Executive Engineer (Electrical)/South Zone
SOUTH DELHI MUNICIPAL CORPORATION Office of the Executive Engineer (Electrical)-IV MC Primary School, Police Colony Hauz Khas, New Delhi-110016
Improvement and Development of electrical installation of Community Center Block 18 Dakshinpuri, in Ward No-79S under South zone.
2021_SDMC_98020_1
NIT NO.21 ITEM No.1 (2021-2022)
Open Tender
Electrical Works
Item Rate
30 days
DAKSHINPURI EXTN
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
₹4,146
Yes
23 Dec 2021
13 Dec 2021
21 Dec 2021
13 Dec 2021
20 Dec 2021
13 Dec 2021
Amount
Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.Group C
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
2 X 4 sq. mm + 1 X 4 sq. mm earth wire
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 A
Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required 5/6 Amps Switchs
15/16 A switch
3 pin 5/6 A socket outlet
6 pin 15/16 A socket outlet
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Upto 35 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Upto 35 sq. mm (clamped with 1mm thick saddle)
Supply of XLPE insulated,PVC sheathed Al.conductor Armoured Cable 1.1 KV grade Conforming to IS 7098 of following Sizes (c) 2x4 Sqmm
S/I/T/C of LED Tube type Luminaire 20 Watt rating complete with polycarbonate housing batten integrated electronic driver prewired with high efficient LEDs with the followingExtruded Aluminium Batten prewired with high efficient LED with the following:(a) Total System wattage 20 watt +/- 5% (b) Luminous Efficacy Lumens/watt >=95 (c) power factor >= 0.95
Supply of 18'' ( 450 mm )sweep 1400 rpm exhaust fan heavy duty complete with shutter,blade etc as required
Supply of 12'' ( 300 mm )sweep 1400 rpm exhaust fan heavy duty complete with shutter,blade etc as required
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.Upto 450 mm sweep
Providing and fixing extra conduit down rod of 20 mm dia, 2 X 10 cm length, wiring with 2 X 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored
Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc.complete as required.
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.100A,30 KA FPMCCB
P/F Hot press sheet moulded compound (SMC) fire retradant (Temp.resistance up to 200 C),IP 55weather proof pole box of inner dimension 300x200x105 mm (NS)and outer dimension of 333x233x150 mm high dome complete with suitable arrangement for fixing of 4 nos of 6 to 32amp single pole MCB &63 Amp .Double pole isolator (MCB/Isolator excluded)with netural link duly shorting on DIN Channel with 2 nos of MS clamps with SS back plate of suitable sizewith danger monogram property printed on the cover etc as reqd.
stage.html
html • 0.02 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .