Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.2 LAccepted-AOC | L1 | Accepted-AOC Being overall reasonable | |
| 2 | L2₹29.7 L+₹1.1 L (3.94%)Rejected-Finance SHOP NO 259 LOHOGAON ROAD KALWAD KHANDVE NAGAR PUNE 411032 | PUNE | MAHARASHTRA | 411032 | L2 | Rejected-Finance Not lowest bidder | |
| 3 | L3₹30.5 L+₹2.0 L (6.84%)Rejected-Finance PLOT NO 8 PREMA APARTMENT VEDANTNAGAR CHHATRAPATI SAMBHAJINAGAR 431 007 M S | CHHATRAPATI SAMBHAJINAGAR | CHHATRAPATI SAMBHAJINAGAR | MAHARASHTRA | 431007 | L3 | Rejected-Finance Not lowest bidder | |
| 4 | L4₹41.8 L+₹13.2 L (46.3%)Rejected-Finance OFFICE NO 101 MALAN PLAZA NEXT TO ESSAR PETROL PUMP NEAR GODAMBLE CORNER RAHATNI PIMPRI DP ROAD RAHATANI PUNE 411 017 | PUNE | PUNE | MAHARASHTRA | 411017 | L4 | Rejected-Finance Not lowest bidder |
Tender Value
₹36.1 L
EMD Value
₹72,140
Closing Date
11 Feb 2020, 6:00 pmClosed
GE CENTRAL KIRKEE
GE CENTRAL KIRKEE RANGE HILLS ROAD KIRKEE PUNE 411003
REPAIR SERVICING OF DG SETS AND CONNECTED WORKS UNDER AGE EM II IN GE CENTRAL KIRKEE
2020_MES_313377_2
8322/E8 OF 2019-2020
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
KIRKEE
AS PER NIT
7 documents required · 7 mandatory
₹500
Yes
GE CENTRAL KIRKEE
₹72,140
Yes
12 Mar 2020
4 Feb 2020
12 Feb 2020
4 Feb 2020
11 Feb 2020
4 Feb 2020
Amount
Annual maintenance for diesel engine driven generating sets of capacity up to 62.5 KVA Make Kirloskar and Crompton Greaves including attending to under mentioned jobs to ensure its satisfactorily performance. as and when required or at least ones in qtr.
Checking the condition and cleaning of Air System - oil Bath / air element :-(a) Checking the Air cleaner condition (b) Checking the Functioning of vacuum indicator (c) Checking the Hoses condition (d) Checking the condition and Clean oil cooler & cyl liner fins HA Engine.
Lub oil system :- (a) Checking the Lub oil level / oil condition (b) Checking the condition of Engine oil and replacement if required (c) Checking the Oil leakage if any (d) Checking & Cleaning centrifugal lub oil fitter
Cooling system :- (a) Checking the coolant in the system (b) Checking the Coolant level and conditions (c) Checking the Coolant leakages and rectification (d) Checking the Belt condition and tension adjusted (e) Checking the Radiator condition and cleanliness (f) Checking the Condition of all hoses and clamps
Fuel system :- (a) Checking the Fuel tank cleanliness (b) Checking the Condition of fuel hoses and leakages (c) Checking the Drain water from water sep for K series (d) Checking the condition of baby filter and glass filter and cleaning of filter
Canopy :- (a) Checking the Condition of canopy locks and hinges (b) Checking the Working of exhaust fan (HA Engine only)
AC Alternator :- (a) Checking the conditions of Alternator and mountings (b) Checking the conditions of Couplings plate and bolt (c) Checking the AVR / main alt connections (d) Checking the Proper earthing condition (e) Checking the Cond of power cable connection & terminals (f) Checking the Conditions of brushes for brush type alt only
General :- (a) Checking of vibration pads and there condition (b) Overall condition of the engine and alternator
Electrical wiring :- (a) Checking the Electrolyte level and terminal condition of Battery (b) Checking the Condition of Battery (c) Checking the Battery voltage in DC (d) Checking the Functioning of charging alternator (e) Checking the Function of external charge (14.1 volt DC) (f) Checking the Functioning of all gauges/meter (g) Checking the Functioning of ESU (HWT, LLOP,LFL) (h) Checking the Earthing connection of Panel (j) Checking the Panel is mounted on AV mounts (k) Checking the AMF module type (l) Checking the Supply to stop solenoid (m) Checking the Auto manual mode operation (n) Checking the all wiring are connected tight (o) Checking the Overall condition of the Panel
General Checks :- (a) Checking the fan belt and adjusting tension (b) Checking the fuel and oil filter asserting its condition (c) Checking the air filter and its oil level cleaning the oil filter. (d) Checking of FIP performance and oil level. (e) Tightening the base bolt and nuts and mounting bolts and nuts. (f) Checking the coupling bolts and adjustment checking the self starter and dynamo. (g) Checking the battery distilled water levels and topping up to the required level. (h) Checking the loose connections if any in the panel board and tightening the same (j) Checking the anti vibration mounting adjusting the bolts. (k) Checking the radiator and radiator hose and arresting leak if any.
Note 1 :- The scope includes all scheduled & periodical maintenance of DG set as per OEM recommendations like KOEL care/Cummins or equivalent. The quoted rates are inclusive of arranging specialised services for breakdown complaints including repairs and overhauls.Replacement of fuel and oil filter and other consumables will be measured and paid separately under relevant items of schedules.The servicing shall be done by authorised service team of KOEL/Cummins or a person having certificate from the OEM. The certificate in respect of preventive maintenance checks done as per prescribed format of OEM duly signed shall be submitted to department as and when required or at least ones in qtr. Note 1: The contractor shall mention mobile number for lodging complaints if any through SMS. The response time for minor complaints shall be max 2 working day and major complaint shall be 4 days. Arrangement of listed spares as per CA is contractor's responsibility and the spares not listed in the tender shall be intimated to department for procurement action. Failing the above the contactor is liable for a penalty of Rs 500/- per complaint on subsequent days after laps of 2 days for minor complaints and 4 days for major complaints.
All as per Item No 1 above but 110 KVA Rating with Cummins make 6 cylinder, Model NT 495 Engine
All as per Item No 1 above but 160 KVA Rating with Cummins make 6 cylinder, Model NT 743 Engine
All as per Item No 1 above but 500 KVA Rating with Kirloskar make Engine
All as per Item No 1 above but 1000 KVA Rating with Cummins make 16 cylinder, model-KTA 3067- G Engine
All as per Item No 1 above but Diesel driven engines only for fire fighting pump up to 160 HP pump with Cummins make 6 cylinder, Model NT 743 Engine
Supply only following consumable spares suitable up to 62.5 KVA DG Set or diesel engine driven sets
Lub oil filter element
1.1 liter fuel filter kit (container/ outer body)
Fuel filter primary and secondary
Cooalant Rubber hoses
Fuel / Oil pipe/hoses with adapter and copper washer as per existing size and length up to 0 .75 mtr long any pipe for that particular DG set
Fuel / Oil pipe/hoses with adapter and copper washer as per existing size and length up to 1 to 1.5 mtr long any pipe for that particular DG set
Air circulating system hoses
Oil circulating system hoses
Air cleaner dry type
Air hose for turbo charger
Hose for turbo charger oil drainage with adapter
Supply only following consumable spares suitable for 110 to 160 KVA DG
Air Cleaner Outer
Air Cleaner Inner
Coolant Rubber hoses
Lub oil filter
Lub oil by pass Filter
Fuel filter primary and secondary
Fuel / Oil pipe/hoses with adapter and copper washer as per existing size and length up to 0 .75 mtr long any pipe for that particular DG set
Fuel / Oil pipe/hoses with adapter and copper washer as per existing size and length up to 1 to 1.5 mtr long any pipe for that particular DG set
Filter element for water separator filter
Water separator filter unit complete with outer body and mounting bracket complete
Air hose for turbo charger
Hose for turbo charger oil drainage with adapter
Supply only following consumable spares suitable for 500 KVA DG Set
Air Cleaner Outer
Air Cleaner Inner
Coolant Rubber hoses
Lub oil filter
Fuel filter primary and secondary
Fuel / Oil pipe/hoses with adapter and copper washer as per existing size and length up to 0 .75 mtr long any pipe for that particular DG set
Fuel / Oil pipe/hoses with adapter and copper washer as per existing size and length up to 1 to 1.5 mtr long any pipe for that particular DG set
Air hose for turbo charger
Hose for turbo charger oil drainage with adapter
Water separator filter
Supply only following consumable spares suitable for 1000 KVA DG Set
Air Cleaner Outer
Air Cleaner Inner
Coolant Rubber hoses
Lub oil filter
Lub oil by pass Filter
Fuel filter primary and secondary
Fuel / Oil pipe/hoses with adaptor and copper washer as per existing size and length up to 0 .75 mtr long any pipe for that particular DG set
Fuel / Oil pipe/hoses with adaptor and copper washer as per existing size and length up to 1 to 1.5 mtr long any pipe for that particular DG set
Air hose for turbo charger
Hose for turbo charger oil drainage with adaptor
Water separator filter
Water separator filter complete with outer body and mounting bracket complete
Oil pipe/hoses with adaptor and copper washer between external oil pump and engine as per existing size and length up to 1 to 1.5 mtr long any pipe for that particular DG set NOTE for item No 7 to 10 :- 1 The rate quoted for the hoses of coolent, oil, air etc are deemed to be included for replacement of tightening clip/clamps as per existing size if required to be changed 2 :- The makes & model of the all spares required to be replaced should be as per OEMs make and got approved before purchasing . 3. The contractors are advised to visit the site before quoting the rates as the generators are old vintage and spares required are of a specific types.
Supply only Coolant/ Inhibitor
Supply only Engine oil 15 W 40 grade Make Indian oil / HP / Tata BP /Valvoline.
M&L for flexible silencer pipe suitable for 110 KVA DG set as per existing dia and length to be fixed with new nut bolt and asbestos packing
M&L for flexible silencer pipe suitable for 1000 KVA DG set as per existing dia and length to be fixed with new nut bolt and asbestos paking
M&L for silencer muffler suitable for 110 KVA DG set as per existing dia and length to be fixed with new nut bolt and asbestos packing
Supply and fixing in replacement of Silencer for 1000 KVA DG Set as per existing model including painting work, welding work, any fabricating work at site for fixing silencer etc required to complete the job and functional and testing DG Set on load complete all as directed by Engineer - in - charge. Note :- (a) Contractor should visit the site before quoting tender and provide skilled labour while executing the job. (b) Proper Scaffolding arrangement is to be made while Dismantling, fixing and painting of exhaust pipe and silencer is included in the quoted rate. (c) Misc items such as replacement of worn out nut, bolts etc required for satisfactory completion of job are deemed to be included in the above cost.
Supply & refilling of Electrolyte Chemical for Ni Cd batteries- 50 ltrs , along with Distilled water 150 ltrs including testing of batteries 12 volts 90 to 180 AH 40 Nos complete all as specified and directed.
S&F fabricated MS bracket /MS Plates/supports for MS and CI Pipe line, made out of angle iron and flat iron including bolts, nuts, washers and painting with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and as directed.
M&L for repairs/ servicing to external electric operated oil circulating/priming pump 2 HP for 1000 KVA DG set by replacement of ball bearing 6206 make SKF 2 Nos , replacement of oil pump impeller , oil seals , oil hose connector and connection etc complete all as specified and as directed.
M&L for repair to self starter of 110 KVA DG 24 volt DC supply by replacement of ball bearing, solonide switch rewinding of Armature etc complete all as specified and as directed.
M&L for repair to self starter of 1000 KVA DG 24 volt DC supply by repacement of ball bearing , solonoid switch rewinding of Armature etc complete all as specified and as directed.
M&L for repair to battery charging alternator of 110/62.5 KVA DG 24 volt DC supply by replacement of ball bearing , carbon brush rewinding of Armature,fan pulley etc complete all as specified and as directed.
M&L for repairs to water pump assembly of 110 KVA DG set by replacing water pump repair kit , bearings , water seal etc complete all as specified and as directed.
M&L for repairs to turbo charger of 110 KVA DG set by replacing turbo charger repair kit , bearings , oil seal , high speed turbo blade etc complete all as specified and as directed.
M&L for repairs to turbo charger of 1000 KVA DG set by replacing turbo charger repair kit , bearings , oil seal , high speed turbo blade etc complete all as specified and as directed.
M&L for replacement of turbo charger complete as per existing make and model suitable for 110 KVA DG set Cummins engine
M&L for replacement of turbo charger complete as per existing make and model suitable for 1000 KVA DG set Cummins engine
V Belt Make fenner/ shakti/dunlop suitable for 500KVA DG Set
V Belt Make fenner/ shakti/dunlop suitable for 110KVA DG Set
Fuel pump overhauling kit suitable for 110KVA DG Set
Removing Fuel pump up to 110 KVA from the engine transporting to work shop , Servicing , calibrating, Testing and refixing on the engine all as directed by Engr-in-charge.Note:- Spares will measured and paid separately
M&L for servicing / cleaning / repairs to radiator of 50/62.5 KVA DG SET by draining out of water removing radiator hoses removing radiator from engine taking it to repair workshop ,removing of sludge , flushing with anti scaling agent with high pressure pump, straitening of fins using fins straitening comb ,refixing to its original position connecting of hoses refilling of water/ coolant and testing complete all as specified and as directed.
M&L for servicing / cleaning / repairs of radiator of 160 KVA DG SET by drainig out of water removing radiator hoses removing radiator from engine taking it to repair workshop ,removing of sludge , flusing with antyscaling agent with high pressure pump , straitning of fins using fins straitning comb ,refixing to its original position conecting of hoses refilling of water/ coolent and testing complete all as specified and as directed.
M&L for servicing / cleaning / repairs to radiator of 110 KVA DG SET by draining out of water removing radiator hoses removing radiator from engine taking it to repair workshop, removing of top and bottom tanks removing of sludge flushing with anti scaling agent rectification of leakage refixing of top and bottom tanks by welding / soldring straitening of fins using fins straitening comb ,refixing to its original position conecting of hoses refilling of water/ coolant and testing complete all as specified and as directed.
M&L for servicing / cleaning / repairs to radiator of 1000 KVA DG SET by draining out of water removing radiator hoses removing radiator from engine taking it to repair workshop, removing of top and bottom tanks removing of sludge flushing with anti scaling agent rectification of leakage refixing of top and bottom tanks by welding / soldring straitening of fins using fins straitening comb ,refixing to its original position conecting of hoses refilling of water/ coolant and testing complete all as specified and as directed.
M&L for repairing and testing of pump centrifugal/mono block upto 5 HP of any make and type including welding work, turning, re-metaling of shaft bush bearing,locking key,air release / pump watering key and other such accessories etc required to make pump functional and testing on load complete all as specified and as directed .NOTE Replacement of bearings or rewinding of motor if required shall be measured and paid for separately.
M&L for repairs to water circulating condenser unit of for 1000 KVA DG set by disconnecting of both hot and cold water inlet ,outlet pipe lines, opening of both end flanges/covers ,cleaning/ decaling of copper tubes using anti scaling chemical and hand operated cleaning brush of appropriate length and dia as required for the tubes , checking for any leakage after decaling ,removing of leakage copper tube ,welding / brazing of leakage ,refixing of copper tube into condenser ,sealing / brazing of tube with main body , refixing of condenser end covers/flanges including replacement of rubber gaskets ,connection of inlet and outlet pipe lines including replacement of rubber gaskets/packing and testing on completion complete all as specified and as directed.
Material and Labour for Servicing/Cleaning of FRP cooling towers of 1000 KVA DG Sets by dismantling top cover, fan with fan motor and removing the honey comb frills. Cleaning of base tray , pot strainer etc. servicing of fan motor with greasing refixing the fan & top cover descaling of water circulating system by using scale removing non corrosive chemical supply and fixing new honeycomb frills testing commissioning complete all as directed by Engr-in-charge Note: 1:- The rate quoted are deemed to be included for replacement of any damaged / rusted nut bolt washers ,pins ,locking pins , grease, descaling chemical etc 2 :- Major spares as required during the servicing and repairs will be measured and paid separately 3:- The repairs should be done for the motors installed at height of more than 3 mtrs necessary safety measures are deemed to be included in the quoted rates.
Supply only honeycomb frills as per existing size , shape and qty required for 40 ton cap cooling tower for 1000 KVA DG set complete all as specified and directed
M&L for repair/ cleaning to individual MS diesel storage tank of capacity 500 ltr for DG sets by decaning of diesel ,removing of sludge repairing of leakage by welding, replacement of inlet and outlet pipe connection using GI sockets welding to tank for fixing of GI pipes and level indicating pipe etc complete all as specified and as directed.
M&L for repair/ cleaning to MS tank of Bulk diesel storage of capacity 10000 ltr at 12 mtr height for DG sets by decaning of diesel ,removing of sludge repairing of leakage by welding, after flushing out with water to avoid caching of fire while welding , replacement of inlet and outlet pipe cnnection using GI sockets welding to tank for fixing of GI pipes , painting of tank from out side with synthetic enamel paint superior quaolity make and colour as approved by Engr in charge complete all as specified and as directed.
Repairs to mechanical level indicating system of bulk diesel tank by replacing inner float ,flexible 2 mm dia GI wire rope upto tank height, rope guiding pulley, level indicator and painting of level markings on outer side of tank etc complete all as specified and as directed.
Checking of alternator exciting system with Authorised mechanic of KOEL/Cummins or a person having certificate from the OEM and checking the complete system including controls and repair /modification / replacement of suitable AVR for existing system complete suitable for 110 KVA alternator old model 1986 vintage all as specified and as directed.
Checking of alternator exciting system with Authorised mechanic of KOEL/Cummins or a person having certificate from the OEM and checking the complete system including controls and repair /modification / replacement of suitable AVR for existing system complete suitable for 1000 KVA alternator old model 1986 vintage all as specified and as directed.
Servicing of alternator of 110 KVA cap by opening/dismantling and disconnecting all the connection from panel to terminal box repairs / replacing the field coils cotton binding tape /insulating material, refixing the field coils after varnishing drying to alternator and making the electric connection to terminal box with proper brass nut bolts and washers, testing and commissioning complete testing after repairs all as directed by Engineer-in-Charge
M& L for Ball bearing ZZ type NO 6302 make SKF/NBC complete all as specified and as directed.
M&L for rewinding of motors with super enamelled copper winding wire as per existing gauge and No of turns including insulating material cotton binding tape varnishing taking out connection wires etc upto 7.5 HP 3 phase motors or excitation winding of alternator etc complete all as specified and as directed.
M&L for Water Pump Pulley (115PCD)
M&L for Water Pump Assy for 110 KVA set
M&L for Starter (DELCO REMI 50 MT)
Dismantling of exists U/S asbestos rope and Supply and fixing asbestos rope 20 mm dia wrapped over the exhaust pipe complete and piping applicable of smooth finishing complete all as specified and as directed.
S&F water pressure gauge 0-30 PSI (approved make) with suitable valve & brass connector all as specified and directed.
S&F Oil pressure gauge 0-10Kg/cm sq 100 mm dia (approved make) with suitable connector all as specified and directed.
S&F temperature gauge 0-150 degree centigrade as per existing model for DG set engine (approved make) with suitable connector all as specified and directed.
S&F Oil pressure sensor for safety of engine as per existing model suitable for 1000 KVA Cummins make DG set engine (approved make) all as specified and directed.
S&F water temperature sensor for safety of engine as per existing model suitable for 1000 KVA Cummins make DG set engine (approved make) all as specified and directed.
M & L for spray painting of DG Sets/DG Driven pump sets with two coats of anti corrosive paint over a coat of red oxide primer after removing the existing deteriorated paint by scrapping the complete body along with foundation of DG Set/Diesel driven pump sets and filling the cavities with filter and marking of SM/MES No. with black paint up to 160 KVA DG set complete all as directed.
M & L for spray painting of DG Sets/DG Driven pump sets with two coats of anti corrosive paint over a coat of red oxide primer after removing the existing deteriorated paint by scrapping the complete body along with foundation of DG Set/Diesel driven pump sets and filling the cavities with filter and marking of SM/MES No. with black paint for 1000 KVA DG set complete all as directed.
Repairs/overhauling of micro processed based ATS of any make & capacity 600 Amps and replacement of minor items like springs, washers, bolt & nuts and other insulating materials etc and also including calibration and testing of control and protection devices of equipments in the following steps all as directed by Engineer-in-Charge:- (i) Disconnecting and taking out the ATS after taking shut down of the respective panel and check the defects. (ii) Overhauling the ATS by opening all parts and lubricating the moving parts as per the requirement. (iii) Re-assembling the ATS complete, installing to its original position, testing and commissioning theATS for both manual and automatic shifting mechanism for proper functioning of the ATS including replacement of NO/NC auxiliary contacts and no voltage / low voltage coil complete all as specified and as directed. Note:- (i) Cost of lubricants or cleaning agent shall be deemed to be included in the unit rate quoted. (ii) Replacing of defective parts will be measured and paid separately.
Repairs to main DG set panel consisting of replacement of copper bus bar trunking of ratting 2500 amp 3 phase with 100% neutral including replacement of busbar supporting insulators nut bolt MS ducting made out from 1.6 mm thick MS sheet duly supported by angle iron frame with minimum 40x40x4mm size angle complete including cutting ,bending ,welding etc duly painted with one coat of red oxide and two coat of oil paint as per existing colour to match with the main panel complete all as directed by Engr in charge NOTE ;- Contractors are advised to check the site before quoting the rates as the busbar with ducting to be changed in existing main big size combined panel of four Nos DG set
Removing of engine make Cummins Model No NTA 855G2F from site coupled with fire fighting pump after decoupling from pump and shifting to workshop for overhauling and resifting to its original place and recoupling with pump and testing complete all as specified and directed .
Dismantling / opening of engine for Overhauling Overhaul the same and reassembling complete including replacement of all defective parts, calibration and testing after repair complete. including replacement of all small parts like nut bolts packing gaskets locking pins sealing washers etc which are not mentioned in the list of major items supply only / repair jobs /machinening works etc to make engine functional without any extra cost NOTE :The major parts / repair jobs /machinening works shall be measured and paid for separately
Supply only the following items/carry out jobs for the engine make Cummins Model No NTA 855G2F
Upper & lower gasket set Complete
liner / cylinder
Piston assembly including gusan pin locking pins etc.
Main bearings
CR bearing
Thrust washer with bush kit
OIL seal
Injector barrel and plunger
Injector barrel and plunger service kit
Inlet valve with springs
Exhaust valve with springs
Valve seat and insert
Bolt set
Cam follower roller set
Oil seal kit
Coolant hose pipe set
OIL hose pipe set
Turbo charger repair kit
Turbo charger hose set
Diesel pressure pipes from PT pump to injectors
Machining work 0f cylinder head
Machining work of Crank shaft
Cam rod repairing
PT pump repairing complete including replacement of spare parts and pressure testing etc
Self starter repairing including replacement of spare parts solenoid switch also
Alternator repairing including replacement of spare parts
Water pump repairing including replacement of spare parts
V belt set make fenner / Helicord / Shakti
Heat exchanger cleaning
Gasket Kit for Heat exchanger
Injector sleeve
Connecting Rod
M&L for dismantling of existing panel with MS stand/rack including disconnecting of incoming and out going cables gland lugs/thimbles, etc carefully so that the same can be reconnected to new panel. and Supply, fix & testing LT panel-TTA (Totally type tested) factory made, single front,fix type, Floor mounted panel with aluminium bus bar of suitable size, panel fabricated with 2.0 mm CRCA sheet for load bearing members &1.6 mm thick sheet for non load bearing members. Panels shall be Suitable for following incoming & outgoing , including accessories and making connections of incoming and outgoing cables, to be fixed on concrete base or on cable duct with necessary angle iron base frame duly painted and fixing material like fastener nut, bolt etc cable entry as per site requirement complete all as specified and directed.(Make:- L&T/ABB/Legrand)
INCOMER : MCCB 4P, 36 kA, 160 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links and insulating shields Make - Legrand, Cat No. - 420097 /L&T /ABB
OUTGOINGS a) MCCB TP, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In,with spreader links and insulating shields Make - Legrand, Cat No. - 420043 /L&T /ABB
b) MCB TPN 32 AMPs "C" curve 10 KA Make Legrand Cat No 408699 /L&T /ABB
All as per Item No.64 above but suitable for and including following accessories :
INCOMER : MCCB 4P, 36 kA, 160 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links and insulating shields Make - Legrand, Cat No. -420097 /L&T /ABB
OUTGOINGS a) MCCB TP, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In,with spreader links and insulating shields Make - Legrand, Cat No. - 420043 /L&T /ABB
All as per Item No.64 above but suitable for and including following accessories :
INCOMER : MCCB 4P, 36 kA, 160 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links and insulating shields Make - Legrand, Cat No. -420097 /L&T /ABB
OUTGOINGS a) MCCB TP, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In,with spreader links and insulating shields Make - Legrand, Cat No. - 420043/L&T /ABB
Supplying & fixing in replacement power contactor 3 pole, type ML-1.5, with standard coil voltage 415 volts, Rating 25 Amp as per Cat No.SS91851 of M/s L & T or eqivalent in M/s Siemens/ Schneider/ABB including testing connecting commissioning complete all as specified and directed.
Supplying & fixing in replacement MCB 6 to 32 Amps, triple pole, 10 KA breaking capacity complete all as specified and directed. Make - Legrand cat No 408650-58 or equivalent in ABB/L&T/ Siemens
Supplying & fixing in replacement MCB 6 to 32 Amps, single pole, 10 kA breaking capacity complete all as specified and directed. Make - Legrand cat No 4085 87-95 or equivalent in ABB/L&T/ Siemens.
Supplying & fixing in replacement thermal over load relay direct mounting type suitable for ML type contactor of range 4-6.5 to 10-16 Amps Make L&T or equivalent in M/s Siemens/ Schneider/ABB including testing connecting commissioning complete all as specified and directed.
Supply and laying in trenches / laid in floor/duct /drawn through conduit XLPE insulated PVC bedded un armoured heavy duty electric cable 1100 Volt grade with aluminium conductor of cross sectional area 6 Sqmm 4 core complete all as specified and directed.
Supplying & fixing in replacement control cable 2.5 sqmm 12 core PVC insulated FR PVC round sheathed copper conductor flexible industrial cable 1100 volt conforming to IS 694 complete all as specified and directed. Make Havells /Polycab /finolex
Supplying & fixing in replacement rotary type on off switch for water pump / cooling tower motor as per existing shape and size to be fixed on panel complete all as specified and directed.
Supplying & fixing in replacement generator starting switch with key as per existing shape and size to be fixed on panel complete all as specified and directed.
Supplying & fixing in replacement off load change over switch 4 pole 100 amp with enclosure including removing of old one and disconnecting and reconnecting of cable connections complete all as specified and directed . make Havells /Standered /L&T
Supplying & fixing in replacement electric operated single phase 230 volt self priming type pump 0.5 HP for filling of fuel for DG set ISI mark to be fitted on angle iron frame including electric connection complete all as specified and directed
M & L for GM battery terminal suitable for 180 AH batteries duly soldered with battery lead as per existing model complete all as specified and as directed.
M & L for copper thimble heavy duty to be connected to battery lead by crimping and soldering 70 sqmm complete all as specified and as directed.
M & L for copper thimble heavy duty to be connected to battery lead by crimping and soldering 120 sqmm complete all as specified and as directed.
M & L for PVC insulated cable with copper conductor 1100V of size 70 sqmm multi stranded single core complete all as directed.
M & L for PVC insulated cable with copper conductor 1100V of size 120 sqmm multi stranded single core complete all as specified and as directed.
S&F Indicating lamp 240 volts LED type complete all as specified and as directed by Engr-in-Charge.
M&L for GI pipe medium grade 20 mm dia with all fittings to be fitted on wall / on iron structure in short length for fuel filling of DG sets
M&L for stop/ball valve 20 mm bore gun metal ISI mark any reputed make
S & F in repairs of rusted /warn out MS heavy duty silencer pipe bends as per existing angle and length 250 mm dia flanged ends with nut bolt gasket etc suitable for 1000 KVA DG Set all as directed by Engr in charge
M&L for earthing complete with GI earth plate electrode of size 60cm x 60cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5m below the normal ground level connected with GI strip 32 x 6mm by means of bolts, nuts, check nuts & washers of galvanised iron steel including necessary excavation and earth work in any type of soil, removing surplus soil to a distance not exc 50m, with and including PCC chamber in PCC (1:2:4), type B1,using (20mm graded stone aggregate),"mild steel angle iron frame" made out of MS angle iron of size 40x40x6mm thick duly painted with two coats of synthetic enamel paint over one coat of red oxide zinc chrome primer hinged with and including 6mm thick 12" x 10" size MS cover with handle, watering arrangement with funnel internally secured with wire mesh with 20mm dia medium grade pipe for watering 40mm dia light grade, GI pipe for lead protection in and including alternate layers of charcoal dust and common salt complete all as shown in electrical "plate No '3' and connected to earthing test point all as specified and indicated including testing on completion complete all as specified and directed. Note:- The excavation/earth work is in rocky area contractors are advised to see the site before quoting the rates. 2. If the earthing result is not achieved than the contractors should re-do the earthing with out any extra payment/at his own cost.
S&F in repairs earth continuity conductor or main earthing lead fixed to wall on batten or fixed to pole GI strip or buried in ground 32 x 6 mm all as specified and directed.
S&F in repairs of cooling tower water circulating pipe line GI pipe medium grade 80 mm dia with fittings to be fixed on floor ,wall ,on roof etc complete with MS clamp / angle support all as directed by Engr in charge
S&F in repairs Gun Metal Non return valve with iron wheel 80 mm dia screwed both ends
S&F in repairs Butterfly valve flanged type 80 mm dia CI body with handle
S&F in repairs of rusted /warn out MS heavy duty silencer pipe 250 mm dia duly cutting, bending, welding etc flanged end with nut bolt asbestos gasket etc in short length as per site requirement all as directed by Engr in charge
Rama Electricals
ASHWAMEDH ENGINEERS
M/S. Niksun Electro-Infra Private Limited
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .