Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.4 LAccepted-Finance | L1 | Accepted-Finance OK | |
| 2 | L2₹13.4 L+₹1.0 L (8.43%)Accepted-Finance | L2 | Accepted-Finance OK | |
| 3 | L3₹16.4 L+₹4.1 L (32.8%)Accepted-Finance | L3 | Accepted-Finance OK |
Tender Value
₹19.1 L
EMD Value
₹20,000
Closing Date
25 Jul 2025, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE ETC NOIDA
220 KV SUBSTATION SECTOR-20 NOIDA
Increasing capacity and construction of associated bay at 220 KV substation Dadri under ETD2 Noida
2025_UPTCL_1053747_1
E-T-14/ETCN/2025-26
Open Tender
Electrical Works
Item Rate
60 days
NOIDA
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,770
EE ETD NOIDA
₹20,000
20 Sept 2025
2 Jul 2025
26 Jul 2025
2 Jul 2025
25 Jul 2025
2 Jul 2025
Amount
Erection of Main & Auxiliary structure lattice type ATM, BTM, BCT, ALP etc. constisting of coloumn, beam, peak, mast etc. and auxilary structure for installation of CTs. PTs, LAs, etc. The job consist of shifting of all material from store to site of erection, erection of structure as per drawing with the help of GI nut & bolt, flat & spring washer, matching the hole, cutting & matching of member if required including cost of all men and T & P excluding GI structure Nut & bolt to complete the work. Erection of Main & Auxiliary structure lattice type BCT, ALP etc. upon foundation and its proper tighteing.
Erection of following Equipments/Panels as per technical specification, manual and instruction as per direction of supervising engineer.
245KV SF-6 Circuit Breaker.
245KV Current Transformer.
245KV Bus Isolator
245KV Line Isolator
245KV Tandem Isolator.
245KV Post Insulator for support
198KV Lighting Arrestors.
220KV Control & Relay Panel of 160MVA TF
245KV CT Junction box
145KV CB with structure
145KV Line Isolator
145KV Bus Isolator
145KV Tandem Isolator
145KV Post Insulator
Earthing Work
Earthing of 198KV/120KV LAs and netural of transformation by 40mm dia 3000mm long conical shape its placing inside the ground in rectangular shape and connectiong all 3/6 nos electrodes with 75X10/50X6 mm MS flat laid on its edge and then this rectangle/triangle shape strictlty as per drawing. (a) 198/120KV LA (rectangle shape by 06 electrodes) with 40MM dia round bar
160MVA Transformer (triangular shape by 03 Electodes) with 40MM dia round bar
Earthing of equipments by cutting straightening, bending, laying 700mm below ground and above ground of following size of MS flat for earthing of main and auxiliary structure equipments structure. Transformer body and its neutral point including welding with main earthmat and with object to be earthed, excavation of trenches, its back filling, including painting of MS flat with red oxide primer and Green paint to complete the work.
Laying MS Flat of size 75X10 MM
Laying MS Flat of size 50X6 MM
Laying MS Flat of size 25X6 MM
Laying of following size control cable in trench/cable trays from different control room equipments to 220/132/33KV CB, CT, CVT and their junction boxes. Transformer marshalling box, isolator box and other outdoor equipments installed in 132KV swithyard as per cable schedule including carriage of cable drum from store and all other associated work.
2 CoreX 2.5mm2
4 CoreX 2.5mm2
6 CoreX 2.5mm2
10 CoreX 2.5mm2
Termination of control cable at each end
Jumpering, interconnection of equipment with specified conductor of various 220KV bus isolator with main /Transfer of ACC Tarantulla with ACSR Zebra conductor, jumpering of 220KV bay equipment with zebra. The work includes cutting of conductor, bending in proper shap, clamping with the help of clamps and all other associated work to complete the work.
Stringing of all 3 Phases (R,Y & B Phase) of jack bus of 220KV with ACSR Zebra conductor, the work includes cutting & bending of conductor, fixing of single bolted type tension fitting/suspension. Hoisting of disc insulator and shifing of material form store site to erection site and all other associated work to complete the work satisfactory as per drawing and technical specification.
220KV Jack Bus for 160MVA Transformer for Zebra conductor
132KV Jack Bus for 160MVA Transformer by twin zebra conductor.
Jumpering, interconnection of equipment with specified conductor of various 220KV bus isolator with main/Transfer of ACC Tarantulla with ACSR Zebra conductor. Jumpering of 220KV bay equipment with zebra. The Work includes cutting of conductor, bending in proper shap, clamping with the help of clamps and all other associated work to complete the work.
Transformer Erection work
Shifting of 160MVA T/F with accessories from unloading point to plinth with the help of rail pulling devices sleepers etc upto distance of Approx 30 Mtrs including turning if required at 220KV substaion Dadri.
Complete Erection of 160 MVA Transformer and accessories HV/LV/TV/N bushing radiators, conservator tank. A frame, Header oil pipe line, pump cooling fan etc. oil filling up to required level
Centrifuging the transformer oil in main tank and circulate the transformer oil through centrifuging machine and taking BDV time to time. (Centrifuging machine shall be provided by the contractor)
Erection of RTCC Panel of new 160 MVA 220/132KV Transformer after shifting of RTCC Panel from stores/designated place to control room then making cable terminations as per cable schedule (to be prepare by contractor) and making earthing of the RTCC Panel
Installation of mulsifire system on 160 MVA (Installation of high velocity automatic water spraying system for 160 MVA TF inclduing laying of water pipe line, valves, quartzoid, HVWS nozzles along with all material complete)
Supply & Installation tesing commissioning of quick opeining folld, deluge valve of HD of 150 NB as per Max working pressure 10 Kg/cm² as per specification (HD/Mather Platt/equivalent in Nos)
Supply & installation of gate valve (Slucie valve/Butterfly valve) as per IS specification (IS code: 14846) (Zoloto/Kartar make) in Nos (i) 150NB
Supply & installation of "Y" Type strainer(Kartar/Kalpana/agro make) of Dia (i) 150 NB
Supply & laying of different size of M.S pipe B class for fire water pipe line support as per IS specification (IS code-1239) complete with elbow tee socket reducer ete. with anti corrosive treatment with details as below :
Supply & laying of different size of GI pipe B class for fire water pipe as per IS specification (IS code-1239) as per drawing enclosed completed with elbow TEE socket reducer.
Supply & laying of flanges as per IS- 1538 of different size as per drawing, work include proper butt welding with pipe & proper packing and coupling along with N&B
Supply installation & commissioning of high velocity water spray nozzles flow 3.5 KG/cm² spray core angle 90 degree
Supply installation & commissioinig of qratzioid bulb detectors (QBD) operate at 90 C sensing at rated temp for actuation of the element 10-12 sec.
Supply, installation & testing of fixed differential switch (Danfoss/Indofss make) type pressure switch range 1-10 KG cm²
Pressure guage as per IS specification IS code-3624
Dismantling of 245KV CB, Post insulator, CVT and shifting dismantled material to store.
Providing & fixing of phase plate (R,Y, B phase) of 02mm thick aluminum sheet of size 5' dia covering of 3 M HIP/MDF retro reflected sheet in single piece with all mounting with GI nut and bolts 1 set comprises of R, Y, B phase plates
Carriage of Miscellaneous material from different sub-stations (with in 50KM area) to 220KV S/S Dadri.
Safe carriage of loaded structure from fabrication unit to 220KV Dadri, Greater Noida approximate distance 710KM. Rate should be quoted for 710KM/mt
SATKAR TRADERS (BID ID -5369309)
Gupta Elect and Engg Works (BID ID -5374521)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .