Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance VILLAGE KARTHOLI NATIONAL HIGHWAY BARI BRAHAMANA JAMMU JAMMU KASHMIR 181133 | SAMBA | JAMMU AND KASHMIR | 181133 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹7,100
Closing Date
28 Apr 2021, 4:00 pmClosed
Executive Engineer ED-II Jammu
Office of the Executive Engineer ED-II Jammu
Fixing of Rate contract for SITC of 63 KVA 11/0.433 KV 3-Phase Distribution Substation(Energy Level 2, BIS Marked (Aluminum Wound) on turnkey basis at different locations under the jurisdictionofElectricDiv-II Jammu during21-22
2021_PDD_122267_1
Enit 15 of 2021-22 dated 10-04-2021
Open Tender
Electrical Works
Turn-key
45 days
Executive Engineer ED-II Jammu
Please refer Tender documents.
3 documents required · 3 mandatory
₹200
Executive Engineer ED-II Jammu
₹7,100
Yes
3 Jun 2021
12 Apr 2021
29 Apr 2021
12 Apr 2021
28 Apr 2021
12 Apr 2021
12 Apr 2021 - 28 Apr 2021
Amount
Supply, Installation & commissioning of 11/0.433 KV, 63 KVA 3-Phase Distribution Transformer with Bi-metallic terminal Connectors, Energy Level: 2, "BIS Marked" (Aluminium Wound) alongwith LV Cable Box having detachable Alumnium Gland plate.
Supply, Transportation, Erection of 9 Mtr Long ST Pole (ST-410 SP33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface.
Supply, Transportation, Fabrication & Fixing of MS Channel Iron, Cross arms, Angle Iron Braces, Clamps etc duly fabricated, red oxide & aluminium paint coated including all necessary Nut & Bolts & Washers etc.
Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A
Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
Providing & Fixing of PVC Cable 120 mm² alongwith 12 Nos Al. Thimble of 120 mm²
Providing & Fixing of LT Distribution Box with100 Amp MCCB for incomer & switch fuse unit for Out Going Ckt.
Providing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Providing of Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole
Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of Wedge Connectors / PG Clamps
Providing & Fixing of Anti Climbing device with Clamps
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid Stay Rod & 7/3.15 mm dia stranded wire complete
M/S HI TECH ELECTRICALS
HI-TECH TRANSFORMERS
INDUSTRIAL ELECTRICALS
U3 ENTERPRISES
Raina Builders and Suppliers
M/S VINAYAK ENGINEERS
KAPIL GUPTA
JASMEET SINGH
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .