| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹44.0 LAccepted-AOC | L1 | Accepted-AOC Being Lowest and Quoted rates are reasonable | |
| 2 | L2₹52.0 L+₹5.0 L (10.5%)Rejected-Finance | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹52.1 L+₹5.1 L (10.9%)Rejected-Finance 011 NAGAREWADI 612 NAGAREWADI POST PADALI TALUKA SHIRUR KASAR DISTRICT BEED 413249 BEED MAHARASHTRA 413249 UDYAM MH 05 0079863 | BEED | MAHARASHTRA | 413249 | L3 | Rejected-Finance Other than lowest | |
| 4 | L4₹52.5 L+₹5.5 L (11.7%)Rejected-Finance PULGAON | L4 | Rejected-Finance Other than lowest | |
| 5 | L5₹53.7 L+₹6.7 L (14.2%)Rejected-Finance | L5 | Rejected-Finance Other than lowest |
Tender Value
Refer Docs
EMD Value
₹90,000
Closing Date
2 Apr 2024, 6:00 pmClosed
GE PULGAON
GE PULGAON CAD CAMP PULGAON PIN 442303
REPAIRING/REPLACEMENT OF OLD VINTAGE WIRING, FITTINGS AND FLAME PROOF FITTINGS AND FIXTURES AT INSIDE DEPOT AREA (ASD, BSD, CSD, DSD, ESD, FSD, TOSD) AT CAD PULGAON UNDER GE PULGAON
2024_MES_646059_1
8113/PUL/E8
Open Tender
Civil Works
Item Rate
270 days
GE PULGAON
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
Yes
GE PULGAON
₹90,000
Yes
7 May 2024
12 Mar 2024
9 Apr 2024
12 Mar 2024
2 Apr 2024
28 Mar 2024
12 Mar 2024 - 27 Mar 2024
Amount
Taking down from any height carefully concealed/ casing caping/ ERW pipe point wiring copper / aluminium (light / fan / scoket) complete/as required (with fittings such as switches ceiling rose, pendents, regulators sockets etc as required) and making good disturbed surface with exisitng specification all as specified and directed by Engr-in-Charge.
Point wiring for explosive sheds and other required bldgs with 1100 Volts grade PVC insulated single core FRLSH cable with strranded copper conductor of size 1.5 Sqmm drawn through and including ERW rigid stove enamelled steel conduit of suitable size but not point less than 19mm dia with and includings all accessories, bends,elbow,coupling etc and incl 1.5 Sqmm earth FRLSH copper wire etc complete all as specified.
Point wiring for explosive sheds and other required bldgs with 1100 Volts grade PVC insulated single core FRLSH cable with stranded copper conductor of size 2.5 Sqmm drawn through and including ERW rigid stove enamelled steel conduit of suitable size but not point less than 19mm dia with and includings all accessories, bends,elbow,coupling etc(and incl 2.5 Sqmm earth FRLSH copper wire etc complete all as specified.
Point wiring for explosive sheds and other required bldgs with 1100 Volts grade PVC insulated single core FRLS cable with stranded copper conductor of size 4 Sqmm drawn through and including ERW rigid stove enamelled steel conduit of suitable size but not point less than 19mm dia with and includings all accessories, bends,elbow,coupling etc and incl 4sqmm earth FRLSH copper wire etc complete all as specified.
Supply and fix in replacement LED tube light fitting. 1 x 16W / 20W flameproof type FLP-WP made of aluminium alloy LM6 complete with all accessories suitable for Gas/Vapour Group of IIA & IIB and Zone 1 & IP-65 Protection.
Supply and fix in replacement LED tube light fitting. 2 x 16W / 20W flameproof type FLP-WP made of aluminium alloy LM6 complete with all accessories suitable for Gas/Vapour Group of IIA & IIB and Zone 1 & IP-65 Protection.
Supply and fix in replacement flame proof rotary switch, in cast aluminium LM-6 suitable for 16A, single pole 250V with protection IP-65, equipement standard as per IS-2148/81 complete as specified and directed by Engr-in-Charge. Note. The rate quoted to be inclusive of brackets made of MS steel of suitable size for the above fittings.
Supply and fix in replacement Switch flame proof rotary type with termination box in LM6, 16A, double pole 250V with protection IP-65, equipement standard as per IS-2148/81 complete as specified and directed by Engr-in-Charge. Note. The rate quoted to be inclusive of brackets made of MS steel of suitable size for the above fittings.
Supply and fix in replacement Flame proof switch socket & plug combined in LM6 cable termination box in LM6, 16A, 250V, 2P+earth with protection IP-65, equipement standard as per IS-2148/81 complete all as specified and directed by Engr-in-Charge. Note. The rate quoted to be inclusive of brackets made of MS steel of suitable size for the above fittings.
M & L in replacement flame proof 3 way lighting junction box with plain cover in cast aluminium LM-6 material, with protection IP-65, equipement standard as per IS-2148/81 equipment standard , alongwith cable glands complete all as specified and directed. Note. The rate quoted to be inclusive of brackets made of MS steel of suitable size for the above fittings.
M & L in replacement flame proof 4 way lighting junction box with plain cover in cast aluminium LM-6 material, with protection IP-65, equipement standard as per IS-2148/81 equipment standard , alongwith cable glands complete all as specified and directed. Note. The rate quoted to be inclusive of brackets made of MS steel of suitable size for the above fittings.
S & F in replacement Flame proof - weather proof LED flood light fitting with protection IP-65 suitable for 100 Watt for indoor type complete all as specified and directed.
S & F in replacement Flame proof - weather proof LED flood light fitting with protection IP-65 suitable for 60 Watt for indoor type complete all as specified and directed.
M&L point wiring complete with 1.5sqmm single core unsheathed PVC insulated FRLS cable 1100 V grade multistranded copper conductor of different code of ISI marked drawn through and incl PVC casing caping of suitable size with accessories ISI marked incl PVC insulated copper cable for earth of same type and sized connected to earth dolly including provision of PVC box of suitable size for mounting switches / sockets and fan regulators etc complete all as specified and directed for the following:- Note: Cutting chases for laying conduct and sunken boxes and making good to walls, floors will be included in the above quoted rates.
(a) One light point controlled by one switch one way
(b) One ceiling fan / exhaust fan / wall mounting fan point controlled by one switch one way
(c) One socket outlet three pin 5/6 Amps controlled by one switch on the same board.
(d) One switch socket outlet three pin 5 /6 Amps controlled by one switch on independent board.
M&L for point wiring with stranded copper conductor 2.5 Sqmm (Nominal Area) Single core, Multistranded, FRLS , PVC insulated and unsheathed cable FRLS 1100 volts grade mult stranded for earth, ISI marked drawn in and including PVC casing caping of suitable size with accessories ISI marked including PVC insulated copper cable for earth of same type and sized connected earth dolly including provision of PVC box of suitable size for mounting complete all as specified and as directed.
S&F socket outlet (Multipurpose type) but 5A/15A flush type compete all as specified and as directed.
S&F switch flush type 15/16A complete all as specified and as directed.
M&L switch piano flush type single pole,one way, 5 Amps, 240 V complete all as specified and directed including taking down old U/S one.
S&F socket outlet 5/6 pin type,5 Amps, 240 V complete all as specified and directed including taking down old U/S one
S&F switch socket combination 5/6 pin flush type (multipurpose type) 5 Amps, 240V complete all as specified and directed including taking down old U/S one. .
S&F in replacement sheet metal enclosure Single pole and neutral 240 V with a two pin and earth plug and socket complete with one single pole MCB of 20 Amp complete all as specified and directed
S&F ceiling rose surface type with 3 terminals complete including taking down old U/S one .
S&F in replacement fan regulator electronic step type AC 240 Volts,50 Hz complete including taking down old U/S one .
S&F in replacement lamp holder,PVC/Polycarbonate type with back plate suitable for batten fittings complete all as specified and directed including taking down old U/S one.
S and F in replacement LED tube lights fitting. 1x18/20W all as specified and as directed.
Supply and Fix to wall / pole of any height LED bldg security light 36 watt IP 65 including GI pipe suitable size bracket not less than 1 metre bend to shape with 2 clamps, nuts, bolts, washers and PVC 3 core ISI mark flexible wire from ceiling rose to fitting complete including taking down u/s lights all as specified and as directed.
Taking down carefully sub main wiring including batten/ conduit/ERW stove enameled metallic rigid conduit by unscrewing from wall, ceiling and making good surfaces to match with original status as specified and directed.
Material and labour for Submain wiring with three single core with flame Retardant and low smoke (FRLSH), copper conductor three run 2.5 sqmm (Nominal area ) including earth conductor of same size using approved colour coding as IS (Red, Black and Green for single phase circuit), unsheathed stranded copper cable 1100 volts grade ISI marked with TEC and FIA approved and including drawing into surface mounted ERW stove enameled metallic rigid conduit of suitable size with necessary fixing accessories and fittings such as Tees, bends,elbow,juction boxes, connecters, saddles, screws, rowel plug etc all as specified and directed. Note:- (i) Three run of 2.5 sqmm and one run of ERW steel conduit shall be measured as one length. (ii) All coduit pipe and coduit accessories shall be totally enclosed IP-65 protection and certified by CMRI Dhanbad. (iii) The complete electrical installation/wiring and all equipment and apparatus shall be got tested and certified as totally enclosed as suitable for use in explosive building on completion by the " Director Central Mining Research Institute (CMRI) Dhanjbad. The testing charges complete and arranging tools, plants, testing equipments et shall be born by the contractor.
Material and labour for Submain wiring with three single core with flame Retardant and low smoke (FRLSH), copper conductor three run 4 sqmm (Nominal area ) including earth conductor of same size using approved colour coding as IS (Red, Black and Green for single phase circuit), unsheathed stranded copper cable 1100 volts grade ISI marked with TEC and FIA approved and including drawing into surface mounted ERW stove enameled metallic rigid conduit of suitable size with necessary fixing accessories and fittings such as Tees, bends,elbow,juction boxes, connecters, saddles, screws, rowel plug etc all as specified and directed. Note:- (i) Three run of 4 sqmm and one run of ERW steel conduit shall be measured as one length. (ii) All coduit pipe and coduit accessories shall be totally enclosed IP-65 protection and certified by CMRI Dhanbad. (iii) The complete electrical installation/wiring and all equipment and apparatus shall be got tested and certified as totally enclosed as suitable for use in explosive building on completion by the " Director Central Mining Research Institute (CMRI) Dhanjbad. The testing charges complete and arranging tools, plants, testing equipments et shall be born by the contractor.
M&L flame proof distribution board TPN 4 way ( Totally enclosed dust and flame proof /jet proof ( IP-65 protection) including flame proof MCB TPN 32-01 NOS, SP 5 to 30 Amps-12 NOS 240 volts AC 10KA (10 Nos) and RCCB 01 Nos 40 Amps, TPN MCB 40 Amps 415 volts AC 50 Hz 16 KA (01 No) Flame proof suitable for gas group I/IIA/IIB/IIC as per IS-2148 of 1981 , with complete internal bus bar & wiring upto terminals.
M&L flame proof distribution board SPN 8 way ( Totally enclosed dust and flame proof /jet proof ( IP-65 protection) including flame proof MCB SPN 32 Amp-01 NOS, SP 5 to 30 Amps-6 NOS 240 volts AC 10KA, Flame proof suitable for gas group I/IIA/IIB/IIC as per IS-2148 of 1981, with complete internal bus bar & wiring upto terminals.
S and F in repairs of sheet steel enclosure with double door flush mounting, MCB, DB, SPN, 4 ways, 240 volt factory fitted rated bus bars,earth bar,neutral links complete including. blanking plates as required and making good the disturbed surfaces.
S and F in repairs of sheet steel enclosure with double door flush mounting ,MCB, DB, SPN, 8 ways,240 volt factory fitted rated bus bars,earth bar,neutral links complete including. blanking plates as required and making good the disturbed surfaces.
S and F in repairs of sheet steel enclosure with double door flush mounting ,MCB, DB, SPN, 12 ways,240 volt factory fitted rated bus bars,earth bar,neutral links complete including. blanking plates as required and making good the disturbed surfaces.
S and F in repairs of sheet steel enclosure with Double door TPN 4 ways 440 volt factory fitted rated bus bars,earth bar,neutral links complete including blanking plates as required and making good the disturbed surfaces all as specified and as directed.
S and F in repairs of sheet steel enclosure with Double door TPN 8 ways 440 volt factory fitted rated bus bars,earth bar,neutral links complete including blanking plates as required and making good the disturbed surfaces.
S and F in repairs sheet metal enclosure single pole and neutral 240 V with a two pin and earth plug and socket complete with two pole MCB of 20 to 32 Amp complete all as specified and as directed.
S and F in replacement of MCB TPN 63 Amps 415V ,50 Hz ,breaking capacity 10 KA," C " series all as directed.
S and F in replacement of MCB SPN 40 Amps 240V ,50 Hz, breaking capacity 10 KA," C " series all as directed.
S and F in replacement of MCB SPN 20 to 32Amps 240V ,50 Hz, breaking capacity 10 KA," C " series all as directed.
S&F MCB SP 6-32 Amps 240V ,50 Hz, breaking capacity 10 KA," C " series all as directed.
Overhauling to ceiling fan of any size / sweep (i.e 1200mm sweep) complete by rewinding with new copper winding wire of same gauge with approved quality of super enamelled copper winding wire including varnishing heating and replacement of defected / unserviceable spares such as bearing , Canopy -02 Nos , down rod, Hanging clamp, capacitor, bushes by cleaning / oiling / lubricant and re-assembling , testing for proper functioning complete all as specified and as directed. NOTE : Copper winding wire including varnishing heating and repalcement of defective split pin shall deemed to be included in the item rate.
All as per ser item No. 42………. but for exhaust fan of 225 to 450 mm sweep complete all as specified and directed by Engr-in-Charge
M and L for painting of ceiling fan 1200mm sweep after prepation of old painted surface with one coat of white synthetic enamelled paint complete all as specified and as directed.
M and L for painting of exhaust fan 225 to 450 sweep after prepation of old painted surface with one coat of black synthetic enamelled paint complete all as specified and as directed.
Supply only Metal Bush suitable for Ceiling fans complete
Supply only Capacitor 2.5 mfd suitable for Ceiling fan complete
Supply only Capacitor 4 mfd suitable for Exhaust fan complete
Supply only ball bearing suitable for Ceiling fan, as per sample complete all as specified and directed
Supply only ball bearing suitable for Exhuast fan, as per sample complete all as specified and directed
S&F in repair 'U' clamp with nut bolts, washers, split pins, rubber bush of ceiling fan complete all as specified and directed.
S&F in repair outer cover top and bottom of celing fan motor suitable for 1200mm fan complete all as specified and directed
Supply only fan blade adjustable type, suitable for Exhaust fan 225 to 450 mm complete all as specified and as directed.(Set of three)
Supply only fan blade adjustable type, suitable for ceiling fan 1200mm complete all as specified and as directed.(Set of three)
Supply only stator suitable including connecting shaft suitable size for ceiling fan 1200mm sweep complete all as specified and as directed.
Supply only canopy suitable for Ceiling fan complete all as specified and directed
Supply only down rod suitable for ceiling fan 1200mm sweep suitable for ceiling fan complete
Supply and fixing multi strand three core 1.5 sqmm flexible copper conductor suitable for connection of ceiling fan from ceiling rose to ceiling fan complete.
Supply and fixing LED Serene recess mounting 1'x4' feet CRCA housing ,1x 36 Watt white powder coated, with polymer diffuser complete with accessories
M&L for earthing complete with galvanised steel earth plate electrode 60cm x 60 cm x 6 mm thick burried directly in ground (earth pit not less than 2.25M deep below ground level) with top edge of the plate not less than 1.5 M below ground level connected with galvanised earth wire 4 mm dia by means of bolts nuts check nuts and washers of galvanised iron to earth test point all as specified or indicated including necessary excavation and earth work any type of soil PCC (1:3:6) watering funnel with wire mesh, GI tubing 20 mm medium grage for watering, 15mm bore light grade for GI Protection, Charcole and salt in requisited quantity complete all as specified and directed and all as shown in electrical plate No.3 of SSR part 1. Note: GI earth wire and protection pipe upto 7.5m in length shall be included in quoted rate.
M/s MM TRADERS
MAHARASHTRA ENTERPRISES
M/S Maa Durga Constructions,Pulgaon
SHRI RANI SATI TRADERS
Paragon Electrotechnics
metro electrical services
SMART ENERGY SOLUTIONS
SHREE SIDDHIVINAYAK TRADERS
Bidder Name
Paragon Electrotechnics
SHRI RANI SATI TRADERS
SHREE SIDDHIVINAYAK TRADERS
MAHARASHTRA ENTERPRISES
metro electrical services
M/S Maa Durga Constructions,Pulgaon
M/s MM TRADERS
SMART ENERGY SOLUTIONS
I P Constructions
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .