer / authorised applicator of the manufacturer complete :- (i) Cleaning of surface with the help of various equipments wire brush etc and surface to be made dirt, oil and foreign particle free (ii) Repair of surface as and where required with Polymer Modified Mortar using Sika Raintite (iii) Prime coating of entire surface with Sika Raintite (iv) 2 Coat on surface with SIKA Top Seal 107 will be applied one after another.
M & L for 75mm thick plain cement concrete 1:4:8, type D-2 using 40mm graded crushed stone aggregate as in sub base complete all as specified and as directed. Note:- Finishing surfaces of concrete to be even and rough to receive the topping layer.
M&L for non abrasive paving (endura) tiles 300mm x 300mm x10mm thick (square/ rectangular) polished, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement over & including 15mm screed bed CM 1:4 to match complete al as specified and directed. Note:-The texture ,colour ,Shade of tiles & laying of tiles to any pattern & any design with one or more colours shall be approved by GE and Rates also including in this item for necessary raking circular cutting or notching and waste on tiles.
M&L for machine pressed precast concrete interlocking paver block any shape & size confirming to IS 15658-2006 of 80 mm thickness, M-40 grade rubber moulded glossy finish with grey cement and pigment complete all as secified and as directed. Note-Shapes of interlocking paver block shall be triangular/Zigzag/Haxagon/or other ,Colour of paver blocks & laying pattern approved by GE.
M&L for sand filling under floors or in foundations including watering and consolidation or layer of sand cushioning below interlocking paver block complete all as specified and as directed.
S&F Cement concrete tiles 25cm x 25cm x22mm thick, with grey cement & pigment machine pressed; set, jointed & pointed in neat cement slurry in floors ,path & cut , polished over and including 20mm thick secreed bed or bedding in CM 1:6 complete all as specified and as directed.
M&L for PCC 1:2:4 type B-1 using 20mm graded crushed stone aggregates as in surface channels and drains complete all as specified and as directed.
M&L for extra for forming fair finished drain or channel 30 cm inner girth in cement concrete, using ex- tra cement, including forms, moulds, mitred/stopped ends etc complete all as specified and directed.
M&L for for precast reinforcement cement concrete 1:2:4 type B-1 using 20mm graded stone aggregate as in landings, cover slabs (for manholes etc.) chullah hoods, chajjas, water troughs, mangers, shelves and similar articles with plain faces set in cement mortar (1:4) complete all as specified and as directed. Note:- Reinforcement shall be measured and paid separately.
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in any type of soil. Note:-(1) The excavation work will be carried out by mannualy or mechanical means in any location/ area as directed by engr-in- charge. (2) Any dammage occur to water supply pipe line/ electric cable/existing drain/sewage line during excavation work will be make good up to satisfaction of Engr- in-charge.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm with any type of soil complete all as specified and directed.
Removing excavated Soils material exc. 250m but n exc. 500 m and depositing where directed complete all as specified and directed.
M&L 200mm Reinforced concrete pipes, class NP-3, laid and jointed complete with collarsthick including demolition and breaking up drain pipes in cement mortar including demolition of PCC bedding and hunching complete all as specified and directed
M&L 150mm Reinforced concrete pipes, class NP-3, laid and jointed complete with collarsthick including demolition and breaking up drain pipes in cement mortar including demolition of PCC bedding and hunching complete all as specified and directed
M&L Concrete bed to drain pipes including packing under,and haunching against the sides of pipes after they are laid and tested in Cement concrete 1:4:8 type D-2 using 40 mm graded crushed stone aggregate for Bore of pipe in 200mm/150mm complete all as specified and directed
Supply, install, test and commissioning of copper wound step down transformer, outdoor type, oil immersed, naturally cooled ONAN, rated temperature rise in oil & winding 45/50 degree centigrade complete with standard fittings of capacity 400 KVA HT 11 KV, 3 phase, LT 433V, 4 wire, 50Hz of vector group Dyn-11 with off load tap changing device on HT side to vary secondary voltage from + 5 percent to -10 percent in steps of 2.5% including cable box on LT and HT side, first fill of new transformer oil having dielectric strength not less than 60KV, suitable mounting rails of appropriate gauge and other standard accessories all as per IS:1180 (Part 1) : 2014. Note :- The rate quoted deemed to be inclusive of the following”:- (a) Accessories such as oil level gauge, rating and diagram plate, monogram plate, explosive vent with diaphragm, thermometer pocket with thermometer, gun metal drain valve at bottom, Air release plug, inspection cover, lifting lugs, hooks, bi-directional plane rollers, oil temperature indicator, winding temperature indicator, silica gel breather & other standard accessories all as per IS:1180 (Part 1) : 2014 etc. Any other item as per manufacturer recommendations for best function of transformer if required are deemed to be included in quoted rates. (b) The cost of PCC foundation required for installation of transformer shall be measured and paid separately under relevant schedule item. (c) The transformer shall be one of the make mentioned in group 1 appendix 'F'
Platform for installation of transformer of size 3x2.5x1 metre for installation of transformer with brick steps on one side, chain link fencing around transformer, fencing should have hinged door and locking arrangement complete all as shown on drawing No CEPZ/C-TD/002/13 Sheet 2/5 complete all as specified and directed.
M&L earthing complet with galvanised steel earth plate eletrode 60cm x 60cm and 6 mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 meters below normal ground level, connecting to the Galvanised iron earth strip 32mmx6mm size, by means of bolts, nuts, check buts and washers of galvanised iron and 32mmx6mm earth lead protected by provision of GI medium grade pipe 40mm bore including provision of aggregates with 40mm thick cover of RCC (1;2:4) reinfored with XPM (weight not less than 4 Kg/Sqm) and frame of angle iron 25mmx25mmx6mm with lugs 02 Nos and with 6mm dia MS bar handle made to shape, GI light grade 20mm bore pipe for watering perforated at bottom 1.75 metre long placed on top edge of earth plate, common salt and charcoal filling, test point made out of 75mmx50mmx6mm phosphorous bronze with fixing arrangment, funnel, wire mesh and earth work in hard/dense soil, returning filling in distance not exceeding 50 mtr and removal of surlus soil to plate No 3 of SSR-2009 Part-I and connecting to earth test point all as specified or indicated including testing on completion complete all as specified and directed.
Notes:- (i) RCC pit cover shall be precast of RCC (1:2:4) Type B1, 80mm thick reinforcement with 8mm TOR steel @100 C/C in lieu of CI cover and the rate includes in the unit rate of item (ii) Earth lead shall be protected upto test point using necessary arrangement with GI pipe and the rates includes in the unit rate of item. (iii) Charges for earth resistivity test deemed to be included in the quoted rate. (iv) PCC Chamber shall be constructed 500mm away from the edge of earth pit (v) Earth resistance should be less than 3 Ohm. In case the test results are not found below 3 Ohm, complete earthing will be redone without any extra cost to the Govt. (vi) For effective visibility, identification and traceability of earth pit (EP) with corresponding earth of equipment and building, markers in metal (Mild Steel) shall be provided. Earth test of earth pit is to be provided with a colour code. The direction regarding the size, shape and colour of the mild steel identification board etc shall be given by the Engineer-in-Charge. (vii) On completion of the entire work the contractor shall submit a register/ record showing location of earthing, earth value, date of testing etc to the Engineer-in-Charge.
Supply, laying, jointing and testing, laid in trenches/road crossing/under floor/on walls/on poles including clamps or passing through pipes 1100 volts grade XLPE insulated, armoured heavy duty electric cable with PVC insulated stranded aluminium conductor served with an inner sheathing of PVC tape, galvanised steel strip or wire or tape armoured with an overall sheathing of cross sectional area 300 sqmm 3.5 core complete with suitable size of lugs and cable glands etc., each cable termination is to be made with suitable size of cable glands and aluminium thimbles for junction boxes, security lights, Feeder Pillar for incoming and out going cables all as specified and as directed. Note :- Earth work exevation, returning fillting, removal and sand causing shall be measured and paid septarlely under relavant item.
All as per Srl item No 189 here-in-before but of cross sectional area 240 Sqmm 3.5 core complete all as specified and directed.
All as per Srl item No 189 here-in-before but of cross sectional area 150 Sqmm 3.5 core complete all as specified and directed.
All as per Srl item No 189 here-in-before but of cross sectional area 35 Sqmm 3.5 core complete all as specified and directed.
All as per Srl item No 189 here-in-before but of cross sectional area 25 Sqmm 3.5 core complete all as specified and directed.
All as per Srl item No 189 here-in-before but of cross sectional area 16 Sqmm 4 core complete all as specified and directed.
M&L for sand cushioning to under ground cables with a layer of sand 8 cm before laying the cable and 15 cm after laying the cable complete all as specified. Note :- Punned thickness of 18 cm shall be measured and paid
M&L for brick covering with equal to length of brick as mechanical protection to cable with well burnt sub class 'B' bricks laid as directed
Removing excavated soil to a distance not exceeding 50 mtr and deposting where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed.
M&L for GI tubing light grade 50 mm bore for cable protection laid in trenches in road crossing or fixed to wall/Pole including taking down old UNSV GI tubing of any size complete all as specified and directed.
M&L for GI tubing light grade 80 mm bore for cable protection laid in trenches in road crossing or fixed to wall/Pole including taking down old UNSV GI tubing of any size complete all as specified and directed.
Supply, installation, testing & commissioning LT cubical Panel board indoor type, floor mounted factory made, CPRI approved, dust and vermin proof (Protection class IP-54), double door (front and back opening) with locking arrangement ,made out of 2.00mm thick CRCA sheet duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, aluminium bus bar of 200 Amps , complete suitable for operating on 415 Volt 50 Hz AC supply internally wired with copper conductor including connecting all incoming and outgoing using proper size thimbles, nuts, bolts & washers, having legs 60cm made out of 50x50x6mm angle iron grouted in PCC 1:3:6 type C-2 platform upto 60cms above ground level and 45 cm below ground level complete and comprising of the following:- (i) Bus bar chamber made out of CRCA sheet openable from front side having copper bus bar of 3 phase and neutral of size of 250 Amps, made out of electrolite copper strip shall be insulated with colour coded heat shrinkable sleeve (ii) MCCB 160 amps, 415 Volt,25 KA, 4 pole with thermal and adjustable magnetic setting -01 No (incomer) (iii) MCCB 25 amps, 415 Volt,16 KA, 3 pole with thermal and adjustable magnetic setting -06 Nos (iv) Digital multi functional meter which shows PF, Volts, Amps etc complete- 01 No (v) Indicator lamp assy RYB (set of 3) -01 No (vi) Digital Amp Meter 0-250 Amps-01 No Note:1.The MCCB should have Ics=100% Icu for short circuit breaking capacity of minimum 16 kA/25 KA as indicated rms at 415 volts 50 Hz AC. The MCCBs shall have spreader links and barriers as standard feature of manufacturer
Supply, installation, testing & commissioning LT cubical Panel board indoor type, floor mounted factory made, CPRI approved, dust and vermin proof (Protection class IP-54), double door (front and back opening) with locking arrangement ,made out of 2.00mm thick CRCA sheet duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, aluminium bus bar of 200 Amps , complete suitable for operating on 415 Volt 50 Hz AC supply internally wired with copper conductor including connecting all incoming and outgoing using proper size thimbles, nuts, bolts & washers, having legs 60cm made out of 50x50x6mm angle iron grouted in PCC 1:3:6 type C-2 platform upto 60cms above ground level and 45 cm below ground level complete and comprising of the following:- (i) Bus bar chamber made out of CRCA sheet openable from front side having copper bus bar of 3 phase and neutral of size of 250 Amps, made out of electrolite copper strip shall be insulated with colour coded heat shrinkable sleeve (ii) MCCB 160 amps, 415 Volt,25 KA, 4 pole with thermal and adjustable magnetic setting -01 No (incomer) (iii) MCCB 80 amps, 415 Volt,16 KA, 3 pole with thermal and adjustable magnetic setting -02 Nos (iv) Digital multi functional meter which shows PF, Volts, Amps etc complete- 01 No (v) Indicator lamp assy RYB (set of 3) -01 No (vi) Digital Amp Meter 0-250 Amps-01 No Note:1.The MCCB should have Ics=100% Icu for short circuit breaking capacity of minimum 16 kA/25 KA as indicated rms at 415 volts 50 Hz AC. The MCCBs shall have spreader links and barriers as standard feature of manufacturer
Supply, installation, testing & commissioning LT cubical Panel board indoor type, floor mounted factory made, CPRI approved, dust and vermin proof (Protection class IP-54), double door (front and back opening) with locking arrangement ,made out of 2.00mm thick CRCA sheet duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, aluminium bus bar of 200 Amps , complete suitable for operating on 415 Volt 50 Hz AC supply internally wired with copper conductor including connecting all incoming and outgoing using proper size thimbles, nuts, bolts & washers, having legs 60cm made out of 50x50x6mm angle iron grouted in PCC 1:3:6 type C-2 platform upto 60cms above ground level and 45 cm below ground level complete and comprising of the following:- (i) Bus bar chamber made out of CRCA sheet openable from front side having copper bus bar of 3 phase and neutral of size of 600 Amps, made out of electrolite copper strip shall be insulated with colour coded heat shrinkable sleeve (ii) MCCB 400 amps, 415 Volt,25 KA, 4 pole with thermal and adjustable magnetic setting -01 No (incomer) (iii) MCCB 125 amps, 415 Volt,25 KA (outgoing), 3 pole with thermal and adjustable magnetic setting -03 Nos (iv) Digital multi functional meter which shows PF, Volts, Amps etc complete- 01 No (v) Indicator lamp assy RYB (set of 3) -01 No (vi) Digital Amp Meter 0-700 Amps-01 No Note:1.The MCCB should have Ics=100% Icu for short circuit breaking capacity of minimum 16 kA/25 KA as indicated rms at 415 volts 50 Hz AC. The MCCBs shall have spreader links and barriers as standard feature of manufacturer
Supply, installation, testing & commissioning LT cubical Panel board indoor type, floor mounted factory made, CPRI approved, dust and vermin proof (Protection class IP-54), double door (front and back opening) with locking arrangement ,made out of 2.00mm thick CRCA sheet duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, aluminium bus bar of 200 Amps , complete suitable for operating on 415 Volt 50 Hz AC supply internally wired with copper conductor including connecting all incoming and outgoing using proper size thimbles, nuts, bolts & washers, having legs 60cm made out of 50x50x6mm angle iron grouted in PCC 1:3:6 type C-2 platform upto 60cms above ground level and 45 cm below ground level complete and comprising of the following:- (i) Bus bar chamber made out of CRCA sheet openable from front side having copper bus bar of 3 phase and neutral of size of 750 Amps, made out of electrolite copper strip shall be insulated with colour coded heat shrinkable sleeve (ii) MCCB 500 amps, 415 Volt, 36 KA, 4 pole with thermal and adjustable magnetic setting -01 No (incomer) (iii) MCCB 200 amps, 415 Volt, 36 KA (outgoing), 4 pole with thermal and adjustable magnetic setting -02 Nos (iv) Digital multi functional meter which shows PF, Volts, Amps etc complete- 01 No (v) Indicator lamp assy RYB (set of 3) -01 No (vi) Digital Amp Meter 0-750 Amps-01 No Note:1.The MCCB should have Ics=100% Icu for short circuit breaking capacity of minimum 16 kA/25 KA as indicated rms at 415 volts 50 Hz AC. The MCCBs shall have spreader links and barriers as standard feature of manufacturer
Dismantling and installation of Transformer cap 100 kVA to 315 kVA ,disconnecting all existing connections , lifting by chain pulley arrangement,transporting it to various sub station and installing checking all as specified and directed.
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, sockets, Bracke sketch fitting, ceiling roses, lamp holders, brackets, pendants, regulators, sockets, light fitting etc. removing materials to store for taking credit and making good disturbed surfaces of walls, floors, etc complete all as specified and directed by EIC. Note:- The damaged surfaces to be made good with plastering (1:6). & applying colour wash in required coats to matching with existing surfaces as directed by Engineer-in-charge. Cost of the same deem to be included in quoted rates and nothing extra on this account admissible.
M&L Point wiring with 1.5 Sq. mm (nominal area) FRLS PVC insulated and unsheathed multistranded copper conductor cable 1100 Volts grade drawn through and incl PVC rigid concealed conduit (ISI Marked) suitable size with all accessories having thickness not less than 1.8mm incl sheet steel/ CI terminal box of adequate size having thickness not less than 2mm including 3mm thick hylem/masonite sheet including 1.5 Sqmm FRLS PVC insulated unsheathed copper conductor multistranded cable of green colour as earth conductor connected to common earth dolly complete all as specified and directed for one light / fan point controlled by one switch 5 Amp, SP, one way, 240 Volts. Note: 1. Connections of cable with MCBs/Switch Sockets shall be done through proper size copper/brass thimbles. 2. Conduit shall be fixed on surface of roof with necessary saddles where concealing of conduit in not feasible. 3. Proper colour code will be used for wiring as per the electrical rule and as directed.
All as per Srl item No 206 here-in-before but for one 5 pin 5 Amp socket outlet point on inependent board controlled by one switch SP, one way 5 Amp, 240Volts.
All as per Srl item No 206 here-in-before but for one 5 pin 5 Amp socket outlet point on same board controlled by one switch SP, one way 5 Amp, 240Volts.
All as per Srl No 206 above but for call Bell point complete all as specified and directed by Engineer In Charge
M & L for point wiring with 2.5 sqmm single core PVC insulated unsheathed multistranded copper conductor FRLS cable with in and including PVC concealed conduit heavy duty 20mm dia having thickness not less than 1.8 mm with all fittings including anodise pressed steel sunken box having thickness not less than 2mm with 3mm bakelite laminated sheet ISI marked suitable for 5 pin 15 amps socket outlet ,including 2.5 sqmm single core PVC insulated unsheathed multistranded copper conductor FRLS cable as earth continuity conductor connected to comman earth dolly in and including cutting chiseling for concealed piping and making good disturbed surface finishing the surface to match with the existingsurface complete all as specified and directed.Note: (a) Insulation test of point wiring (b) colour coding is to be maintained
All as per srl item No-210 here in above but using 4.00 sqmm PVC insulated unsheathed copper conductor single core multi strand flexible cable and 4 sqmm PVC insulated unsheathed copper conductor single core cable (green color) as earth lead for geyser point complete all as spd and directed.
M & L for Modular point wiring for one light/one fan controlled by one switch with 1.5 sqmm PVC insulated unsheathed multistrand copper conductor FRLS cable with and including PVC concealed conduit ISI maked heavy duty for one light fan/bell point controlled by one switch including lumina plate and metallic boxes of suitable way matching with surrounding modular boxes with suitable size including PVC green insulated unsheathed 1.5 sqmm multistrand copper conductor FRLS cable as continous earthwire and connecting to earth duly, complete all as specified and directed. Note: (a) Insulation test of point wiring (b) colour coding is to be maintained .(Ph-Red, N-Black, Half -Yellow, Earth- Green)
All as per srl item No 212 here-in-before but MODULAR call Bell point complete all as specified and directed.
All as per srl item No 212 here-in-before but MODULAR 3 pin 5 amps socket outlet on the same board with other switch complete all as specified and directed.
All as per srl item No 212 here-in-before but MODULAR 3 pin 5 amps socket outlet on independent Board complete all as specified and directed.
All as per srl item No 212 here-in-before but MODULAR 15/16 Amps socket outlet on inependent board with 2.5 sqmm copper conducter FRLS cale and 2.5 sqmm PVC insulated unsheathed coper onductor cable FRLS (Green Colour) as earth lead complete all as specified and directed.
S & F switch piano flush button single pole one way 5 Amp AC 240 volts, all as specified and as directed.
S & F Bell push flush type 5 Amp 240 volts complete all as specified and directed .
S & F switch piano flush type one way 15 amps SP 240 volts complete all as specified and directed.
S & F socket outlet 2 in 1, 3 pin 5 amps flush type 240 volts complete all as specified and directed.
S & F socket outlet 2 in 1, 3 pin, 5 and 15 amps flush type 230 volts complete all as specified and directed.
S & F lamp holder/batton holder/angle holder insulated body with bakelite back plate suitable for fittings complete all as specified and directed.
M & L for ceiling rose, PVC/Polycarbonate, insulated body, surface Bakelite 65mm dia three terminals all as specified and as directed.
S & F Modular switch 1 way 6 A, 1 module complete all as specified and directed.
S & F Modular switch 1 way 16A, 1 module complete all as specified and directed.
S & F Modular Socket 6A/16A - 2/3 pin combined 2 module complete all as specified and directed.
S & F Modular Socket, 6A - 2/3 pin combined 2 module complete all as specified and directed.
S & F of Modular Fan step regulator 120W-2 module , complete all as specified and directed.
S&F Modular bell push 6 A, 1 Module, Complete all as specified and directed
Supply and fixing of ceiling fan regulator electronic socket type 5 stage speed variation ISI marked complete all as specified and directed.
S & F Bell AC,230 Volts, Single pole complete all as specified and directed .
S&F in replacement mirror light 10 Watt LED 2' length prewired with all accessories including lamp and connected electrically to ceiling rose using PVC insulated and overall sheathed flexible copper conductor 3core cable of size 0.50Sqmm. Make :- WIPRO CAT PART No. D531065 or equivalent in any of the make mentioned in Appendix 'F' here-in-After.
Supply and Install of the electric water heater storage ABC type 25 Ltr capacity 5 Star rated of Stainless Steel body vertical type glass lined of inner tank and heating element and having the wall mounting arrangement,thermostate,indicators and thermally insulated stainless steel tank of glass lined inside the tank and heating element, PTMT connection pipe of 15mm dia and mounting on wall with suitable size of anchor bolts with complete connection of water & testing and all as specified and directed. Make- Havells Puro Turbo DX/ Racold / Bajaj Calenta
S & F LED smart Lamp, B22 type ,14 watt,complete all as specified and directed.
S&F 20W surface / wall mounted batten LED luminair, extruded aluminium housing with PC diffuser and ind electronic driver with high efficiency long life, CRI = 80 (Minimum), PF > 0.95, luminous efficacy > 100 lumens/Watt operating voltage 140V-240V, CCT (K) > 6500, THD < 10% complete including 20W LED tube rod with all accessories internally prewired and including connecting up with 3 core flexible copper conductor cable of suitable size from ceiling rose to connector of LED fitting complete all as specified and directedories prewired and including making connections with 3 core twisted flexible copper cable of size 23/.0076 from ceilling rose/PVC connector to light fittings complete Make of LED Fitting:- CROMPTON DMLN1LT8-16 or Technocommercially equivalent to Philips/ GE.
S & F of Decorative Gate Light Moon Opal made up of high Grade unbreakable polycarbonate material suitable for 25 Watt LED Bulb Make:- CROMPTON CAT Part No:- LEDPOST02513-01 or equivalent in any of the make mentioned in Appendix 'F' here-in-After.
S&F in replacement Energy saving, surface mounted, bulk head LED luminaire 10 W with PDC aluminium housing and polycarbonate diffuser with IP 66 protection complete including connecting up with three core twisted flexible copper conductor cable of suitable size.all as specified. Make :- CROMPTON CAT Part No. LBHP-10-CDL or equivalent in any of the make mentioned in Appendix 'F' here-in-After.
Taking down ceiling fan by disconnecting the electric connection and dismantling the blades and removing from ceiling/roof of bldg by descrewing the nut, bolt etc complete all as specified and directed.(Note-Old u/s balance ceiling fans will be deposited in Store yard)
Rehanging only of ceiling fan and connecting up including provision of PVC insulated and overall sheathed flexible copper conductor cable 3 core of size 0.50Sqmm from ceiling rose or connector to fan including minor repairs such as replacement of locking pin, reel insulators, bolts, nuts etc and spraying one coat of synthetic enamel paint of required color all as required and directed by Engr-in-charge.
M & L for providing/ cutting the round/ square hole of required size in wall finishing the distrubed surfaces as per existing finishes complete all asspecified and supply and fixing MS ventilating fans Single phase, 230 volts 300 mm or 12” H.D EX Fan (900 RPM) complete and supply and grouting the ragged bolts in wall, fixing the frame on the exhaust side (outer surface of the wall) and connecting with and including PVC insulated three core 1.5 sqmm copper cable from ceiling rose to exhaust fan motor and writting MES No. with black synthetic enamel paint 2.0 cm high complete all as spd and directed by Engr-in-charge.
S&F,testing and connecting the star rated ceiling fan 230 volts,single phase of 1200mm sweep double bearing type with including down rod,canopy cover etc and connecting with 3core flexible copper conductor of 0.50 sq mm and including writing of MES No with black enamelled paint as per directed by engr-in-Charge. Make-Orient/Bajaj/CG
S & F of sheet metal enclosure MCB distribution board, double door with IP-43 protection single phase 240 volts 12 way, including suitable size copper bus bar and neutral link fixed flush in wall including chases wall for fixing DB and making good distributed wall surfaces to match with existing specification complete all as specified and directed by Engr-in-charge.
S & F of sheet metal enclosure MCB distribution board, double door with IP-43 protection single phase 240 volts 8 way, including suitable size copper bus bar and neutral link fixed flush in wall including chases wall for fixing DB and making good the distributed wall surfaces to match with existing specification complete all as specified and directed by Engr-in-charge.
S&F MCB SP 240V, 50Hz, 10 KA, 'C' curve of rating 6 to 32 Amp all as specified and directed.
S&F MCB SPN 240V, 50Hz, 10 KA, 'C' curve of rating 6-32 Amp all as specified and directed.
M & L sheet metal enclosure with sheet metal enclosure MCB distribution board single pole and neutral with a two pin and earth plug and socket 20 amps 240 volts, complete with one single pole MCB of 20 amps complete all as spd and directed. Make:- Hager/ Legrand/ ABB
M&L for sub Main Wiring with 2 run of single core, 6Sqmm FRLS PVC insulated and unsheathed, multi starndedcopper conductor cable using colour code for phase red and neutral black with and including 6 Sqmm FRLS PVC insulated and unsheathed copper conductor cable in green colour as earth conductor connected to common earth dolly, drawn in and including concealed PVC rigid conduit of suitable size having thickness not less than 1.8mm (ISI marked) with and including all accessories complete and making good to disturbed surface of wall/floor with cement mortar and finishes to match existing surface including taking down of existing unserviceable surface/cocealed sub main wiring any type complete all as specified and directed. Note: Two run of submain wire (phase and neutral), and one run of earth including PVC conduit and accessories will be measured as one run.
S&F distridution board iron clad vertical DB double door with IP-43 protection and mechanical strength as IK-09 suitable for MCCB as incomer an MCB as outgoing 415V 3Phase 50Hz 4 Way complete with appropriate size of copper bus bar and neutral link complete with one MCCB 3Pole 415V 63Amps rating,16kA with adjustible thermal and adjustible magnetic release of the same make as of distribution board complete all as specified and directed. Note: (MCBs will be measured and paid saperately)
S & F bldg secuirty light fitting energy saving high efficiency LED street light fitting 30 Watts, 5700 K, IP 66, having pressure die cast housing with toughened glass and individual high power LEDs with secondary optics, prismatic polycarbonate cover complete including GI bracket of size 32 mm dia bent to shape having length on less than 1.5 mtr fixing with clamp etc and making connections using cord flexible 3 core copper cable of size 23/ .0076 from ceilling rose/ PVC connector to light fittings or as directed by Engr-in-chrage. Make: CROMPTON CAT REF. LSTS-30-CDL or technocommercially equivalent to Philips/ Wipro.
M & L for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (Earth pit not less than 2.25 metre deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to galvanised earth lead wire 4.0 mm dia by means of bolts, nuts,check nuts and washers of galvanised iron or steel all as showin in electrical plate No.5 of SSR Part-I (2009) including filling of charcoal dust, common salt all around Earth plate upto 150 mm, 20mm bore GI medium grade watering pipe, 15 mm bore light grade earth lead protection pipe upto main board, funnel with wiremesh, 40 mm thick RCC 1:2:4 type B-1 using 20mm graded crushed stone aggregrate reinforced with suitable handle and angle iron frame and necessary excavation and earth work in any type of soil etc. complete all as specified and as directed including test on completion.
Notes:- (i) RCC pit cover shall be precast of RCC (1:2:4) Type B1, 80mm thick reinforcement with 8mm TOR steel @100 C/C in lieu of CI cover and the rate includes in the unit rate of item (ii) Earth lead shall be protected upto test point using necessary arrangement with GI pipe and the rates includes in the unit rate of item. (iii) Charges for earth resistivity test deemed to be included in the quoted rate. (iv) PCC Chamber shall be constructed 500mm away from the edge of earth pit (v) Earth resistance should be less than 3 Ohm. In case the test results are not found below 3 Ohm, complete earthing will be redone without any extra cost to the Govt. (vi) For effective visibility, identification and traceability of earth pit (EP) with corresponding earth of equipment and building, markers in metal (Mild Steel) shall be provided. Earth test of earth pit is to be provided with a colour code. The direction regarding the size, shape and colour of the mild steel identification board etc shall be given by the Engineer-in-Charge. (vii) On completion of the entire work the contractor shall submit a register/ record showing location of earthing, earth value, date of testing etc to the Engineer-in-Charge.
Note: The schedule of credit has been attached in tender in Pdf format and amount of credit schedule i.e. Rs 1554342.85 shall be deducted from the total amount of BOQ to arrive at the contract sum.
JAGSON CONSTRUCTIONS LTD
Faith Builders
Sanjay Constructions
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .