Loading…
Loading…
Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
14 Sept 2026, 6:00 pm
GE (NW) NOFRA
Dr Homi Bhabha Road Navy Nagar Colaba Mumbai
REPAIR/ MAINT OF ELECTRIC SUPPLY DISTRIBUTION NETWORK AT INS SHIKRA, NT POOL, BOAT POOL, PASTA LANE AREA UNDER GE (NW) NOFRA
2026_MES_786634_1
GE (NW) NOFRA 8565
Open Tender
Civil Works
Item Rate
365 days
GE (NW) NOFRA
As Per Tender Document
8 documents required · 8 mandatory
₹500
GE (NW) NOFRA
₹98,000
Yes
27 Aug 2026
27 Aug 2026
16 Sept 2026
27 Aug 2026
14 Sept 2026
8 Sept 2026
27 Aug 2026 - 2 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Material & Labour for repairs/ Overhauling /Servicing to Existing LT electric panels Indoor type of each Transformer by taking shut down from appropiate authority including checking loose connections and tight connection and cleaning inside/out side all connection, replacing all cable glands,thimbles and lugs as per the size of existing cable, applying petrolium jelly on the contactors, providing new insulation tape to bus bars, repair to broken /hanging doors by fixing hinges or welding the door to make it servicable, spray painting (silver colour) / powder coating and testing the entire panel board after the completion of servicing up to the satisfication of Engr-in-charge all as directd and specified. Note :- The tenders quoted rate per unit shall deemed to be inclusive of taking out burnt Voltmeter/ Ampiermeter/CT/LED lamps of any type and discription etc and refixing the same, which shall be measured and paid as supply only vide relivent items of this schedule complete all as specified and directed.
Note : Spare part wiil be measured and paid seprately as supply only vide relivent item No 2 to 6 of this schedule. | 30 | Each Job | - | - |
| 1.01 | (i) Cleaning inside the panel and all incoming and out going feeders i.e including MCCB/SFU/Changeover switches/Contactors/ ACB's thorougly with help of Vaccum Cleaner.
(ii) Checking the loose connections of incoming and out going feeders and rectifify the same with help of new GI nut bolts and washers
(iii) Replacing the burnt out color coated PVC Sleeve of main and fedders bus bar with appropriated size of New PVC heat shrinkable sleeves -01Job | - | - | - | - |
| 1.02 | (iv) Replacing Burnt out Voltmeters/Ammeters/Indicating Lamps/.(Note: New items will be measured and paid separatly)-01Job
(v) Replacing burnt out control wiring of Ammeter/Voltmeter/Indicating lamps and CT'swith 2.5/1.5Sqmm copper single core,1100V grade copper conductor cable- 01Job
(vi) Replacing Burnt out Bus Bar of incomming and out going feededs with approprieted size of new bus bar (Copper/Aluminum) -01Job( Note : Bus Bar will measured and paid separately).
(vi) Replacing Burnt out Insulators of incomming and out going feeders with approprieted size of new Insulators -01Job
(vii) Spray Painting of Panel Board with one coat of synthetic enamel paint. | - | - | - | - |
| 2 | Supply only Aluminium Bus Bar strips, of any size, for extention of MCCB terminals for cable terminations, inside the cable alley of LT panel board, duly supported on the FRP / DMC support insulators including necessary drilling / bending to obtain required shape and size complete all as specified and as directed. | 10 | Kg | - | - |
| 3 | Supply only Copper Bus Bar strips, of any size, for extention of MCCB terminals for cable terminations, inside the cable alley of LT panel board, duly supported on the FRP / DMC support insulators including necessary drilling / bending to obtain required shape and size complete all as specified and as directed. | 13 | Kg | - | - |
| 4 | Supply only Digital LT voltmeter with selector switch of size 96x 96mm rating 0 to 500 volt all as specified and directed. | 4 | Each | - | - |
| 5 | Supply only Digital LT Ammeter with selector switch of size 96x 96mm suitable for CT ratio 5amp, progaramable type and all as specified and directed. | 6 | Each | - | - |
| 6 | Supply only indicating lamp holder with bulb LED(Red Yellow,Blue,Green) type to indicate incoming supply suitable for 24 V DC/110 VAC/230Volts AC and all as specified and directed. | 30 | Each | - | - |
| 7 | Material and Labour for Attending Faults/Trippings and rectifieng /repairing the faults in LT Panels Boards/Capacitor Panels Boads/ MCCB's/ACB's /Change Over switches/Cable Connections/Bus Bar etc including PVC insulating Tapes/Nut bolts and all as specified and directed by Engineer-In-Charge.
Note : (i) Spare parts will be measured and paid separately (ii) Fault rectification and restore the supply withen 4hrs otherwise penality liable Rs 500 per hour till supply will restore. | 80 | Each Job | - | - |
| 8 | Material and labour for fault finding on LT cables of any size and any length with fault detective machine by thumbing method and suitable high voltage and all as and directed by Engineer-in-charge. | 18 | Each Job | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.36 MB
BOQ_881531.xls
BOQ • 1.70 MB
TenderPages8565.pdf
Tender Documents • 25.16 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].