Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1st₹7.1 LAccepted-Finance | 1st | Accepted-Finance 1st lowest bidder | |
| 2 | 2nd₹9.0 L+₹1.9 L (26.1%)Rejected-Finance | 2nd | Rejected-Finance 2nd lowest bidder | |
| 3 | 3rd₹9.0 L+₹1.9 L (26.1%)Rejected-Finance SIMURALI NADIA | PURBA BARDHAMAN | WEST BENGAL | 713502 | 3rd | Rejected-Finance 3rd lowest bidder | |
| 4 | 4th₹10.4 L+₹3.3 L (45.8%)Rejected-Finance 14 SURI LANE KOLKATA 700 014 | KOLKATA | KOLKATA | WEST BENGAL | 700014 | 4th | Rejected-Finance 4th lowest bidder |
Tender Value
Refer Docs
EMD Value
₹14,000
Closing Date
27 Jul 2024, 5:00 pmClosed
Superintending Engineer, SWEC, PWD
OFFICE OF THE SUPERINTENDING ENGINEER (P.W.D) South-Western Electrical Circle PWD Compound, Midnapore, Paschim Medinipur
SITC of silent DG set, UPS and AC machines alongwith related EI work within the campus of Government Fish Technology Station (G.F.T.S) at Junput in the dist of Purba Medinipur-- SITC of DG Set
2024_WBPWD_717235_1
WBPWD/SE/SWEC/NIQ25/2024-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
PURBA MEDINIPUR
Please refer Tender documents.
3 documents required · 3 mandatory
₹14,000
O/O of SE, SWEC,PWD, PWD Compound, Midnapur
10 Mar 2025
20 Jul 2024
29 Jul 2024
20 Jul 2024
27 Jul 2024
23 Jul 2024
23 Jul 2024
Amount
Supply , delivery at site on foundation , commissioning of 30 KVA, 415V, 50Hz, 3Ø silent new DG Set, comprising of Engine, alternator, separate AMF panel, Base frame, Fuel tank, Battery, CPCB-IV approved Engine & Acoustic Enclosure having following specifications :-
Engine Make: Cummins/Volvo/Caterpiller/MTU Force /Mitshubishi/KOEL /Greaves Power / Ashok Leyland / Mahindra
Engine Type : 4 Stroke Diesel Engine Genset output (kVA/kWe) : 30 / 24
Gross engine Power (BHP) : 74 BHP or Higher
Duty : PRIME
Aspiration/Cooling : TCAC
Cylinder /Arrangement : 3 / inline
Type of Governor : Electronic / Mechanical
Fuel Tank Capacity : Minimum capacity 60 Ltrs. Or higher
Fuel Consumption at 75% rated Load with Radiator or Fan : 5.48 Ltr./ Hr. or Less
Fuel Consumption at 100% rated Load with Radiator or Fan : 7.35 Ltr./ Hr. or Less
Overload Capacity : 10% overload for one hour for every 12 hours continuous running at full load or better
Engine instrument Panel : Consisting of starting switch with Key, Lube Oil Indicator, water temperature Indicator, RPM indicator and hour meter.
Safety Controls : Emergency Stop, Low Lube Oil Pressure warning/ Shutdown, High Engine Water Temp. warning/ Shutdown, Sensor failure Indicator, Engine over speed indicator, Battery charging and low battery indicator
Exhaust Silencer : Residential Type
Starting system : 12V./ 24 V. starting system complete with starter motor, charging alternator with rectifier and Cutout as per manufacturer standard.
Battery : Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak Battery warning
Alternator :
Make : Stamford/ Leroy Somer/Mecc alte / CG
Rating : 415 V., 3Ph. 50 Hz., 30 KVA, 1500 rpm
Type : Brushless, self excited and self regulated
Insulation : Class H
Protection : Screen-protected drip proof with Min.IP-23 degree of protection
Voltage Regulation (max) : ±1%
Winding connection : Star with Neutral
Total Distortion factor : Less than 3%
Total Harmonic distortion in output waveform : < 5%
Acoustic Enclosure : The DG set should have integrated acoustic enclosure at the manufacturing state itself. High quality acoustic enclosure must be certified as per CPCB-IV norms.
Base Frame : Common iron channel fabricated base frame containing the engine and alternator, mounted on AVM pads and having provision for lifting Hook.
SITC OF AMF Panel
Cubical type floor mounted AMF panel made from 14 SWG Sheet Steel, duly pretreated, powder coated painted and aesthetically finished, suitable for controlling of 30 KVA DG set having following specification/features.
The AMF panel must be designed to ensure trouble free performance and ensure switching over Electrical Load to DG within 15 (fifteen) second from the instant of mains failure.
Supply & delivery and pouring including transportation of HSD oil
Supply & laying 2.5 sq. mm. 10 core multi core multistrand PVC insulated flexible Cu cable in uPVC / GI pipe from DG to separate AMF panel. [Gloster/ Polycab/RR Kabel] [Bidder should visit the site]
Terms & Conditions
(i) Rate should be quoted inclusive of all applicable taxes and Duties etc.
(ii) All materials, equipments & accessories must conform to the relevant IS specifications. The DG Set must be supplied from the authorized OEM of the respective Engine Manufacturer.
(iii) Necessary manufacturer's test certificate for Diesel Engine, Alternator etc. Will have to be submited in triplicate during delivery of the equipment.
(iv) Copy of "Type Approval Certificate" and Certificate of "COP" must be produced at the time of delivery issued from the competent Authority (As per CPCB-II).
(v) Circuit Diagram for AMF Panel must be submitted from the Manufacturer/OEM.
(vi) The entire set must be warranted at least 15 months from the date of Delivery/12 months/ 5000 Hrs from the date of Commissioning whichever is earlier. However Engine & Alternator should be warranted of 2 years/5000 Hrs, whichever is earlier. Vii) During warrenty period if any discripency occurs regarding performance of the DG set that has to be attended within 24 Hrs. sharp
GEM ENGINEERS CO-OP SOCIETY LTD
LOKNATH ENGINEERING
T.D.K. ENTERPRISE
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .