Making the Building Management System Functional, Commissioning and Testing Works at IIM Ranchi
2026_IIMRC_925390_1
IIM Ranchi/NIT/BMS/2026-27/39
Open Tender
Access Control System
Works
90 days
IIM Ranchi Campus
As per tender
3 documents required · 3 mandatory
₹0
₹1 L
Yes
IIM Ranchi Campus
8 Sept 2026
8 Sept 2026
30 Sept 2026
8 Sept 2026
29 Sept 2026
8 Sept 2026
8 Sept 2026 - 29 Sept 2026
15 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Comprehensive Troubleshooting, Rectification, Reconfiguration & Recommissioning of the Existing Building Management System (BMS) | |||||
| 1.01 | – Diagnostic audit of the existing BMS architecture — DDC controllers, field sensors, actuators and BACnet IP network — to identify hardware faults, communication failures and configuration errors.
– Rectification of identified faults at controller, sensor and network level, including restoration of BACnet IP communication between DDC panels and the central workstation, and correction of point-mapping errors.
– Recommissioning of all HVAC, electrical and utility systems integrated with the BMS to ensure stable, real-time data acquisition and control response.
– Development of dynamic, device-specific graphic mimic screens for all monitored/controlled equipment (AHUs, chillers, pumps, cooling towers, DDC panels) depicting live status, setpoints and alarms.
– Design and deployment of a centralised, role-based dashboard configured to client-specified KPIs for consolidated visibility of building performance and system health.
– Configuration of automated trend logs and historical/real-time reports (energy consumption, run-hour, alarm/event logs, equipment performance) and a searchable point/device library for ease of operation and maintenance.
– Preparation of as-built documentation, Operation & Maintenance manual, and hands-on training for facility operating staff. | 1 | Job | - | - |
| 1.02 | Checking, Testing & Configuration of DDC Panels and Connected Field Devices
– Physical inspection of panel wiring, terminations, power supply (230V AC / SMPS), MCBs and I/O modules for damage, loose connections or corrosion.
– Verification and correction of I/O point mapping between each DDC and its connected field devices (temperature, pressure, flow and level sensors, valve/damper actuators, VFDs, etc.).
– Reconfiguration and calibration of control logic, setpoints, PID loops, interlocks and alarm thresholds as per the sequence of operation and site requirement.
– Verification of BACnet IP communication between each DDC and the central BMS server, including network addressing, object mapping and polling stability.
– Functional performance testing of each panel under live operating conditions, with a signed-off checklist per panel.
– Scope covers 21 Nos. DDC panels installed across the plant rooms, AHU rooms and utility areas of the IIM Ranchi campus. | 12 | Job | - | - |
| 1.03 | DDC Controller with I/O module, expandable per I/O summary — minimum 32-bit dual-microprocessor standalone controller on TCP/IP, BACnet/IP, integral web browser, calendar function (day/month/week/year), real-time clock, 1-second scan time; peer-to-peer capable without router/PC; lockable powder-coated cabinet with connector strip, internal wiring, step-down transformer and MCB | 12 | Nos | - | - |
| 1.04 | UL-listed, BTL-certified Hardware Interface / Soft Integrator with inbuilt web browser for open-protocol third-party integration; same make as DDCs, with all necessary ports for software integration | 1 | Nos | - | - |
| 1.05 | Immersion-type Temperature Sensor with Well | 5 | Nos | - | - |
| 1.06 | Ultrasonic Water Flow Meter, Pipe Dia. 250 mm | 5 | Nos | - | - |
| 1.07 | Outside Air Temperature + Humidity (RH) & Wet-Bulb Sensor, with sun-shield and rain protection | 5 | Nos | - | - |
| 1.08 | Water Bi-Level Switch for Cooling Tower level status | 3 | Nos | - | - |
| 1.09 | Differential Pressure Switch across Pump (status indication) | 4 | Nos | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.60 MB
BOQ_972452.xls
BOQ • 0.29 MB
BMSTender.pdf
Tender Documents • 0.58 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .