| 2 | L2₹2.8 Cr+₹11.4 L (4.28%)Admitted-Finance 2 CORRIGENDUM ADDENDUM 01 DATED 11 01 2024 3 YOUR TENDER SUBMITTED ON 15 01 2024 ON E TENDER WEBSITE 4 CORRIGENDUM ADDENDUM 02 DATED 06 02 2024 5 YOUR PRICE BID OPENED ON 06 02 2024 ON E TENDER WEBSITE | +31.50% | ₹2.8 Cr+₹11.4 L (4.28%) | L2 | Admitted-Finance |
Tender Value
₹2.1 Cr
EMD Value
₹4.2 L
Closing Date
2 Jul 2026, 3:00 pmClosed
Executive Engineer
Electrical Division -02, Vikas Minar
Supply Replacement Testing and Commissioning of outdated Electric Sub Station equipments with DG set at DDA Roshanara Club.
2026_DDA_913315_1
14/EE(E)/ELD-2/DDA/2026-27
Open Tender
Electrical Works
Percentage
180 days
As per tender documents
Please refer Tender documents.
16 documents required · 16 mandatory
₹0
₹4.2 L
In the office of SE(E)/E and Sports,Vikas Minar
27 Jul 2026
16 Jun 2026
3 Jul 2026
16 Jun 2026
2 Jul 2026
19 Jun 2026
19 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supplying, Installation, Testing & Commissioning of indoor type floor mounted metal clad, 11 KV VCB panel totally enclosed & fully interlocked, horizontal drawout, horizontal/ vertical isolation floor rolling type breaker as per IS 13118, IEC-62271-100 & 62271-200 & 60694, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, Elecrically charged and auto/manually closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz A.C. supply with short circuit fault level of 500 MVA, rated Short circuit breaking capacity of 26.3 KA for 3 sec and internal arc fault withstand capacity of 26.3 KA for min. 1 sec complete with self contained, fully interlocked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of 800 Amps capacity, breaker featured with mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4 NO+4 NC and equipped with following switchgears and accessories i/c connections suitable for 3 core x 240 sq. mm. XLPE 11 KV cable (cable entry from rear bottom) end termination with heat shrinkable jointing material etc. as required.
Note :
(i) The Panel Board shall be OEM made only. Franchise made MV Switchboards shall not be accepted.
(ii) Cost of end termination not included in this item.
(iii) Panel shall be type tested from NABL accredited labs like CPRI/ ERDA etc. i/c Seismic Compliance Zone-IV and should be internal are tested AFLR (Front, Lateral, rear) protections as per IEC 62271-200.
INCOMER SWITCHGEAR PANEL
a) 1 No. 800 Amp. VCB, 500 MVA, 26.3 KA/3 sec.
b) Spring charged motor - 230 V AC
c) 1 No. – withdrawal type 11 KV / 110 Volts three phase PT of Class 0.5 OR 1.0 accuracy for metering, class 5P10 for protection.and 100 VA burden with associated encapsulated HRC fuses for primary isolation, space heater with 1 No. caliberated intelligent multifunction digital panel meter of 0.5 accuracy with multiline display with communication interface port RS485 for giving output on BECNET/ MODBUS protocol of IBMS for recording V, A, KVA, KVAR, KW, KWhr, pf etc. complete with wiring connections etc. as required at site.
d) 1 No. – (0-300 A) Ammeter, digital type with selector switch.
e) 1 No. – Microprocessor based numerical relay with O/L, E/F and S/C protection.
f) 1 No. – Set of dual core dual ratio 3 CTs 150/75/5/5 A of 15 VA burden and accuracy Class – 1.0 for metering and class 5P10 for protection.
g) Trip circuit supervision relay.
h) Control switch
i) Indication lamps for ON, OFF, TCH, Auto trip, R,Y,B indication, spring charging.
j) space Heater
k) Digital multi function meter , 96 X 96 mm with operation on MODBUS/ TCP-IP protocol.
l) Emergency push button.
m) 1 set of surge arrestors as per OEM recommendation.
n) Earth switch with making capacity for cable side earthing.
OUTGOING SWITCHGEAR PANEL
a) 2 Nos. 800 Amp. VCB, 500 MVA, 26.3 KA/3 sec.
b) Spring charged motor - 230 V AC
c) 2 Nos. – (0-100 A) Ammeter, digital type with selector switch.
d) 2 Nos. – Microprocessor based numerical relays with O/L, E/F & S/C protections.
e) 2 sets – Set of dual core dual ratio 3 CTs 60/30/5/5 A of 15 VA burden and accuracy Class – 1.0 for metering and class 5P10 for protection.
f) Trip circuit supervision relay.
g) Control switch
h) Indication lamps for ON, OFF, TCH, Auto trip, R,Y,B indication, spring charging, push buttons, space heater with thermostatcomplete with all standard accessories for each outgoing as required at site.
i) Hooter
j) Digital multi function meter , 96 X 96 mm with operation on MODBUS/ TCP-IP protocol
k) Emergency push button.
l) 1 set of surge arrestors as per OEM recommendation
m) Earth switch with making capacity for cable side earthing
n) Auxillary relays for protection of chilers.
o) 8 way alarm annunciator window.
p) Power pack with 220 Volt AC input & 24 Volt DC continuous output suitable for closing/ tripping/ indication of HT panel board with 2 Nos. 12 Volts each maintenance free batteries of 100 AH each for all 3 panels ( 1 I/C +2 O/G), charging unit, capacitor bank for emergency delivering for trip system complete with suitable capacity of Ammeter & Voltmeter i/c connections with 2.5 sq. mm FRLS insulated copper conductor cable etc. as required.
q) All necessary items required for completion of panel like MCBs, DBs etc. shall be provided alongwith the panel.etc complete as required. | 1 | Each | 35,97,746 | ₹35,97,746 |
| 2 | Supplying, installation, testing and commissioning of 800 KVA capacity (continuous loading) level 2 rated (Corresponding Level as per BIS amended upto date of receipt of tender) , 11/0.433 KV step down, 3 Phase, 50 Hz, Dyn 11 vector group, ONAN (Oil Natural Air Natural) copper wound transformer (Electrolytic grade 99.9% pure copper, Core made of first grade Cold Rolled Grain Oriented (CRGO) Core grade MOH or better, suitable for out door/indoor applications with On Load Tap Changer (OLTC) on HV side having AVR relay and Remote Tap Changer Control (RTCC) for automatic sensing of incoming voltage, automatic operation of OLTC and facility for remote and manual operation of OLTC HV side in range of +5% to -15% in steps of 2.5%, having cable end boxes on HV side suitable for 3x300 sqmm XLPE cable of 11 KV grade, including bus trunking / LT Cable 1.1 KV grade on LV side including supplying and laying of copper conductor multicore control cable from transformer to HT breaker/panel for safety tripping, complete with all accessories and safety provisions as per relevant IS Code including first filling of filtered dehydrated oil, i/c supplying and grouting of suitable M.S. Channel with all accessories and transformer shall be confirming to IS : 2026 (Part 1 to Part 5), IS : 1180 and as per CPWD specifications complete in all respects etc as required at site. The maximum flux density in any part of the core and yoke at rated voltage and frequency shall be such that the flux density with + 12.5 percent combined voltage and frequency variation from rated voltage and frequency does not exceed 1.9 Tesla. The permissible temperature-rise shall not exceed 35 0C for oil and 40 0C up to 200 KVA and 40 0C for oil and 45 0C for above 200 KVA for winding. Inside of tank shall be painted with varnish or liquid resistant paint. For external surfaces one coat of thermo setting powder paint or one coat of epoxy primer followed by two coats of polyurethane base paint shall be used. IS: 1180 (Part 3) shall be referred to for paint thickness for normal to medium corrosive atmosphere. For highly polluted atmosphere and special application external paint work shall be as per direction of Engineer-in-Charge. Design ambient condition: a) air temperature 50 0C, b) Relative Humidity 90 % Max, c) Seismic Zone as per location of site, d) Altitude as per location/site. Noise level Shall not exceed limits as per NEMA TR-1 with all accessories running measured as per IEC 551 / NEMA standard. The transformer should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc. Marking Each transformer shall be provided with rating plate made of anodized aluminium/ stainless steel material securely fixed on the outer body, easily accessible, as per IS: 1180 Part-3. The entries on the rating plate shall be indelibly marked. Fitting and Accessories : The following fittings shall be provided:- a) Two earthing terminals with the earthing symbol b) Oil level gauge indicating oil level at minimum, 30°C and maximum operating temperature; c) Air release device (for non-sealed type transformers) d) Rating and terminal marking plates; e) Silica gel breather f) Drain-cum-sampling valve (¾″ nominal size thread, IS 554) preferably steel with plug for three phase transformers; g) Thermometer pocket with cap; h) Oil filling holes having (1¼″ nominal size thread) with cover (for sealed type transformers without conservator); i) Lifting lugs for the complete transformer as well as for core and winding assembly; j) Pressure relief device or explosion vent above 200 kVA; k) One filter valve on the upper side of the tank (for transformers above 200 kVA); l) Unidirectional flat rollers (for transformers above 200 kVA); m) Inspection hole (for transformers above 200 kVA); n) HV side neutral grounding strip (where one of the HV bushing terminal is connected to earth); o) Buchholz relay for transformers above 800 kVA. p) Arcing horns or suitable rating lightning arrestors for HT side – 3 Nos. q) Bird guard; r) Oiltemperature indicator and winding temperature indicators for transformers above 200 kVA with suitable tripping mechanism abovepermissible limit s) Jacking pads (for transformer above 1 600 kVA); t) Additional Neutral separately brought out on bushing for earthing. u) Magnetic oil level gauge (for transformer above 1600 kVA) with low oil level alarm contact; v) Non return valve (for conducting pressure test); w) Pressure relief device or explosion vent x). Monogram Plate y) Inspection cover z). Detachable type radiators with top and bottom shutoff valve. aa) Oil Conservator with Oil level indicator, minimum level marking and drain plug for all transformers of capacity 50 KVA and above. bb) Necessary hardware, clamps, lugs etc. for termination on HV/MV etc. for all transformers. | 2 | Each | 15,30,525 | ₹30,61,050 |
| 3.01 | Sub Head II - HT Cable
Supply of 11 KV 3 core x 240 sq mm Stranded Compact Circular Aluminium Conductor, Conductor Screen With Extruded Semi Conducting Compound, XLPE Insulated, Insulation Screening with extruded Semi Conducting Compound in combination with Copper Tape, cores laid up, innersheath of PVC tape, galvanised flat steel strip armoured and overall PVC Sheathed Cable conforming to IS: 1554 (Part-2) 1988 amended upto date. Cross linked polyethylene (XLPE) insulated, PVC sheathed conforming to IS: 7098 (Part-2) -1985, 2011 (Reaffirmed 2021) amended upto date.
3C X 240 Sq mm | 80 | Meters | 4,790 | ₹3,83,200 |
| 3.02 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 kV grade of following size in the existing RCC / HUME/ METAL pipe as required.
Above 120 sq. mm and upto 400 sq. mm | 20 | Meters | 170 | ₹3,400 |
| 3.03 | Supplying and making indoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11KV grade as required : 240 Sq mm | 2 | Each | 4,144 | ₹8,288 |
| 3.04 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing masonry open duct as required.
Above 120 sq. mm and upto 400 sq. mm | 60 | Meters | 146 | ₹8,760 |
| 3.05 | Supplying and making outdoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :
240 Sq mm | 2 | Each | 7,010 | ₹14,020 |
| 4 | Sub Head III -LT PANEL AND APFC PANEL
Main LT Panel
Supply, Installation, testing & commissioning of dust damp and vermin proof factory built modular bolted construction extendable type PLC BASED AUTO SYNCHRONISING, AUTO LOAD TRANSFER, AUTO LOAD SHARING, AUTO LOAD BALANCING Main LT panel suitable for 415 V, 3 Phase, 4 wire 50 Hz. AC supply system fabricated in compartmentalized design from CRCA sheet steel of 2mm thick for frame work and covers, doors of 1.6 mm thick sheet & 3mm thick for glands plates having 4B segregation and IP 42 protection i/c cleaning and finishing complete with 9 tank process for powder coating of approved shade &color, short circuit withstand capacity of 31 MVA for 1 Sec. bottom base channel of MS Section not less than 75mm x 50mm x 5mm thick, fabrication shall be done in transportable sections, entire panel shall have a common aluminum earth bar of size 50mm x 6mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring with 2.5 Sq mm. FRLS PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half having knock outs for cable glands of required size. Panels shall be suitable for 415V, 3-phase, 4-wire, 50Hz supply system and with 20% spare space, lifting hooks shall also be provided in case of large panels. (Panel shall be as per IS/ IEC 61439 (part 1 & 2) type tested from NABL accredited labs like CPRI/ ERDA etc. i/c. Seismic Compliance Zone-IV and should be internal arc tested at 50KA for 0.1-0.5 sec. as per IEC 61641. Panel should also have minimum mechanical impact strength of IK09 as per IEC 62262)
All ACBs should have Ics=Icu=Icw for 1 sec
All MCCBs shall be rating for 50kA (Ics=Icu). All MCCBs above 63A should be provided with Copper Spreader Terminals
Approval shall be taken for each panel before fabrication. Galvanized hardwares with zinc passivation shall be used in fabrication of panels.
Panel Vendor shall coordinate with the Main Electrical Contractor .
Surge suppressor of 36 KA shall be provided between phase to neutral and neutral to earth at each bus section.
All MCCBs will have adjustable microprocessor O/L, S/C & inbuilt E/F protections.
All outgoings shall be rating for 50kA (Ics=Icu for 1 sec)
Set of RYB phase indicating lamps with control MCBs on each outgoing to be provided. Each backed up with 2A MCB.
ACB outgoing shall be provided with Trip lamp also.
All Multifunction meters are suitable (Transformer shall be provided with suitable ratio CL-1, 15VA Cast resin CTs.
All outgoings shall be provided with multifunction meters of 3-phase, with all functions with RS 485 communication port.
Cable entry suitable from top and bottom
DLP Gas flooding system using heat detection tube for complete LT Panel including Gas, Gasbank, tubes , LP Switch, Master control unit, associated piping network, actuators, valves etc complete as required.
Interlocking between transformer and bus-couplers feeders shall be provided to avoid Paralleling power supply of Discom.
Details:
(i) Incoming From Transformer's (2 Nos. 800 KVA) Incomer feeder - 2 Nos.
a) 1250 A, 4P, 50 KA Air Circuit Breaker Horizontal drawout type of fault breaking capacity 50KA (Ics=lcu =Icw for 1 sec) upto 690V) Electrical Draw Out Motorized operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS-13947-2 1993 as amended up-to-date complete with following accessories for each ACB - 2 Nos.
b) Independent Electrical / manual spring closing mechanism - I No.
c) Microprocessor release (EMI & EMC certified) for over current, earth fault & short circuit protection - I set.
d) calibrated Intelligent multifunction digital panel meters of class 0.5S accuracy with communication interface port RS 485 for recording Voltage (Between Phases and between each phase and neutral), Current (In each Phase and neutral), KVA, KW, KWhr, KVAR, pf, 64 samples/cycle, Total harmonic distortion, with suitable rating CTs etc. complete with wiring , connections etc.
3 Nos. Phase indication LED lamps with 2 Amp back up MCB, breaker 'ON/OFF' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.
Shunt trip coil 220V A.C.
27-Undervoltage with definite time relay - 1 No
1 No. DC under voltage trip relay
(ii) Bus coupler
1250 Amp 4 pole ACB - 1 set.
a)Air Circuit Breaker Horizontal drawout type of fault breaking capacity 36KA (Ics=lcu =Icw) upto 433V) Electrical Draw Out Motorised operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS-13947-2 1993 as amended up-to-date complete with following accessories for each ACB 1 no.
b) Independent Electrical / manual spring closing mechanism - I No.
c) 3 Nos. Phase indication LED lamps with 2 Amp back up MCB, breaker 'ON/ OFF' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.
Bus coupler shall have equipped with the following:
Shunt trip coil 220V A.C.
Breaker Control Switch - 16A (MCB 10 KA)
(iii) Bus Bar
1600 Amps capacity TPN aluminium extensible type main bus bars of minimum of (As per capacity of corresponding incoming / Bus couplers), and auxiliary bus bar of suitable capacity with heat shrinkable coloured sleeves and i/c DMC/ SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 35 MVA for 1 Sec. (N=50%)
(iv) Outgoings:-
All Microprocessor based release ACB/ MCCB of following capacity and rating, 36 KA (Ics=Icu= 100% upto 690 V) with 3 phase 4 wire dual source type Multifunction meter of class 0.5S accuracy with communication interface port RS 485 for recording V-V (Between Phases and between each phase and neutral ), current ( In each Phase and neutral), KVA, KW, KWhr, KVAR, pf, 64 samples/cycle, Total harmonic distortion, with suitable rating CTs etc. complete with wiring , connections etc.
800 A 36 KA, 4P ACB - 2 Nos. (essential panel +1 no spare)
630 A 36 KA 4P MCCB=2 nos (for capacitor panel)
400 A 36 KA, 4P MCCB - 1 Nos. ( for non essential panel)
All Thermal magnetic based release MCCB of following capacity and rating, 36 KA (Ics=Icu= 100% upto 690 V) with 3 phase 4 wire dual source type Multifunction meter of class 0.5S accuracy with communication interface port RS 485 for recording V-V ( Between Phases and between each phase and neutral ), current ( In each Phase and neutral), KVA, KW, KWhr, KVAR, pf, 64 samples/cycle, Total harmonic distortion, with suitable rating CTs etc. complete with wiring , connections etc.
250 A 36 KA, 4P MCCB - 2 Nos.
160 A 36 KA 4P MCCB - 2 Nos.
63 A 36 KA 4P MCCB - 1Nos.
Interlocking:
Electrical Interlocking through advance contacts/ contactors in MCCB/ ACB's (Incomers & Bus couplers) should be provided to ensure that only one supply is available at a time on each section of bus and to eliminate any possibility of accidentally approaching two supplies at one bus section as per single line diagram enclosed.
HMI- 1 set
Necessary interlocking with PLC auto controls such that 2 Nos. T/F incomer, 1 No Bus cupler, 1 Nos DG incomer, shall be successfully operational in all possible combinations.
MV panel as above
APFC Panel | 1 | Set | 38,60,044 | ₹38,60,044 |
| 5 | HYBRID Power Factor Correction System
Supply, Installation, testing and commissioning of 250 KVAR HYBRID APFC Panel, 3 phase 4 wire, 415 V, 50 Hz AC System for Ambient temperature -5°C to +40°C of following capacity with passive solution of 60% capacity and active solution of 40% capacity,3Phase 4 wire Hybrid Power Factor Correction Solution (with arrangment for neutral current balance) to achieve >0.99 lag and TDDI/THDV values within IEEErecommended limits.APFC should be designed as perIS 16636 Or IEC 61921. The active section andpassive section shall work in sync to give optimizedoutput. The degree of protection of passive sectionshould be IP 42, and of active section should beminimum IP 21.The switching device for APFCpassive section should be through capacitor dutycontactor and for the active compensation systemshall be IGBT based with 3 level topology having 12 IGBT in inverter circuit. The active compensation system should filter harmonics from 2nd to 50th individual harmonic order and shall be selectable for the entire range. The active compensation systemshould have feature to improve PF correction andharmonic filtration having response time < 100 Microsecond. The hybrid panel shall be indoor type floormounted free standing totally enclosed, extensible,fabricated in compartmentalised designed made ofCRCA sheet steel of 2.0mm thick for framework &covers, 3 mm thick for gland plate i/c cleaning & finishing complete with 9 tank process for powder coated of approved shade ( RAL 7032-Siemens gray or as approved by Engineer-in-Charge), having front section (switch gear and control accessories) and rear section (capacitor and reactor), front and rear access, having suitable current carrying capacity, extensible TPN Aluminium alloy bus bar of high conductivity, DMC/SMC bus bar supports,bottom base channel of MS Section, fabrication shall be done in transportable section, entire panel shall have common copper earth bar of minimum size of 25mm x 5mm with 2 nos. earth studs, the earth terminals provided on the body of capacitorba shall also be bonded to the main capacitor panel earth bus with 2 nos. 8 SWG or 6 SWG GI earth wires/ equivalent size of copper conductor cable, forced ventilation for maintaining temperature rise not more than 5°C from ambient, interconnections, connections with 14% detuned reactor and heavy duty 525 V ISI marked Impregnated MPP(Metalized Polypropylene) Capacitor (IS 13340 Part -1 & 2) APFC Panel shall be in compliance with IS :16636 & CPWD Specifications etc. as per below
details.
(A) Incomers
Suitable capacity MCCB/ACB (Upto 300 KVAR, MCCB and above 300 KVAR, ACB ) Microprocessor base with O/C, S/C, E/L release of TPN 50KA breaking capacity (Ics=Icu), ON, OFF, Trip, R, Y, B - LED Indicating Lamp set alongwith required Instruments and accessories with extended rotary handel and door interlocking arrangment. Current rating of the Incomer in ampere shall be APFC Panel rating in KVAR x 1.4 x 1.5 or Nearest higher standards rating.
(B) Instruments & Indications
a)For Passive Section :
i) 3-Phase current sensing APFC microprocessorrelay/controller , advance 12/16 stages (12 stages forover all capacity of panel (active + passive) below 500KVAR and 16 stages 500 KVAR & above) and havingdisplay of Phase wise V, A, PF, Cos-Phi, KW, KVA,KVAR, THD-V , THD-I, harmonics up to 31 level.
ii) Auto Manual Selector switch, auxiliary contactorswith timer for delay in manual mode.
iii) V,Digital Multi function meter with LED Display for A, PF, KW, KVA, KVAR, THD-V & I, Frequency.
iv)Suitable rating control transformer shall beprovided for control and indication circuit.
v) All components like control transformer, meter,relay and indicating lamp shall be protected by usingsuitable rating individual MCB's.
vi)Wiring of the control circuit shall be done by using
2.5 sq mm, FRLS/HFFR 1100 V grade, PVC insulatedmulti stranded copper control wire.
vii)Communication Ethernet/RS485/SNMP port openprotocol for BMS integration as per approved byEngineering in charge.
b) For Active Section : Dedicated HMI(Human Machine Interface) (Minimum 7 inchdisplay) for controlling and communication andhaving display of Phase wise V, A, PF, Cos-Phi, KW,KVA, KVAR, THD-V , THD-I, harmonics up to 50thlevel. Communication Ethernet/RS485/SNMP portopen protocol for BMS integration as per approved by Engineering in charge | 2 | Each | 13,65,289 | ₹27,30,578 |
| 6 | Supply, Installation, testing & commissioning of LT panel suitable for 415 V, 3 Phase, 4 wire 50 Hz. AC supply system fabricated in complartmentalized design from CRCA sheet steel of 2mm thick for frame work and covers, doors of 1.6mm thick sheet & 3mm thick for glands plates having 4B segregation and IP 42 protection i/c cleaning and finishing complete with 9 tank process for powder coating of approved shade & colour, short circuit withstand capacity of 31 MVA for 1 Sec. bottom base channel of MS Section not less than 75mm x 50mm x 5mm thick, fabrication shall be done in transportable sections, entire panel shall have a common aluminium earth bar of size 50mm x 6mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring with 2.5 Sqmm. FRLS PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half having knock outs for cable glands of required size, .Panels shall be suitable for 415V, 3-phase, 4-wire, 50Hz supply system and with 20% spare space, lifting hooks shall also be provided in case of large panels. (Panel shall be as per IS/ IEC 61439 (part 1 & 2) type tested from CPRI/ ERDA/ ASTA/ DEKRA i/c. Seismic Compliance Zone-IV and should be internal arc tested at 50KA for 0.1-0.5 sec. as per IEC 61641. Panel should also have minimum mechanical impact strength of IK09 as per IEC 62262). "( LT panel for essential services )
A ) INCOMER
i) 1 Nos. 800A, 50kA, Air Circuit Breaker Horizontal drawout type of fault breaking capacity 50KA (Ics=lcu =Icw =100% for 1 sec) upto 690V) MDO Motorized operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/ isolated position indicators and frame earthing contact, conforming to IS-13947-2 1993 as amended up-to-date complete with following accessories for each ACB(780 AMP Load in whole building)
ii) Independent Electrical/ manual spring closing mechanism - 3 Nos.
iii) Microprocessor release(EMI & EMC certified) for over current, earth fault & short circuit protection - 3 set.
iv) calibrated Intelligent multifunction digital panel meters of class 0.5S accuracy with communication interface port RS 485 for recording Volts (Between Phases and between each phase and neutral ), Current (In each Phase and neutral), KVA, KW, KWhr, KVAR, pf, 64 samples/cycle, Total harmonic distortion, with suitable rating CTs etc. complete with wiring, connections etc.
v) 6 Nos. Phase indication LED lamps with 2 Amp back up MCB, breaker 'ON/ OFF' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.
B) BUSBARS
i) 1200 Amps capacity TPN aluminium extensible type main bus bars & auxiliary Bus Bars of suitable capacity with heat shrinkable coloured sleeves and i/c DMC/ SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 36kA capacity
C) OUTGOING
i) 2 Nos- 250 Amps FP MCCB, 36 KA thermal magnetic based release(O/C & S/C) protection.
ii) 1 Nos- 400 Amps FP MCCB, 36 KA MCCB thermal magnetic based release(O/C & S/C) protection.
iii) 2 Nos- 63 Amps FP MCCB, 36 KA 4P MCCB thermal magnetic based release(O/C & S/C) protection.
iv) 6 No-125 Amp FP MCCB,36 KA thermal magnetic based release(O/C & S/C) protection
vi) 16A Switch Socket - 1 nos. for lighting in emergency (panel illumination). | 1 | No. | 12,04,230 | ₹12,04,230 |
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 3.05 MB
NIT14.pdf
Tender Documents • 3.88 MB
BOQ_959817.xls
BOQ • 0.38 MB
coor14.pdf
PDF • 0.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .