Servicing overhauling dehydration of 500 KVA Kirloskar make transformer installed at TU Block SPS Pitampura
2026_DJB_287003_16
NIT No. 34(2025-26)M-VII
Open Tender
Miscellaneous Works
Item Rate
45 days
EE ENM M VII
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Account No 50448339804
₹5,600
Yes
21 Feb 2026
16 Feb 2026
23 Feb 2026
16 Feb 2026
23 Feb 2026
16 Feb 2026
Disconnecting of HT supply from main HT panel after proper switching off 11 KV discharging the supply. Complete drain out of transformer oil from transformer to empty oil drum by oil machine, dismantling of conservator tank all protection relays cable end boxes vent pipes and other items as required.
Cleaning of transformer oil tank and removing of sludge settled in the bottom with the help of vacuum pressure cleaning machine thoroughly, cleaning of core and winding of transformer with hot oil and proper safety precaution to prevent the winding damage as required, cutting of old overheated insulation of winding and re-insulation of weak point with the help of HT insulation material and proper taping etc.
Replacement of top cover gasket vertical vent gasket & missing hardware to stop the oil leakage.
Repairing of tape changer
Replacement of salica gel.
Complete assembling of transformer cleaning of complete transformer tightening of all connection of incoming and outgoing side and testing & checking of IR test with megger of winding & cable of both sides with HI pot machine.
Filling of T/oil to up to top up level as required to make power
P/Fixing of winding protection pad
Checking & matching of control wiring of all protection relays and calibration of bucchlaz relay and protection relays testing the same.
Repairing of LT Copper bolt, remettaling and finishing the same as per original shape and size.
Repair of cooling fins, replacement of cooling fins gasket and oil seal for stopping the leakage.
Dehydration & filtration of complete transformer oil and checking the die electric strength up to 50 KV at site as required.
Complete cleaning and chemically washing of oily and muddy transformer body and painting of transformer with enamel paint.
P/fixing of Heat Shrinkable Jointing Kit for transformer HT Cable as per site requirement.
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.50 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.15 MB
BOQ_380188.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .