Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.3 LAccepted-AOC 58 CHANDRALOK BLDG MAYO HOSPITAL ROAD NAGPUR 440018 | NAGPUR | NAGPUR | MAHARASHTRA | 440018 | L1 | Accepted-AOC Amount Awarded | |
| 2 | L2₹26.4 L+₹15,214 (0.58%)Rejected-Finance | L2 | Rejected-Finance Other than Lowest Bidder | |
| 3 | L3₹27.6 L+₹1.3 L (4.97%)Rejected-Finance 58 CHANDRALOK BUILDING MAYO HOSPITAL ROAD NAGPUR 440 018 | NAGPUR | MAHARASHTRA | 440018 | L3 | Rejected-Finance Other than Lowest Bidder | |
| 4 | L4₹31.2 L+₹4.9 L (18.8%)Rejected-Finance PULGAON | L4 | Rejected-Finance Other than Lowest Bidder | |
| 5 | L5₹33.6 L+₹7.4 L (28.0%)Rejected-Finance 26 740 35 KESARI HOUSE NEAR RICO INDUSTRIAL AREA DEVIPURA SIKAR RAJASTHAN 332 001 | SIKAR | SIKAR | RAJASTHAN | 332001 | L5 | Rejected-Finance Other than Lowest Bidder |
| Sl No | Description | Qty | Unit | M/S Maa Durga Constructions,Pulgaon L4 | Paragon Electrotechnics L1 | Chinmaya Enteprises L2 | M/S. ELECTROPOWER TECHNOLOGIES L3 | HUMERS INFRATECH L5 |
|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply, installation, testing and commissioning of transformer outdoor type step down transformer 11kV/0.433 kV AC 3 phase, 50 Hz, 500 kVA capacity, core type copper wound, on HV & LV coil immerse, naturally cooled, oil natural-air natural (ONAN) with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector group DYN-II with neutral brought out on secondary side (LV) and having 7 step tapping at +/2.5% of each step (+5% to 10%) on HV side to be charged by means of hand operated OFF load tap change gear, the maximum temperature rise should not exceeds 45 degree celsius in oil and 55 degrees celsius in HV/LV winding when measured by resistance method after continuous full load run on and ambient temp of 40 degree celsius the transformer shall be in accordance with IS-1180 (Part-I) (level-3) with amendment No. 4, losses at 50 % Load -1354W, Losses at 100% Load - 3909W, Transformer must be BIS approved & BEE Marked, Manufacturer must have a NABL approved Lab and comprises of the following:-
(a) Three porcelain bushing suitable for 11kV on HV side and including end termination box complete with copper rods, nuts, bolts and washers. (b) One cable end termination box on LT side (secondary side) consisting of four nos porcelain bushing with copper rods complete with nuts, bolts and washers. (c) Oil conservator with filter type drain valve and oil level guage. (d) De-hydration breather with filter fill of dehydrating agent (Silica gel). (e) Explosive vent, thermometer pocket on tank cover, oil drain filter valve, lifting lugs/ hooks, oil filter hole with cap/ plug with connection plate complete, air release valve plug and four nos plain cast steel detachable roller. (f) One No 100mm, dial type thermometer, vapour pressure type having range 0-120 degree celsius with metal guard having maximum perimeter temperature reading indicator with re-setting device. (g) Two earthing terminal on tank cover to facilitate fixing of 50 x 6mm galvanised iron earth strip for earthing of body. (h) Rating plate an terminal marking plate - 02 Nos. (j) Extra bushing for neutral in the LT cable box for providing independent set of earthing for neutral. (k) First filling of new and unused transformer oil IS 335 marked filtered and tested for dielectric strength not less than 50KV at 2.5mm air gap between testing electrodes. (l) Cable terminal Boot for transformer comprising of Basic Impulse level-95kV, Bushing diameter- 30-45mm, Voltage Um-17.5kV max, Description - Flexible Bushing Boots, Diameter D over Termination- 35mm-400mm, suitable for HT/LT XLPE UG Cable sizes- 95 to 240 sqmm.
Note 1:- Certification of dielectric strength shall be submitted to the contractor after filling the oil.
Note 2:- The Contractor is required to afford all facilities for factory visit, inspection of transformer, testing ON load and OFF load and examination of all material used & workmanship in items assembled or manufactured by them.
Note 3:- (i) All the tests including pre-commissioning at site are to be conducted in presence of MES representative/ SEI and all test certificate duly signed by all concerned to be submitted by the contractor to the department before completion of work.
(ii) The equipment should carry a guarantee of 30 months from the date of dispatch or 24 months from the date of completion of the contract, whichever is later. Any defect during this period will be attended in a period of three days including spares and labour without any extra cost to Govt. | 1 | Each | 25,00,000 ₹25,00,000 | 20,95,636 ₹20,95,636 | 19,75,000 ₹19,75,000 Lowest | 19,80,000 ₹19,80,000 | 27,00,000 ₹27,00,000 |
| 2.00 | Supply of Trolley having chasis fabricated out of 6 x 3 inches size channel (Main Section) mounted over suitable suspension system driven through 5 stud axle, folding disc and wheeled through 7.5 x 16 type tyres of make Appollo/ Ceat / MRF. Entire trolley is to be fabricated with suitable knuckle joint and separate double eye tie rod / sling so that it can be pulled to desired location with the help of tractor of any other suitable load carrier vehicle. (Min Load carrying capacity of trolley 4 Ton). Heavy duty trolley made up of stainless steel with two coat of painted four wheeled suitable for 500 KVA transformer alongwith outer guard and over head shed. Extra space for HT cable and LT cable. Complete all as specified and directed. | 1 | Each | 3,86,000 ₹3,86,000 | 3,00,000 ₹3,00,000 Lowest | 3,75,000 ₹3,75,000 | 4,00,000 ₹4,00,000 | 4,00,000 ₹4,00,000 |
| 3.00 | Supply, laying, jointing and testing cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric power cables (hevy duty) with aluminium conductor 11000 volts grade of size 3 core 95 Sqmm complete all as specified and directed. | 75 | RM | 1,431 ₹1,07,325 | 1,400 ₹1,05,000 | 1,600 ₹1,20,000 | 2,100 ₹1,57,500 | 1,350 ₹1,01,250 Lowest |
| 4.00 | Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed. | 2 | Each | 6,005 ₹12,010 | 5,000 ₹10,000 | 9,500 ₹19,000 | 11,500 ₹23,000 | 4,500 ₹9,000 Lowest |
| 5.00 | Supply, laying, and testing XLPE insulated,PVC bedded galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 240 sqmm 3.5 core, complete all as specified and directed. | 55 | RM | 2,103 ₹1,15,665 Lowest | 2,130 ₹1,17,150 | 2,800 ₹1,54,000 | 3,600 ₹1,98,000 | 2,800 ₹1,54,000 |
Tender Value
₹35.0 L
EMD Value
₹70,000
Closing Date
3 Jul 2026, 6:00 pmClosed
CWE Nagpur
Commander Works Engineer Bldg No. P-9, Sitabuldi Fort, Nagpur - 440 001 Pin-900419, C/o 56 APO
PROVISION OF 500 KVA TRANSFOREMER TROLLEY MOUNTED AND ALLIED WORK AT MIL STATION KAMPTEE
2026_MES_771864_1
84926/E8
Open Tender
Electrical and Maintenance Works
Item Rate
140 days
GE Kamptee
As per tender documents
9 documents required · 9 mandatory
₹500
GE Kamptee
₹70,000
Yes
10 Aug 2026
12 Jun 2026
6 Jul 2026
12 Jun 2026
3 Jul 2026
26 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing and commissioning of transformer outdoor type step down transformer 11kV/0.433 kV AC 3 phase, 50 Hz, 500 kVA capacity, core type copper wound, on HV & LV coil immerse, naturally cooled, oil natural-air natural (ONAN) with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector group DYN-II with neutral brought out on secondary side (LV) and having 7 step tapping at +/2.5% of each step (+5% to 10%) on HV side to be charged by means of hand operated OFF load tap change gear, the maximum temperature rise should not exceeds 45 degree celsius in oil and 55 degrees celsius in HV/LV winding when measured by resistance method after continuous full load run on and ambient temp of 40 degree celsius the transformer shall be in accordance with IS-1180 (Part-I) (level-3) with amendment No. 4, losses at 50 % Load -1354W, Losses at 100% Load - 3909W, Transformer must be BIS approved & BEE Marked, Manufacturer must have a NABL approved Lab and comprises of the following:-
(a) Three porcelain bushing suitable for 11kV on HV side and including end termination box complete with copper rods, nuts, bolts and washers. (b) One cable end termination box on LT side (secondary side) consisting of four nos porcelain bushing with copper rods complete with nuts, bolts and washers. (c) Oil conservator with filter type drain valve and oil level guage. (d) De-hydration breather with filter fill of dehydrating agent (Silica gel). (e) Explosive vent, thermometer pocket on tank cover, oil drain filter valve, lifting lugs/ hooks, oil filter hole with cap/ plug with connection plate complete, air release valve plug and four nos plain cast steel detachable roller. (f) One No 100mm, dial type thermometer, vapour pressure type having range 0-120 degree celsius with metal guard having maximum perimeter temperature reading indicator with re-setting device. (g) Two earthing terminal on tank cover to facilitate fixing of 50 x 6mm galvanised iron earth strip for earthing of body. (h) Rating plate an terminal marking plate - 02 Nos. (j) Extra bushing for neutral in the LT cable box for providing independent set of earthing for neutral. (k) First filling of new and unused transformer oil IS 335 marked filtered and tested for dielectric strength not less than 50KV at 2.5mm air gap between testing electrodes. (l) Cable terminal Boot for transformer comprising of Basic Impulse level-95kV, Bushing diameter- 30-45mm, Voltage Um-17.5kV max, Description - Flexible Bushing Boots, Diameter D over Termination- 35mm-400mm, suitable for HT/LT XLPE UG Cable sizes- 95 to 240 sqmm.
Note 1:- Certification of dielectric strength shall be submitted to the contractor after filling the oil.
Note 2:- The Contractor is required to afford all facilities for factory visit, inspection of transformer, testing ON load and OFF load and examination of all material used & workmanship in items assembled or manufactured by them.
Note 3:- (i) All the tests including pre-commissioning at site are to be conducted in presence of MES representative/ SEI and all test certificate duly signed by all concerned to be submitted by the contractor to the department before completion of work.
(ii) The equipment should carry a guarantee of 30 months from the date of dispatch or 24 months from the date of completion of the contract, whichever is later. Any defect during this period will be attended in a period of three days including spares and labour without any extra cost to Govt. | 1 | Each | - | - |
| 2 | Supply of Trolley having chasis fabricated out of 6 x 3 inches size channel (Main Section) mounted over suitable suspension system driven through 5 stud axle, folding disc and wheeled through 7.5 x 16 type tyres of make Appollo/ Ceat / MRF. Entire trolley is to be fabricated with suitable knuckle joint and separate double eye tie rod / sling so that it can be pulled to desired location with the help of tractor of any other suitable load carrier vehicle. (Min Load carrying capacity of trolley 4 Ton). Heavy duty trolley made up of stainless steel with two coat of painted four wheeled suitable for 500 KVA transformer alongwith outer guard and over head shed. Extra space for HT cable and LT cable. Complete all as specified and directed. | 1 | Each | - | - |
| 3 | Supply, laying, jointing and testing cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric power cables (hevy duty) with aluminium conductor 11000 volts grade of size 3 core 95 Sqmm complete all as specified and directed. | 75 | RM | - | - |
| 4 | Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed. | 2 | Each | - | - |
| 5 | Supply, laying, and testing XLPE insulated,PVC bedded galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 240 sqmm 3.5 core, complete all as specified and directed. | 55 | RM | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.39 MB
Tender.pdf
Tender Documents • 0.83 MB
BOQ_864322.xls
BOQ • 6.83 MB
corrigendum2.pdf
PDF • 0.57 MB
corrigendum1.pdf
PDF • 1.89 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .