| 1 | L1₹15.9 LAccepted-AOC 10TH FLOOR UNIT 2 TECHNIPLEX 2 VEER SAVARKAR FLYOVER S V ROAD GOREGOAN WEST MUMBAI 400 062 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400062 | ₹15.9 L Quoted ₹16.4 L | L1 | Accepted-AOC Award of Contract |
| Sl No | Description | Qty | Unit | VAV Airconditioning L1 |
|---|---|---|---|---|
| 1.00S.I.T.C of Horizontal/ Vertical double decker type Integrated factory fabricated EUROVENT CERTIFIED AS PER EN-1886/13053 Double skin Air handling units. Frame work construction : Frame work of Extruded aluminum alloy section with Thermal Break for AHU. It shall be made out of 1 mm pre coated galanised steel sheet outside & 1 mm thick Aluzinc sheet inside, with 50 mm thick Rock wool insulation with density not less than 96 + 4 kg /cum between them. Thermal Bridging Factor : TB2 (0.60 <_ kb < 0.75) The casing sealing : should confirm of LI class of leakage as per EN 1886. Thermal Transmittance - T2 Casing strength - D1 Drain Pan: Drain pan made out of 1.2mm stainless steel (SS Grade 304) sheet instulated with 25mm thick closed cell insulation nitrile rubber with thermal brake profile. AHUs to be provided with marine lamps on both sides and view ports. Installation of new AHU with all new foundations, vibration isolator pads etc shall be in vendors scope. Make - Stulz, System Air, Flaktwood, Trane, Euroclima. Filter Section - Mixing box with AL damper at inlet of return air and fresh air. Return Air Section shall be provided with Washable type of ‘EU 4’ filter ( Pre filter, efficiency 90% down to 10 Micron) and 'EU 7' filters ( Micro Vee filters , efficiency 99% down to 3 Micron ) before cooling coil. Coil Section : Chilled water coil of 6 row deep constructed with Aluminium fins of minimum 0.15 mm, thickness with Anti corrisive coating and copper tubes of minimum 20 gauge thickness. Copper tube shall be 1/2'' mm diameter. The coil face area shall not exceed 2.5m/sec. The coil section shall be equipped with factory fitted Mist eliminator of PVC. Space provision for UV lamps before cooling coil. | ||||
| 1.01 | Fan Section: Direct drive backward curved Radial EC fan with permanent magnet brushless DC motor for stepless variation of speed of fan based on temperature/pressure sensor Inputs. The fan section shall be provided with limit switch for safety to shut off fan during Opening of access door. Supply air outlet damper provided. Minimum Two nos. or more fans with 100% redundancy as per CFM should be considered for each AHU. Fan Make - Ebm, Zeil abegg
Electrical starter : Built in starter panel with Auto /Manual switch and incomer power terminal provisions must be provided as Integral part of the AHU. AHU to be provided with individual fan run status.
Electrical starter : Built in starter panel with Auto /Manual switch and incomer power terminal provisions must be provided as Integral part of the AHU. AHU to be provided with individual fan run status.
Removing of old AHU along with connected piping, old connected ducting, power and control cabling and foundation. Installation of new AHU along with supply installation of new chilled water piping with insulation of TF quality 50 mm thick thermocole section covered with hessain cloth, SS wire mesh and 12 mm thick sand cement plaster in finished condition. New foundation blocks required for installation of new AHU shall be in vendors scope. Removing of old insulation material, taking out of TMH premises and disposing it in proper manner is in vendors scope.
HBB Servic floor Endoscopy (2400 CFM, 6TR, 125mm Static) | 1 | Nos. | 5,99,096 ₹6.0 L |
| 2.00 | Supply, installation, testing & commissioning of Laminar Cabinet of Size-7 feet * 4 feet made out of SS 304 grade with Minipleated High Efficiency Particulate filters of H13 rating with a filtration efficiency of 99.99% down to 0.3 microns . The filters shall be made of water resistant,fire‐retardant microfine glass fibre media with Hotmelt Foil seperators. The maximum Pressure Drop of the HEPA filter will not exceed 25 mmWC in clean condition MOC of filter frame shall be Aluminium Anodized.The filters shall be supplied with factory fitted leak-proof 18G SS 304 Plenum Box. Joint shall be with neoprene rubber gasket to minimize leakage. The plenum box shall be common for multiple filters and MOC will be 1.2 mm thick ss 304 will have perforated 1.2 mm thk SS 304. The filteration ceiling system should have flow equilizer to achieve uniform and constant air distribution over the entire surface. It should have provision for the insertion of OT light pendent at the centre of the cabinet with neccessary covering sheet at top and bottom in SS 304 sheet. The flow rate of Laminar Air Flow Ceiling should not be less than 2400CFM at average velocity of 0.24 m/s.All hardwares to be in medical grade Stainless Steel construction only.MOC of filter resting frame shall be made of SS 304. Entire Laminar Cabinet shall be thermally insulated with Armaflex make antimicrobial 23 mm thick,50 kg/cum density FM approved closed cell nitrile insulation backed with Aluminium Foil. Validation of Filters at site is in vendor scope which includes DOP and particle count test. | 1 | Nos. | 3,79,892 ₹3.8 L |
| 3.00 | Carrying out validation of clean room AHU's filters (At AHU Level) and inside the OT served by this AHU (DOP & Particle count test) | 1 | Nos. | 23,530 ₹23,530 |
| 4.00 | SITC of insulated Butterfly Valves with extended neck of Pressure Rating PN 16, with extended stem complete with gaskets, suitable flanges, nutbolts as per relevent standards and specification. Make- Kitz/Audco/Danfoss
32 mm dia | 4 | Nos. | 5,165 ₹20,660 |
| 5.00 | SITC of Y Strainer of ductile CI body with stainless steel strainer for chilled water circulation including insulation as per standard.
Make - Trishul / Emrald / Sant
32 mm dia | 1 | Nos. | 4,632 ₹4,632 |
| 6.00Electronic, self-balancing, pressure independent type dynamic balancing valve with integrated 2 way modulating rotory type control valve with integrated Temperature sensor, ultrasonic flowsensor and calculator. The electric actuator shall be capable of accepting upto 10V DC electric signal for signal input for Temperature control input or DDC input. The Valve shall be compatible to Building Automation System (modbus/Bacnet) integration or through Cloud API with following points like BTU, true Flow, delta T, Delta T manager status and chill water temperature integration and shall be capable to maintaining Delt T with low Delta T manager. The valves selection to be done depending on flow requiremnt of AHU, other accesories to be included as per specification: Make- Belimo, AZBIL,Sauter | ||||
| 6.01 | 25 mm dia | 1 | Nos. | 1,21,005 ₹1.2 L |
| 7.00 | Supply and Installation of 5 mm wall thickness PVC drain piping for Air handling unit with all fittings and supports, saddle, pressure clamps etc with 9 mm thick tubular type nitrile insulation wrapped with glass cloth dipped in adhesive recommended by manufacturer.
Make- Prince/ Astral/ Kisan/ Supreme
50 mm dia | 30 | Rmt | 485 ₹14,550 |
| 8.00 | Supply, installation, balancing and commissioning of factory fabricated Aluminium sheet
metal rectangular/round ducting complete with neoprene rubber gaskets, elbows,
splitter dampers, vanes, hangers, supports etc. as per approved drawings and
specifications of following sheet thickness complete as required.
Make- Jindal / Sail / Tata
20 Gauge | 70 | SQM | 1,855 ₹1.3 L |
Tender Value
₹17.4 L
EMD Value
₹34,740
Closing Date
10 May 2025, 6:55 pmClosed
CE, TMC on behalf of Director, TMC
Engineering Department, 6th Floor, Service Block, TMH, Parel
HVAC Works for proposed Endoscopy Operation Theater in OT Complex at 4th floor Homi Bhabha Block
2025_TMC_855699_2
TMC/HVAC/Endoscopy Work OT
Open Tender
Machineries/ Mechanical Engg Items
90 days
TMH, Parel
As per tender document
5 documents required · 5 mandatory
₹0
₹34,740
5 Feb 2026
2 May 2025
13 May 2025
2 May 2025
10 May 2025
4 May 2025
2 May 2025 - 3 May 2025
Amount
S.I.T.C of Horizontal/ Vertical double decker type Integrated factory fabricated EUROVENT CERTIFIED AS PER EN-1886/13053 Double skin Air handling units. Frame work construction : Frame work of Extruded aluminum alloy section with Thermal Break for AHU. It shall be made out of 1 mm pre coated galanised steel sheet outside & 1 mm thick Aluzinc sheet inside, with 50 mm thick Rock wool insulation with density not less than 96 + 4 kg /cum between them. Thermal Bridging Factor : TB2 (0.60 <_ kb < 0.75) The casing sealing : should confirm of LI class of leakage as per EN 1886. Thermal Transmittance - T2 Casing strength - D1 Drain Pan: Drain pan made out of 1.2mm stainless steel (SS Grade 304) sheet instulated with 25mm thick closed cell insulation nitrile rubber with thermal brake profile. AHUs to be provided with marine lamps on both sides and view ports. Installation of new AHU with all new foundations, vibration isolator pads etc shall be in vendors scope. Make - Stulz, System Air, Flaktwood, Trane, Euroclima. Filter Section - Mixing box with AL damper at inlet of return air and fresh air. Return Air Section shall be provided with Washable type of ‘EU 4’ filter ( Pre filter, efficiency 90% down to 10 Micron) and 'EU 7' filters ( Micro Vee filters , efficiency 99% down to 3 Micron ) before cooling coil. Coil Section : Chilled water coil of 6 row deep constructed with Aluminium fins of minimum 0.15 mm, thickness with Anti corrisive coating and copper tubes of minimum 20 gauge thickness. Copper tube shall be 1/2'' mm diameter. The coil face area shall not exceed 2.5m/sec. The coil section shall be equipped with factory fitted Mist eliminator of PVC. Space provision for UV lamps before cooling coil.
Fan Section: Direct drive backward curved Radial EC fan with permanent magnet brushless DC motor for stepless variation of speed of fan based on temperature/pressure sensor Inputs. The fan section shall be provided with limit switch for safety to shut off fan during Opening of access door. Supply air outlet damper provided. Minimum Two nos. or more fans with 100% redundancy as per CFM should be considered for each AHU. Fan Make - Ebm, Zeil abegg Electrical starter : Built in starter panel with Auto /Manual switch and incomer power terminal provisions must be provided as Integral part of the AHU. AHU to be provided with individual fan run status. Electrical starter : Built in starter panel with Auto /Manual switch and incomer power terminal provisions must be provided as Integral part of the AHU. AHU to be provided with individual fan run status. Removing of old AHU along with connected piping, old connected ducting, power and control cabling and foundation. Installation of new AHU along with supply installation of new chilled water piping with insulation of TF quality 50 mm thick thermocole section covered with hessain cloth, SS wire mesh and 12 mm thick sand cement plaster in finished condition. New foundation blocks required for installation of new AHU shall be in vendors scope. Removing of old insulation material, taking out of TMH premises and disposing it in proper manner is in vendors scope. HBB Servic floor Endoscopy (2400 CFM, 6TR, 125mm Static)
Supply, installation, testing & commissioning of Laminar Cabinet of Size-7 feet * 4 feet made out of SS 304 grade with Minipleated High Efficiency Particulate filters of H13 rating with a filtration efficiency of 99.99% down to 0.3 microns . The filters shall be made of water resistant,fire‐retardant microfine glass fibre media with Hotmelt Foil seperators. The maximum Pressure Drop of the HEPA filter will not exceed 25 mmWC in clean condition MOC of filter frame shall be Aluminium Anodized.The filters shall be supplied with factory fitted leak-proof 18G SS 304 Plenum Box. Joint shall be with neoprene rubber gasket to minimize leakage. The plenum box shall be common for multiple filters and MOC will be 1.2 mm thick ss 304 will have perforated 1.2 mm thk SS 304. The filteration ceiling system should have flow equilizer to achieve uniform and constant air distribution over the entire surface. It should have provision for the insertion of OT light pendent at the centre of the cabinet with neccessary covering sheet at top and bottom in SS 304 sheet. The flow rate of Laminar Air Flow Ceiling should not be less than 2400CFM at average velocity of 0.24 m/s.All hardwares to be in medical grade Stainless Steel construction only.MOC of filter resting frame shall be made of SS 304. Entire Laminar Cabinet shall be thermally insulated with Armaflex make antimicrobial 23 mm thick,50 kg/cum density FM approved closed cell nitrile insulation backed with Aluminium Foil. Validation of Filters at site is in vendor scope which includes DOP and particle count test.
Carrying out validation of clean room AHU's filters (At AHU Level) and inside the OT served by this AHU (DOP & Particle count test)
SITC of insulated Butterfly Valves with extended neck of Pressure Rating PN 16, with extended stem complete with gaskets, suitable flanges, nutbolts as per relevent standards and specification. Make- Kitz/Audco/Danfoss 32 mm dia
SITC of Y Strainer of ductile CI body with stainless steel strainer for chilled water circulation including insulation as per standard. Make - Trishul / Emrald / Sant 32 mm dia
25 mm dia
Supply and Installation of 5 mm wall thickness PVC drain piping for Air handling unit with all fittings and supports, saddle, pressure clamps etc with 9 mm thick tubular type nitrile insulation wrapped with glass cloth dipped in adhesive recommended by manufacturer. Make- Prince/ Astral/ Kisan/ Supreme 50 mm dia
Supply, installation, balancing and commissioning of factory fabricated Aluminium sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. Make- Jindal / Sail / Tata 20 Gauge
Supply ,Installation of Thermal Insulation of Nitrile Rubber Insulation 25 mm thick with self adhesive properties & all the joints sealed & finished with self adhesive tape. & as per technical specifications. For Supply Air Duct Make : Armaflex, K Flex, Aeroflex.
SS vertical return air risers. Make- Airtech/ Fabtech/ AAF/ Camfil
Supplying and installing of 6" dia Pressure gauge with SS Ball valve. Make- H GURU/ Dwyer/ Gandhi
Supplying and installing of 6" dia Temperature gauge with SS thermowells. Make- H GURU/ Dwyer/ Gandhi
Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc Make- Dynacraft, Systemair, Carryair.
Supply and Fixing of Extruded AL powder coated Four way Diffuser with removable core,4 side flanges. Make- Dynacraft/Ravistar/Caryaire/Ductocraft (For Return Air)
Supply and Fixing of Extruded AL powder coated Return Air Grills with louvers but without AL volume control damper. Make- Dynacraft/Ravistar/Caryaire/Ductocraft (For Return Air)
SITC of Chilled water piping out of M.S. heavy class ERW C -class pipe (pressure rating PN 16) confirming to relevant IS 1239 Code upto 150 mm dia pipes, from 150 mm and above upto 2S0 mm dia 6 mm thick pipes and above 250 mm dia 6-8 mm thick pipes, with necessary fittings, teak wood gutties for indoor and hard puff blocks for outdoor pipes, elbows, tees, reducers. Suitable GI supports as specified. Pipe make - Tata / Jindal / SAIL Supply & Installation of Chilled Water Piping Insulation In Building Area of Nitrile Rubber self adhesive properties having a K value of not more then 0.033º W/m k at an average temperature of 0 deg C. Density shall be between 40 to 60 Kg/M³ +/- 2% Temperature range : 5 to 12 deg. C, 25 mm thk. Insulation for pipe dia 0 to 80 mm & 32 mm thk for pipe dia 100 & above as per technical specifications covered with UV Glass cloth covering system for the protection of existing nirtrile insulation 205 GSM thick applied on the nitrile insulation with proper adhesive and 26g Al cladding. Insulation Make - Armafex / ALP
32 mm dia pipe