Tender Value
₹48 L
EMD Value
₹96,000
Closing Date
6 Jan 2020, 6:00 pmClosed
CWE (AF) Gurgaon
HQ CWE (AF) Gurgaon, Old Palam Road, Delhi Cantt-110010
REPAIR MAINT OF VOLTAGE STABILIZERS DG SETS LT DISTRIBUTION SYSTEM AND ALLIED WORKS AT AF STN GURGAON UNDER GE AF GURGAON
2019_MES_304609_1
CWE/GGN/G-40/2019-20
Open Tender
Civil Works
Item Rate
180 days
GE (AF) Gurgaon
As per NIT
8 documents required · 8 mandatory
₹500
GE (AF) Gurgaon
₹96,000
Yes
4 Feb 2020
7 Dec 2019
7 Jan 2020
7 Dec 2019
6 Jan 2020
21 Dec 2019
7 Dec 2019 - 28 Dec 2019
Amount
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel single door floor mounted and wall/pole mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15 mm thick of outer body of suitable size with aluminium bus bar 1400 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following complete all as specified and directed and including (Location Dhobi Ghat): -
Incoming
(a) ACB, 4 Pole, 415 Volts, 800 Amp, 50 KA breaking capacity drawout type-01 No
(b) Alum bus bar 1400 Amp TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3 pole, 250 Amp, 25KA, 415 V AC - 02 Nos
(b) MCCB 3 pole, 160 Amp, 25KA, 415 V AC - 02 Nos
(c) MCCB 3 pole, 100 Amp, 25KA, 415 V AC - 05 Nos
(d) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel single door floor mounted and wall/pole mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15 mm thick of outer body of suitable size with aluminium bus bar 1000 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following complete all as specified and directed and including (Location - Behind Old camp Mandir) : -
Incoming
(a) MCCB, 4 Pole, 415 Volts, 630 Amp, 50 KA breaking capacity -01 No
(b) Alum bus bar 630 Amp TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3 pole, 320 Amp, 36KA, 415 V AC - 02 Nos
(b) MCCB 3 pole, 200 Amp, 25KA, 415 V AC - 02 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel single door floor mounted and wall/pole mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15 mm thick of outer body of suitable size with aluminium bus bar 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following complete all as specified and directed and including (Location - Near Sancharika School): -
Incoming
(a) MCCB, 4 Pole, 415 Volts, 320 Amp, 36 KA breaking capacity -01 No
(b) Alum bus bar 630 Amp TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3 pole, 125 Amp, 25KA, 415 V AC - 06 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Isolate/de-energize the supply to the LT Panel Board of capacity ranging from 200 Amps to 2000 Amps and voltage 415 Volts/230 Volts, opening the doors/covers of the cubical enclosure for carrying out the servicing/maintenance/repairs of the Panel Board, switch gear, metering etc and re-fixing the same in place after repairs including testing and commissioning of the paenl board comprising of the following:-
a) Cleaning the inside switch gear chambers for removing dust, carbon and rusted surfaces including cleaning with blower and apply insulating varnish.
b) Check the condition of the DMC/SMC support insulators including cleaning applying Dr beck red for better IR values and replacement of insulators if required.
c) Tightening up of all bus bar connections, cable connections, replace bolt, nuts wherever required.
Note : Contractor has to inspect the site before quoting. Any modifications/frame work and renewal is deemed to be included in the quoted rates. Spares will be measured and paid under relevant items of schedule
S&F in repair mild steel hinges suitable for LT panel board shutters incl welding, riveting complete all as specified and as directed.
Disconnecting and taking down existing bus bars 4 wire system from LT panel board cleaning with CTC applying with becktol solution, removing old insulation and providing new heat shrink insulating sleeves, connecting and fixing in the same panel with new nuts, bolts, washers of suitable size complete all as specified and directed.
Disconnecting and taking out old existing worn out control wiring connections incl cable lugs of LT panel board of 4 wire system and supply and connect with new cable PVC insulated, stranded copper conductor 2.5 sqmm incl new copper lugs and nuts, bolts, washers complete all as specified and directed.
Disconnecting and taking out old existing worn out cable lugs, nuts, bolts, washers etc from LT panel board of 4 wire system (incomming and outgoing) and supply and connect with new aluminium lugs and nuts, bolts, washers etc complete all as specified and directed.
Taking out old existing worn out neoprene gasket from shutters of LT panel board single door /double doors or openable on both sides and supply and fix new neoprene gasket complete all as specified and directed.
S&F in repair/replacement MCCB 400 A ,4 pole ,36 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning complete all as specified and directed.
S&F in repair Indicating lamp 240 volts LED type complete all as specified and directed.
Supply, laying and testing in replacement of cable XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 Volts grade cross sectional area 3.5 core x 240 Sq mm. complete all as specified and as directed. Note : Provision of suitable double crimpped lugs and glands deemed to be included in quoted rates.
All as per Srl item No. 14.00 but 3.5 core 185 sqmm
All as per Srl item No. 14.00 but 3.5 core 150 sqmm
All as per Srl item No. 14.00 but 3.5 core 120 sqmm
All as per Srl item No. 14.00 but 3.5 core 95 sqmm
All as per Srl item No. 14.00 but 3.5 core 70 sqmm
All as per Srl item No. 14.00 but 3.5 core 50 sqmm
All as per Srl item No. 14.00 but 4 core 25 sqmm
All as per Srl item No. 14.00 but 4 core 16 sqmm
Supply & Installation of Maintenance Free Earthing System consisting of a Copper bonded steel rod shall have 17.2 mm dia. & min. 10 feet length as per UL 467. The material shall have low carbon, high tensile steel molecularly bonded with 99.99% pure electrolytic grade copper thickness of minimum 250 microns with an exothermically welded Cu Busbar of (50X6X200mm) both tested by CPRI at 25 kA Fault Current carrying capacity. Copper Bonded Rod shall be UL listed. The manufacturer shall be RDSO approved to ensure the manufacturing capacity & capability along with the quality of the earthing rod. Along with a sealed bag of minimum 30 kg (10 kg Bag x 3) RoHS tested Earth Enhancement Compound tested by NABL accredited lab in compliance to IEC 62561-7 with a resistivity of not more than 0.12 ohm-m. It shall be a carbon based material and shall be free from bentonite and other hazardous substances. It shall be a permanent, non-corrosive material and will not leach any chemicals into the ground. It shall retain moisture even in high soil resistivity areas. It shall lower an earth resistance value and shall offer a constant desirable performance. Including an Earth Pit cover shall be made of Poly plastic tested at 7.5 ton load for closing of earth complete all as specified and directed
S&F Earth conitnuity Copper clad steel conductor or main earthing lead fixed to wall on batten or reccess or chases or burried in ground or drawn in conduit/pipe or fixed to pole or any other indicated situation for loop earthing etc as required 8 mm dia after taking down the old one any type complete all as specified and directed
M&L for Boring of holes under road, pavement,hard standing by trenchless technology using ultra sound technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and as directed.
Supply and lay in trenches /under roads/ crossing or fixed to wall/ pole, GI tubing light grade of size 40mm bore for protection of UG cables complete all as specified and as directed.
All as per Item No. 26.00 above but 80 mm complete all as specified and directed.
M&L for defect rectification high tension or LTcable laid in trenches by locating fault with the help of electronic fault locating machine comprising of surge generator pulse, ECHO fault locator with high frequency distance calculator etc.including and additional excavation in normal alluvial strata required for exposing the cable fault ; removal of deteriorated portion of cable treating of cable and keeping the same ready for jointing work for cable of size up to 185 Sq mm three core. The fault locating equipments will be brought to site within the hours of instruction from Engr-in-Charge complete all as specified and directed.
M&L in repairs removing the UG cable for rectification of faults after fault detection excavating the area and Crimping with suitable ferrules/lugs or any other misc items providing suitable insulation tape and relaying complete after rectification of faults complete all as specified and as directed. Note: Excavated area shall be made good to original finish and no extra payment will be done on this account. The items like Lugs, Ferrules, nuts, bolts if any are deemed to be included in the rates quoted and no extra payment will be done on this account complete all as specified and directed Note: Item No 28.00 & 29.00 shall be attended immediately on intimtion by phone or SMS failing which an amount of Rs 5000/- per day after 2 days will be recovered as penality.
Excavation in trenches n exc 1.5 wide and n exc 1.5 m in depth for foundation etc or for laying cable etc n exc 10 Sqm on plan and n exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and as directed.
Returning filling in including spreading, leveling, watering and well ramming in layers n exc 25 cm complete all as specified and as directed.
Removal of excavated material/surplus soil to a distance n exc 50m and depositing where directed at a level n exc 50m above the starting point complete all as specified and as directed.
Supply and filling river sand in trenches including spreading for cushioning of LT UG cable complete all as specified and as dirceted. Note : Punned down thickness shall be measured and paid .
M&L for sub class ‘B’ bricks old size laid flat dry in trenches over cable, across the direction of cable complete all as specified & directed .
Supply & Fix in repairs Mild steel plates, chequered, 5mm thick or over in thickness in available sizes of Fe 410-W (Gde-E-250) quality-A for covering cable trenches complete all as specified and directed.
Supply and Fixing in replacement of security Light for use on top of the watch tower cabin with motorised system: 400 W HPSV high intensity, long range, weather & dust proof motor operated Security Search light with highly polished stainless steel reflector-cum-body, suitable heat sinks, toughened front glass, retaining ring, M.S. Cradle and passivated bolts. The search light would be supplied with 230 V ,400 Watt HPSV Lamps with control gear in cast alumiminum housing, The search light fitting would be suitable for installing on the roof of the watch tower cabin. The search light would be swiveling type & have both vertical & horizontal operational controls with the help of remote control unit with suitable control cables complete all as specified and directed. Make:Kalin/Dragon/Superoptics sale.
Dismantling and taking down existing LED light fittings with safty from pole bracket and refix the same on newly installed pole complete all as specified and directed.
Dismantling concrete poles any size complete and setting aside complete all as specified and directed.
S&F and erection steel tubular swaged pole type 410SP-31(9 Mtr long) complete with CI base plate,taper plug,bolts,nuts,and screws etc duly painted internally and externally with metal oxide anti corrosive paint before errection and painting with two coats aluminium paint after erection complete all as cofirming to IS 2713 (part-1 to 111) and complete all as specified and directed.
Note : Necessary earth work and concrete shall be measured and paid separately
PCC M-10(nominal mix) using 40mm graded crushed stone aggregate in as in foundation filling and mass concrete including necessary form work complete all as specified and directed.
Supply and jointing in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size 185 to 240 Sqmm 3.5 core complete all as specified and directed.
Supply and jointing in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size 70 to 150 Sqmm 3.5 core complete all as specified and directed.
Supply and jointing in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size 25 to 50 Sqmm 3.5 core complete all as specified and directed.
Supply, fixing, testing and commissioning in replacement of LT feeder pillar panel single door floor mounted and wall/pole mounted outdoor type, as per IP-55 grade, made out of MS sheet 3.15 mm thick of size 540x525x200mm with aluminium bus bar 250 Amps, 4 strip (3 phase) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking with 150 Amps 16 KA MCCB four pole for incomer cable, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands etc and providing fixing arrangements including earthing lead fixing arrangement, complete all as specified and directed. Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel single door floor mounted and wall/pole mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15 mm thick of outer body of suitable size with aluminium bus bar 400 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following complete all as specified and directed and including (Location - P-157): -
Incoming
(a) MCCB, 4 Pole, 415 Volts, 320 Amp, 36 KA breaking capacity -01 No
(b) Alum bus bar 400 Amp TPN -01 Set
(e) Indicator lamp LBD type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3 pole, 100 Amp, 16KA, 415 V AC - 08 Nos
(b) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
S&F in replacement of u/s Solar panel in replacement for Intergrated Solar Street light 30 watt LED with intergrated Solar Street light 30 watt LED with Li-ion battery with kit with hardware, connector & panel for installation of street light with Pole, with suitable dia for street light fitting with all fixing arrangements like nuts, bolts, clamps, PCC foundation etc complete all as specified and directed. Note: Earth work & PCC foundation is included in quoted rate. Make :- (Havells /Halonix/ Crompton)
M&L for painting of steel tubular pole including cable protection pipe and all iron parts of 9 mtr long pole complete with 2 coats of aluminium paint after cleaning all rust and dust and preparing surface with wire brush and including strips of white and red colour of synthetic enamel paint up to the height of 1.5 mtr from the bottm of the pole complete all as specified and as directed. Make : Nerolac/Asian paint
S&F MCCB 250 A ,3 pole ,25 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning complete all as specified and directed.
S&F MCCB 200 A ,3 pole ,25 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning complete all as specified and directed.
S&F MCCB 125 A ,4 pole ,16 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning complete all as specified and directed.
Supply and Fix in replacement of old unserviceable pole box with new weather proof street light junction box of size 250 x 140 x 95mm and connecting terminals 4 way and fixing with street light poles using necessary MS clamps, nuts, bolts washers, lugs for incoming and out going cables, gland for cable etc of suitable size complete all as specified and directed.
Supply and fixing weather proof street light junction box of size 300 x 200 x 105mm including MCB SP 6 Amps and connecting terminals 4 way and fixing with street light poles using necessary MS clamps, nuts, bolts washers, lugs for incoming and out going cables, gland for cable etc of suitable size complete all as specified and directed. Note : The rates quoted are inclusive of provision and fixing of suitable lugs and glands for cable connection.
Material and labour for PVC flat three core 2.5 sq mm aluminium wire 1100 volt grade laid in 20 mm dia medium grade rigid PVC conduit (and fixing brackets on PCC pole) from Loop-in-loop out junction box to light fitting terminal complete all as specified and directed. Note :- PVC conduit shall be clamped properly with suitable clamps and no extra payment will be done on this account.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel single door floor mounted and wall/pole mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15 mm thick of outer body of suitable size with aluminium bus bar 1000 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following complete all as specified and directed and including(Location - Near P-104):-
Incoming
(a) MCCB, 4 Pole, 415 Volts, 630 Amp, 50 KA breaking capacity -01 No
(b) Alum bus bar 1000 Amp TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3 pole, 320 Amp, 25 KA, 415 V AC - 01 Nos
(b) MCCB 3 pole, 160 Amp, 25 KA, 415 V AC - 03 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel single door floor mounted and wall/pole mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15 mm thick of outer body of suitable size with aluminium bus bar 400 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following complete all as specified and directed and including (Location - Near P/H No - 02) : -
Incoming
(a) MCCB, 4 Pole, 415 Volts, 320 Amp, 36 KA breaking capacity -01 No
(b) Alum bus bar 400 Amp TPN -01 Set
(e) Indicator lamp LBD type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3 pole, 200 Amp, 25 KA, 415 V AC - 02 Nos
(a) MCCB 3 pole, 125 Amp, 25 KA, 415 V AC - 01 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel single door floor mounted and wall/pole mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15 mm thick of outer body of suitable size with aluminium bus bar 1200 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following complete all as specified and directed and including (Location - Near P-186): -
Incoming
(a) MCCB, 4 Pole, 415 Volts, 630 Amp, 50 KA breaking capacity -01 No
(b) Alum bus bar 1200 Amp TPN -01 Set
(e) Indicator lamp LBD type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3 pole, 250 Amp, 25 KA, 415 V AC - 01 Nos
(b) MCCB 3 pole, 100 Amp, 25 KA, 415 V AC - 04 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Dismantling of exist gauge System and S/F of engine protection unit along with annunciation panel with start/stop relay of 60 amps suitable for analyzing the fault in case of LLOP, HWT, OSR & spare module for any additional safety to be added along with analog indicator for quantity of high speed diesel in the tank, RPM of engine, pressure of the engine to run all these parameters on the manual mode in the engine operation complete all as specified and directed.
Repair and maintenance of DG Set for 'B' Check with S&F replacement of consumables for 'B' Check of any make including replacement of diesel filter, lubricating oil, rubber hose pipe, V-belt, Oil pipe, diesel pipe and worn out parts and tight of nuts, bolts, washers, greasing etc. for proper running of following DG Set complete all as specified and directed. Note: Engine oil & coolant will be measured and paid under relevant items of schedule
Dismantling of radiator fan engine of following capacity, cleaning and chocked tubes after draining out water, washing with caustic, descaling and brazing for water leakage etc. and refixing the same properly of following complete all as specified & directed :
Supply only the following items of DG Set of various capacity :-
a) Battery terminal, lug, bolts type suitable for heavy duty battery.
b) Battery leads for copper conductor multiwired.
Dismantling existing U/S battery charger & S/F of SMPS type battery charger suitable for 24V DC with auto cut off from trickle to boost alongwith AC lead to charge the battery when DG Set is not in use complete all as specified and directed.
Dismantling existing U/S battery charger & S/F of SMPS type battery charger suitable for 12V DC with auto cut off from trickle to boost alongwith AC lead to charge the battery when DG Set is not in use complete all as specified and directed.
Dismantling existing U/S mains voltage monitor from the AMF Panel & S/F of SMPS type AVR system for operation from 90 - 300 volt AC only on the main supply to with stand the exist contactor coil even when the main voltage drops high 90 - 300 volts complete all as specified and directed.
Dismantling of exists U/S asbestos rope and S/F asbestos rope 20 mm dia wrapped over the exhaust pipe complete and piping applicable of smooth finishing complete all as specified and directed.
Taking out FIP from DG Set transporting to service center for overhauling/calibration and refixing on DG Set after replacement of worn out parts such as delivery valves,plunger, O-ring, Spring rotor assembly etc of following complete all as specified and directed.
Dismantling of exist dipstick type fuel gauge and S/F fuel level gauge center inside the exist fuel tank to measure the quantity of diesel inside the fuel tank with all accessories like capacitence resistance, Zink plate, steel stens of required length as per depth of fuel tank and ballown along with facility for triping the generator in case of low fuel alongwith audio visual alarm complete all as specified and directed.
Taking out of turbo charger from DG Set transportation to workshop for repairing and replacement of parts of injector & refixing to DG Set and testing complete all as specified and directed for following capacity :
Dismantling of U/S lube oil pressure gauge S/F of safety control sensor for low lube oil pressure to the present engine for ceasor from low lube oil in the pump of breakage of any oil pipe line /hose during the engine run so that massive damage can be avoided in the engine along with connection & exist panel for display the reason why the engine has stopped complete all as specified and directed.
Dismantling of existing water safety & S/F of safety control sensor for High water tempreture to the perevent engine for ceaser on water pipe line in the DG Set of breakage of any water pipe line during the engine run so that massive damage can be avoided in the engine along with connection & exist panel for display the reason why the engine has stopped complete all as specified and directed.
Dismantling of existing overspeed safety & S/F of safety control sensor for Over speed to the present engine for ceaser from over speed relaye in the Pump of breakage of any oil pipe line /hose during the engine run so that massive damage can be avoided in the engine along with connection & exist panel for display the reason why the engine has stopped complete all as specified and directed.
S/F lead acid, battery 12 volt 180 AH 25 plate including initial charging at various DG Sets complete all as specified and directed. Make:- Exide,Luminous.
Draining Out old used oil and supply & filling new lubricating oil SAE grade (15 w 40 ) multiviscoscity complete all as specified and directed.
Draining out old used coolant from the water pipe line and radiator of engine and supplying and pouring of new coolant suitable for ambient temp from 15 to 40 degree centigrade complete all as specified and directed. Make- TVS / castrol
Supply & pouring distilled water superior grade all as approved complete all as specified and directed.
Material and labour for rubber hose pipe of DG set of any capacity complete all as specified and as directed.
Supply & fixing of fan belt for radiator pump of Gen Set of any capacity complete all as specified and directed.
Supply & fixing super bypass filter for DG set of any complete all as specified and directed.
Taking out old u/s dimmer stat unit for 15 KVA voltage stabilizer after opening the cover of stabilizer with the help of hydra/manual and M&L for new dimmer state coil 10 Amp for proper functioning of voltage stabilizer suitable of 15 KVA stabilizer after disconnecting electrical connections complete all as specified and directed.
Supply and fixing fingers,gland,carbon brush for 15 KVA voltage stabilizer in replacement of u/s fingers complete all as specified and directed.
Supply and fixing Ammeter in replacement of old u/s ammeter for upto 160 KVA voltage stabilizer complete all as specified and directed.
Servicing of stabilizer upto 150 KVA decabonizing/cleaning complete consists of bus bar chamber, circuit cards and metering chambers, inspecting the joints,coils,cleaning of servo card and setting of servo card, circuit spouts for any flash overs/tracks, applying Becktol red solution to the bus bars and spouts having moderate tracking, tightening of joints, cleaning insulators and ensure proper decarbonisation and re-assembling complete all as specified and directed.
M&L in replacement of micro processor base control card for each phase complete all as specified and directed.
M&L for in replacement of servo motor 3 KG torque complete all as specified and directed.
M&L for in replacement of servo motor 10 KG torque complete all as specified and directed.
M&L for in replacement of electronic circuit card complete all as specified and directed.
Supply and fixing voltmeter in replacement of old u/s voltmeter upto 150 KVA voltage stabilizer complete all as specified and directed.
Supply and fixing push button in replacement of old u/s push button upto 150 KVA voltage stabilizer complete all as specified and directed.
Excavation in trenches not exceeding 1.5 mtr wide and exceeding 1.5 mtr in depth for foundation of pole and not exceeding 3 mtr depth and getting out complete all as specified and directed.
PCC M-15(nominal mix) using 20mm graded crushed stone aggregate in as in coping of pole including weathering slightly rounded or chamfered angles throathing as directed including necessary form work complete all as specified and directed.
Dismantling cross-arms of MS channel, lightening arresters, DO fuse etc complete and depositing to E/M yard complete all as specified and directed.
Dismantling insulators any type, any size complete all as specified and directed
Dismantling earth wire complete all as specified and directed.
Dismantling of ACSR or AAC conductors complete all as specified and directed.
k k enterprises
JAIN TRADERS
mayur enterprises
Ridhi engineers and builders
M/s KUNDU CONSTRUCTION
Parveen Builders
blue max associates
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .