Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹61.5 LAccepted-AOC | ₹61.5 L Quoted ₹64.6 L | L1 | Accepted-AOC Being 1st Lowest |
| 2 | L2₹66.2 LRejected-Finance | ₹66.2 L | L2 | Rejected-Finance Being 2nd Lowest |
| 3 | L3₹67.0 LRejected-Finance | ₹67.0 L | L3 | Rejected-Finance Being 3rd Lowest |
| 4 | L4₹76.0 LRejected-Finance 702 A1 SHREE PRASAD TAWADEWADI SHREE DATTAGURU PARK KUMBHARWADA URAN DIST RAIGAD MAHARASHTRA 400 702 | URAN | RAIGAD | MAHARASHTRA | 400702 | ₹76.0 L | L4 | Rejected-Finance Being 4th Lowest |
| 5 | Rejected-Technical SURVEY NO 93 392 PACHMARHI NEAR MILITARY HOSPITAL PAHMARHI HOSHANGABAD M P 461 881 | PACHMARHI | HOSHANGABAD | MADHYA PRADESH | 461881 | - | - | Rejected-Technical Not admitted due to not enlisted in appropriate category i.e. b(ii) |
| Sl No | Description | Qty | Unit | D.N.PATIL L1 | MC Gandhi and Sons L2 | Sagar Electricals L4 | LAXMI ENTERPRISES L3 |
|---|---|---|---|---|---|---|---|
| 1.00 | Dismantling top cover alongwith conservator tank for filteration of Transformer oil and after draining out transformer oil up to terminal level in situ by dismentling copper bus bars HT/LV Bushing and earthing strips,replacement of LT/HT bushing and terminal rod of brass gasket, nuts, bolts & washers etc. Refitting top cover & conservator tank after cleaning and filteration, removing the sludge , reconnecting HT/LT cable/conductor with bushings and earthing strips,& filteration of tranformer oil including toping up of transformer oil by adding new transformer oil having 60 KV dielectric strength and charging/testing the transformer on load complete all as directed by Engineer-in-charge,for transformer of rating upto 160 KVA capacity.
Note : (i) Contractor should make his own arragement of filteration plant at each transformer sites for filteration of transformer oil including provision of electric supply to the filteration plant.
(ii) New transformer oil shall be measured and paid separately.
(iii) Cost of HT/LT bushing and terminal rod wiil be measured and paid separately
(iv) Filteration of oil will be measured separately.
(v) Contractor have to test di-electric strength breakdown voltage before and after filteration of oil and record of the same duly signed by Engineer in charge & contractor to be kept on record. | 2 | Each Job | 7,100 ₹14,200 | 5,900 ₹11,800 | 7,500 ₹15,000 | 4,000 ₹8,000 |
| 2.00 | -Ditto - all as per srl item No.1 above but for transformer of rating 200 KVA. | 3 | Each Job | 7,250 ₹21,750 | 6,000 ₹18,000 | 7,700 ₹23,100 | 4,500 ₹13,500 |
| 3.00 | -Ditto - all as per srl item No.1 above but for transformer of rating 250 KVA. | 2 | Each Job | 7,500 ₹15,000 | 6,500 ₹13,000 | 7,900 ₹15,800 | 5,000 ₹10,000 |
| 4.00 | -Ditto - all as per srl item No.1 above but for transformer of rating 315 KVA. | 3 | Each Job | 7,900 ₹23,700 | 7,500 ₹22,500 | 8,000 ₹24,000 | 5,500 ₹16,500 |
| 5.00 | -Ditto - all as per srl item No.1 above but for transformer of rating 400 KVA. | 2 | Each Job | 8,200 ₹16,400 | 8,500 ₹17,000 | 8,350 ₹16,700 | 6,000 ₹12,000 |
| 6.00 | -Ditto - all as per srl item No.1 above but for transformer of rating 500 KVA. | 5 | Each Job | 8,350 ₹41,750 | 8,600 ₹43,000 | 8,750 ₹43,750 | 7,000 ₹35,000 |
| 7.00 | -Ditto - all as per srl item No.1 above but for transformer of rating 630 KVA. | 1 | Each Job | 8,700 ₹8,700 | 9,000 ₹9,000 | 9,000 ₹9,000 | 8,000 ₹8,000 |
| 8.00 | -Ditto - all as per srl item No.1 above but for transformer of rating 1000 KVA. | 1 | Each Job | 9,000 ₹9,000 | 9,250 ₹9,250 | 9,500 ₹9,500 | 9,000 ₹9,000 |
| 9.00 | Supply only the following spare parts of transfomer 22 /0.433 KV operated in item no 01 to 08:-
HV Bushings for 22 KV from up to 160 KVA | 8 | Each | 300 ₹2,400 | 275 ₹2,200 | 300 ₹2,400 | 200 ₹1,600 |
| 10.00 | HV Bushings for 22 KV from 200 KVA to 630 KVA | 16 | Each | 400 ₹6,400 | 435 ₹6,960 | 450 ₹7,200 | 450 ₹7,200 |
Updated dates
Tender Value
₹70 L
EMD Value
₹1.3 L
Closing Date
8 Apr 2026, 6:00 pmClosed
CWE Karanja
CWE Karanja Naval Station Karanja Uran, Raigad - 400704
COMPREHENSIVE REPAIR WORKS OF B/R AND E/M NATURE LIKE REPAIRS TO CHAIN LINK FENCING, PLINTH PROTECTION, PCC, REPAIR, REPLACEMENT, MAINT OF HT 2/4/6 POLE STRUCTURE, GANG OPERATED DEVICES, PANELS AIR BREAK SWITCHES SERVICE OF HT SWITCH GEAR AND RMUS AN
2026_MES_755428_1
84515-K/E8
Open Tender
Electrical and Maintenance Works
180 days
Naval Staion Karanja
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,000
GE (NW) Karanja
₹1.3 L
25 May 2026
6 Mar 2026
10 Apr 2026
6 Mar 2026
8 Apr 2026
27 Mar 2026
Dismantling top cover alongwith conservator tank for filteration of Transformer oil and after draining out transformer oil up to terminal level in situ by dismentling copper bus bars HT/LV Bushing and earthing strips,replacement of LT/HT bushing and terminal rod of brass gasket, nuts, bolts & washers etc. Refitting top cover & conservator tank after cleaning and filteration, removing the sludge , reconnecting HT/LT cable/conductor with bushings and earthing strips,& filteration of tranformer oil including toping up of transformer oil by adding new transformer oil having 60 KV dielectric strength and charging/testing the transformer on load complete all as directed by Engineer-in-charge,for transformer of rating upto 160 KVA capacity. Note : (i) Contractor should make his own arragement of filteration plant at each transformer sites for filteration of transformer oil including provision of electric supply to the filteration plant. (ii) New transformer oil shall be measured and paid separately. (iii) Cost of HT/LT bushing and terminal rod wiil be measured and paid separately (iv) Filteration of oil will be measured separately. (v) Contractor have to test di-electric strength breakdown voltage before and after filteration of oil and record of the same duly signed by Engineer in charge & contractor to be kept on record.
-Ditto - all as per srl item No.1 above but for transformer of rating 200 KVA.
-Ditto - all as per srl item No.1 above but for transformer of rating 250 KVA.
-Ditto - all as per srl item No.1 above but for transformer of rating 315 KVA.
-Ditto - all as per srl item No.1 above but for transformer of rating 400 KVA.
-Ditto - all as per srl item No.1 above but for transformer of rating 500 KVA.
-Ditto - all as per srl item No.1 above but for transformer of rating 630 KVA.
-Ditto - all as per srl item No.1 above but for transformer of rating 1000 KVA.
Supply only the following spare parts of transfomer 22 /0.433 KV operated in item no 01 to 08:- HV Bushings for 22 KV from up to 160 KVA
HV Bushings for 22 KV from 200 KVA to 630 KVA
HV Bushings for 22 KV 1000 KVA
HV terminal rod with nut bolts, caps etc for 22 KV from up to 160 KVA
HV terminal rod with nut bolts, caps etc for 22 KV from 200 KVA to 630 KVA
HV terminal rod with nut bolts, caps etc for 22 KV 1000 KVA
LV Bushings for 22 KV from up to 160 KVA
LV Bushings for 22 KV from 200 KVA to 630 KVA
LV Bushings for 22 KV 1000 KVA
LV terminal rod with nut bolts, caps etc for 22 KV from up to 160 KVA
LV terminal rod with nut bolts, caps etc for 22 KV from 200 KVA to 630 KVA
LV terminal rod with nut bolts, caps etc for 22 KV 1000 KVA
LT Brass connectors for 12 mm
LT Brass connectors for 20 mm
LT Brass connectors for 30 mm
LT Brass connectors for 42 mm
Supply and fix in repairs Dial type temprature guage 100mm dia with dual calibration in degree celcius and degree Fahrenheit, range 0 to 100 c and equivalent degree Fahrenheit complete with capabillary tube and sensor suitable for transformer of any rating as directed by Engineer-in-Charge
Supply and filling new transformer oil having 60 KV di-electric strength and conforming to IS : 335 for replacement or topping up to oil level mark at the conservator.
Material for rewinding of transformer core with same numbers/grade of copper enamelled conductor with same size of turns as per manufactures's specification and testing and commissioning transformers after repair.
Material for reinsulation of copper windings (LT and HT), Class B, with Electrical Grade Insulating Kraft paper all confirming to IEC-60554-3-5 (1984).
Filteration of transformer oil, in situ, to achieve dielectric strength of the oil not less than 50 KV with 2.5 mm gap all as directed by Engineer-in-charge.Contractor will submit before & after testing report of transformer oil. Note :(i)Contractor will submit before & after testing report of transformer oil.
Disconnecting HT/LT and earth termination connections from transformer, taking down the transformers from plinth/platform and loading into the vehicle; transporting the same to workshop for carrying out necessary repairs and back ,reconnecting HT/LT connections at site and charging the transformer on load, commissioning and testing including meggar test at site all as directed by Engineer - in - Charge
Draining out transformer oil, dismantling top cover alongwith conservator tank, taking out core assembly after disconnecting connections, rewinding with same size and type of copper conductor and number of turns and insulating material such as paper insulator sleeves, heating etc. Putting back the core assembly into the tank after removing sludge and replacement of HT & LT bushing complete with brass terminal, refixing top cover and conservator including replacement of gasket, nut, bolts & washers (filling new transformer oil having 60 KV dielectric strength and carring out type tests as per IS 2026 in presence of Engineer - in - charge for the following capacity :- Note : (i) New transformer oil and its filling shall be measured and paid separately under relevant items of schedule. (ii) Cost of rewinding material, insulation material and spares of transformer shall be measured and paid separately under relevant item of Sch . (iii) Replacement of spares will be on required basis all as directed by Engr-inCharge. 75 to 160 KVA
Ditto - all as per srl item No.31 but for 200 to 315 KVA
Ditto - all as per srl item No.31 but for 400 to 1000 KVA
Disconnecting HT/ LT and earth termination connections from Trolley Mounted Transformer (500 KVA Cap.) and towing the same to a location, within 5 KMs, as directed by Engr-in-Charge including Material and labour for making of HT/ LT and earth termination connections of the Trolley Mounted Transformer to the existing electric distribution system in Indoor/Outdoor Substation complete all as specified and directed by Engr-in-Charge. NOTE - (a). Trolley Mounted transformer will be issued to contractor by MES however Contractor has to make his own arrangements of towing vehicle. (b). The job also includes disconnecting of HT/ LT and earth termination connections of Trolley Mounted Transformer and towing the same to a location as directed by Engr-in-Charge.
Testing of transformers of various capcities installed at various locations at Naval Station Karanja by performing following tests - 1.IR Value on L.V & H.V side using 500 V & 5KV Megger respectively,2.Ratio on all the taps.,3.Magnetic Balance tests on L.V & H.V.,4.Vector group.,5.Magnetizing current. 6.Winding Resistance Test on H.V & LV terminals. Note : (i) Contractor should make his own arragement of testing equipments and electric supply so required (ii) A detailed Test Report should be submitted to Engr-in-Charge.
Supply and fix in repairs heat shirnk right angled boots for XLPE 22 KV 120 Sqmm cable including dismantling of HT cable from HT side of Transformer / HT Breakers.
Material and labour in repair for Heat shrinkable cable end termination joint including jointing Kit outdoor type suitable for earthed 3 core 95/120 sqmm HT 22KV XLPE aluminium conductor cable and HV test after jointing and connecting up complete all as specified and directed. Make:- Raychem/ XICON/ M-Seal/Denson
Material and labour in repair for Heat Shrinkable straight through jointing kit with all necessary jointing material suitable for HT 22 KV XLPE 3 core 95/120 sqmm aluminium conductor cable complete all as specified and directed. Make- Raychem/ XICON/ M-Seal/Denson
Supply and fix in repairs breather assembly with silica gel suitable in situ for transformer of any rating as directed by Engineer-in-Charge.
Supply and fixing CRC bottle spray of 500 ml for opening of rusty surfaces and rusty nut bolts all as specified and as directed by Engineer-in-Charge.
Taking out dry type transformer of capacity 100 KVA to 400 KVA to the workshop with necessary arrangements by giving the supply witjh trolley mounted transformer and refixing the same after complete repairs.
Material and labour for preparation of old painted surfaces of 100 KVA transformer with scrapers, any number of coats, any width or girth and applying two coats of synthetic enamel paint by spray painted including writing 5mm/MES numbers complete all as specified and directed
-Ditto- all as per item No 42 above but 160 KVA transformer.
-Ditto- all as per item No 42 above but 200/250 KVA transformer
-Ditto- all as per item No 42 above but 315 KVA transformer
-Ditto- all as per item No 42 above but 400/500 KVA transformer
-Ditto- all as per item No 42 above but 630 KVA transformer
-Ditto- all as per item No 42 above but 1000 KVA transformer
Material and labour for cleaning and checking the LT/HT connections of dry type transformers and taking out the moisture from the cores of the transformer of capacity 62.5 kVA to 250 KVA all as specified and as directed by Engineer-in-charge
Material and labour for cleaning and checking the LT/HT connections of dry type transformers and taking out the moisture from the cores of the transformer of capacity 315 KVA to 750 KVA all as specified and as directed by Engineer-in-charge
Material and labour for arresting the leakage and cheking out of the LT/HT connections from the transformers of capacity 75 KVA to 250 KVA all as specified and as directed by Engineer-in-charge
Material and labour for arresting the leakage and cheking out of the LT/HT connections from the transformers of capacity 315 KVA to 500 KVA all as specified and as directed by Engineer-in-charge
Material and labour for arresting the leakage and cheking out of the LT/HT connections from the transformers of capacity 625 KVA to 1000 KVA all as specified and as directed by Engineer-in-charge
Periodical Check / preventive maint of HT VCB/RMU 22 KV 800 Amps, 50 Hz as under :- (a) Checking the closing & opening operation of VCB and functional checks and Repair/ Replacement of the defective components.,( b) Overhauling and Calibration of relays (secondary injection/Primary injection on each multiple setting of relays). , ( c) Setting and coordination of relays. (d) Checking and recording of IR value of VCB trolley and panel. , (e) Checking/repairing/rectification of the control wiring., (f) Replacement of panel heater 80 watt., (g) Replacement of worn out bushing CT/Busbar support insulators, (h) Replacement of worn out bushing PT/Busbar support insulators ,(j) Replacement of unserviceable and Open circuit CT's., (k) Checking fibre plates, gaskets and applying multi grease to the mechanical parts & dry graphite conductive sealant to contacts of PT etc. & re-assembling the same and commissioning complete to entire satisfaction of Engineer-in-Charge., (l) Testing of polarities of CT's., (m) High voltage testing with high voltage tester of CT & Breaker pole to withstand working pressure of HT 22 KV to ascertain servicieability and spare parts found defective to be replaced for smooth functioning as directed by Engineer-in-Charge.(n) Labour only for Opening the busbar chamber of HT 22KV VCB panel board cleaning the bus bar chamber, inspect the CT's wiring, spout insulator & bus-bar joints & tightening if required & heating up with hot air blower to remove moisture, meggering, HV testing applying TRTPPEX(B) supplied against Sl Item No 4(b) here-in-after to bus bar & commissioning complete all as specified & directed by Engineer-in-charge.Note:- (i) All spares required for replacement shall be measured and paid separately under respective item of schedule here-in-after as supply only.( ii) Machine grease, oil, liquid sealant and any minor item costing upto Rs 250 will be included in the unit rate of above item and for satisfactory function of the breakers and no extra cost will be allowed. Decision of accepting officer in this regard will remain final & binding. (iii) The overhauling of HT breakers to be carried out either through OEM's service Engineer/authorised dealer/San & Engg consultant /Triotech consultant/ those who posses HT handling license.
Supply only following spare parts required for item No.37 here-in-bofore (Note:- the element of fixing of spare is already included in respective Sl Item No. 37 here-in-before) suitable for VCB of 800 Amps all as per sample :- (a) Spout insulator (Epoxy)
TRTPPX (B) for HT 22 KV for breaker
Current Transformer 22 KV single phase indoor Resin cast CT Ratio 30-15/5-5 Amps Class 1.0 insulation level 28 KV/75 KV as per IS 2075
Strip type heater 80 watt
Closing coil
Tripping coil
PT Primary fuse 22 KV 23 Amps
Control fuse 2 Amps with HRC fuse and fuse holder in existing panel and as specified and directed. Make:EE/Standard/Havells/L&T
Insulation Tape suitable for HT 22 KV 1.5" wide. Make : 3M or equivalent.
VCB gasket suitable for VCB 22KV 800 Amps indoor type all as specified and directed.
Baffle pot assembly suitable for VCB, 22 KV, 800 Amps, indoor type all as specified and directed.
Main moving contact bolted/threaded type suiatable for VCB, 22KV, 800Amps, indoor type all as specified and directed.
PT single phase indoor Resin cast PT Ratio 22kV/R3/110V/R3 Class 1.0, 200VA.
HT bushing with spindle
Thermostat - 0-100 Deg. Celcius
Moving contact rod
Upper fix contact
Lower fix contact
Top and bottom male contact
Female contact
Support insulator
Partition fiber plate
Copper strip of 800 Amps (per Kg)
Material and labour for earthing complete with GI earth plate electrode of size 60cm x 60cm x 6 mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5m below the normal ground level connected with GI strip 32 x 6mm by means of bolts, nuts, check nuts & washers of galvanished iron steel including necessary excavation and earth work in any type of soil, removing surplus soil to a distance not exc 50m, with and including PCC chamber in PCC (1:2:4), type B1,using (20mm graded stone aggregate),"mild steel angle iron frame" made out of MS angle iron of size 40x40x6mm thick duly painted with two coats of synthetic enamel paint over one coat of red oxide zinc chrome primer hinged with and including 6mm thick CI cover with handle, watering arrangement with funnel internally secured with wire mesh with 40mm dia medium grade pipe for watering 40mm dia light grade, GI pipe for lead protection in and including alternate layers of charcoal dust and common salt complete all as shown in electrical "plate No '3' and connected to earthing test point all as specified and indicated including testing on completion including retrieving old GI earth plate, CI cover, GI pipes, angle iron frame from existing earthing complete all as specified and directed.
Supply and fix earth continuity conductor or main earthing lead fixed to wall on batten or fixed to pole GI strip 32 x 6 mm all as specified and directed.
Supply, laying in repairs, in trenches /ducts/fixing on pole/STR with suitable size of GI clamp made out of GI strip 32 mm x 6 mm, XLPE HT insulated, screened, earthed, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) of size 3 x 120sqmm with aluminium conductor suitable for 22 KV grade as per relevent IS including latest amendment for IS (ISI marked cable) testing, commissionong along with HT cable route indicator complete all as specified and directed. Note:- (a) Earth work, EHV cable cover, sand coushioning & GI pipe will be measured and paid seperately. (b) High voltage test to be conducted at site with suitable voltage before and after laying of HT cable and reading shall be recorded jointly and test report to be submitted in triplicate to the Engineer-in-Charge. The cost of the same shall be deemed to be included in the unit rate quoted above.
Taking out carefully cable covers & HTcable from excavtaed trench/duct/pole of size 120 sqmm 3 core
Relaying of HT cable of size 120 sqmm 3 core in trench/duct/pipe obtained from ser item no 42
Excavation in trenches for not exc 1.5 mtr wide and not exc 1.5 mtr depth and getting out in soft/loose soil including taking out faulty cable/cable, cable covers and GI pipe complete all as specified and directed.
Removing excavated materials n.exc 50m and depositing where directed at a level n.exc 1.5m above the Starting point.
Returning filling in including spreading levelling watering and well ramming in layers n.exc 25cm complete all as specified & directed.
Supply and lay sand cushioning to under ground HT cable complete all as specified in SSR Part-I and as directed by Engineer-in-charge.
Supply and Laying reinforced precast concrete cable cover laid width wise factory made, class EHV type 1 with peak size 450 mm x 230 mm x 50 mm complete all as specified and directed.
Laying only precast concrete cover of size 450mm x 230mm x 50 mm obtained from srl No 1
Material and labour for drawing 3 phase with aluminium conductor, steel reinforced DOG.
Material and labour notice plate of 1.6 mm thick mild steel sheet vitreous enamelled white, with letters figures and conventional skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size for HT 22 KV of size 25 x 20 cm.
Material and labour cross arms, bracing, supports, clamps and back plates fabricated from structual steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts in any shape or size as indicted and inclusive of one primer coat one under coat and two finishing coat of aluminium paint.
Dismantling of unserviceable cross arms of MS Chanel/angle sections etc complete all as specified and directed.
Supply and fix in repair following spare parts for out door type ring main units of various configuration complete all as specified and as directed by Engr-in-charge. Ring LT/CT 30/1A, 2.5VA CL-5P10
LT CT Resin cast iron type ratio - 100/1A, 2.5VA CL-1.0
PT 22KV/Root 3/110V/ Root 3, 50 VA-CL-1/EE090562, 3 Phase
Auxillary transformer 22KV/Rt3/230V,AC, 500VA
HT Fuse 22 KV/3.15A/EE090344
CS FPI -earth fault indicator, E/F-10-100A, with 1NO+1NC, sensor-100-120mm Dia with 3m wire, indicator model : CSFPI-E-A-H
8 way battery and charger I/P 230V, O/P 24V DC, 10A (flat type) (12 V X02 battery)
Digital MFM meter flush mounted, size-96x96mm, AC, class 1.0, Aux-40-300V AC model elite 303, CT & PT ratio programmable with RS 485 port
O/C & E/F self powered relay-CSDPR-V2-300-D-L-N-M-C1 with modbus 1A, AUX supply-18-60V DC O/C minimum setting-10% & E/F- minimum setting-5%
Local Remote sitwch 3 Pole/2W/ EE090691
LBS function motor UN2-30 24VDC / 37303017-01
9 micro switch kit /33111884-01
Relay electm 24V DC 5A 4C /O/ 9423140
Relay electm 230V AC 5A 4C /O/ 9423142
Relay electm 4C/ O BASE / 9423230
Push button flush type (Red) with carrier
Push button flush type (Green) with carrier
Contact element 1 NO green Cat Rb2-BE101
Terminal block fuse type elmex model=KUDF4
VCB function spring charging motor, 120W 24V DC, Type:PMR5
Tripping coil
Closing coil
Micro limit switch, Model-D-38, rating-16A, 1 HP, 125/250V AC
Aux switch 6 NO + 6 NC
Pressure switch/ 33210204-01
10A, 230V AC 2 pole with on/off toggle switch, CAT ; Kaycee
Material and labour in repair GI pipe Light grade with all fittings complete laid in trenches/fixed on pole with suitable clamp all as specified for 80 mm bore of pipe for protection of UG cable.
Material and labour in repair for disc insulator porcelain vitreous brown 145 mm height & 225 mm dia ball and socket type two in series assembly with cast aluminium 4 U bolt tension hardware and tension clamps for conductors working pressure HT 22 KV complete all as specified and directed. Make :- INSUC/ BIC/ Durable.
Material and labour in repair for pin insulator porcelain vitreous brown insulator including one galvanised mild steel spindle two galvanised iron washers and one galvanised iron nut for 22000 volts grade 205 mm dia & 215 mm height, complete all as specified and directed. Make :- INSUC/BIC/Durable
- ditto- as per srl item No. 122, but post type insulator.
Supply and install HT 22 KV Gang Operated Air Break Switch, horizantal 3 insulator type complete with handle, pipe and all mechanical fittings 400 Amps double break rotating type with earth switch. Make:- Atlas/Pactil /ABB / Crompton
Material and labour for overhauling i.e greasing, cleaning of GOD and adjustment of its operation complete all as specified and directed by Engineer-in-Charge.
Material and labour for fixed type top contact for DO fuse units in replacement complete all as specified and directed. Make:- Pactil/ MEI/ ATLAS
Material and labour for fixed type bottom contact for DO fuse units in replacement complete all as specified and directed. Make:- Pactil/ MEI/ ATLAS
Supply and fix following spares of vertical type GOD 22 KV grade, 200 Amps rating of make - M/s Pactil/ ATLAS/ MEI in position as in repairs including testing after repairs:- (a). Male contact
(b). Female contact
(c). Tinned copper flexible jumper
(d). MS Jumper carrier
(e). Back connector plate
Supply and install HT 22 KV, 200 Amp outdoor type gang operated single break switch Tilting type vertical mounting consisting of hot dip galvanised channel iron base having 2 Nos 22 KV Post type insulator in stack and 3 stack per phase copper or copper alloy high pressure heavily tinned contacts plated MS arcing horns capable of breaking the magnetizing current complete with horizontal connecting square bar, GI pipe as down rod levers coupling & operating handle with locking arrangement. Make:- Pactil/ ATLAS/ Crompton
Supply and install drop out lift OFF HT 22 KV, 200 Amps fuse link consisting of channel iron base having 2 Nos 22 KV post type insulators in stack & 2 stack per phase complete with fuse carrier of SRBP tube with heavily tinned non ferrous metal parts and spring loaded phosphor bronze contact complete manufactured as per IS 9385 complete all as specified and directed. Make:- Pactil/ Crompton/ ATLAS
Material and labour in repair Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp complete all as specified and directed (Make BHEL/ELPRO/CROMPTON GREAVES)
Material and labour in repairs outdoor type, oil cooled, single phase, single pole wound primary, live tank OIP insulated current transformer dual core having ratio 120-60/1-1A (ratio change by means of tap on secondary winding) insulation Class A, burden 15 VA Class I for metering & 5P-10 for protection complete all as specified and directed. Make:- Pragati Electricals/ ATLAS/ Kappa Electricals
Supply and fix following spare parts of HT 22 KV SF-6, 800 Amps outdoor type circuit breaker controlled by indoor panel : Limit switch with Bracket
operation Counter Assemblly
Carbon Brushes With Cap
Emery Pads
Auxiliary swicth stack 5 NO+5NC
Door Gasket
chemistic
compound Gauge
compound Gauge(small)
Anabond 680 (1 tbue=100gms)
Local Remote sitwch 3 Pole
Trip Coil (single) -30V Dc
Close Coil-30V DC
Set of Circlips,Split Pins ,Dowel Pins etc
Darina Grease(1 Pkt= 250 Gm)
Torsion Spring Right
Torsion Spring Left
TNC switch 2 Pole
DC Contactor
space heater 80 w
Thermostat
Spring Charging Motor
SF-6 Gas filling device with gas filling
Anti pumping device
Material and labour in repairs 'T' hard connector made of cast aluminium suitable for ACSR conductor complete all as specified and directed.
Material and labour in repairs 4 'U' bolt hardware made of cast aluminium suitable for end disc insulator complete all as specified and directed.
Material and labour in replacemnt Bi-metallic aluminium straight connector for C.T. 32mm x DOG conductor complete all as specified and directed.
Material and labour in replacemnt Bi-metallic aluminium straight connectro for C.T. 12mm x DOG conductor complete all as specified and directed.
Material and labour in repairs brass spindle with 32mm dia for CT's with Universal bushing complete all as specified and directed.
Supply and laying in repairs synthetic Rubber insulated mats 3 mm thick for voltage upto 33 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and directed(Make :- ATLAS /Jyoti)
Disconnecting HT 22 KV grade XLPE cable of any size from structure/pole/transformer for finding fault by computer aided fault finding machine and locating exact location by thumping and necessary earth work to expose faulty cable piece and cutting faulty cable and testing remaining cable with High voltage tester to with stand the cable as normal working pressure HT 22 KV complete all as specified and directed by Engineer-in-Charge. Note :- Excavation and earth work and Material and labour for joints shall be measured and paid udnder relevant Item of schedule separately.
Labour only for upkeep of HT out door structure by removing grass, shrubs, trimming branches of trees near to structure removing cleaning, screening for mud etc and relaying of same stone aggregate complete all as specified and directed.
Supply and fix Auxiliary High speed Master trip ralay, Type AVAJH13 , contact 3 NO+2 NC HR , Auxiloiary Voltage : 24 VDC or 110 VDC Make Ashida
Supply and fix 3 phase Over Current + Earth Fault Relay with High Set & RS -485 Port with IDMT and definite time characteritics,password protection, Aux supply (V) of 24-240V, AC/DC, Output contacts 4 No L&T Make - CAT Part No.- MC61CNX4000 Model - MC61Cnx.
Preparation of old painted surface including removing old paint, rust, dust, oil, grease and any other foreign deposits by paint removers or burning off by blow lamps and cleaning with scrapers and chemicals for removal of rust for any number of coats, any width or girth & Material and labour application of aluminium paint one coat for 6 pole stucture (steel or tubular)/ channels/angles /GODs etc. all as specified and directed.
(a) - ditto- as per srl item No. 171, but 4 pole stucture
(b) - ditto- as per srl item No. 171, but 2 pole stucture
Supply, installation, testing and commissioning in repair HT 22 KV out door type, IP-66 protection factory fabricated feeder pillar box made out of 3.25 mm thick cold rolled MS sheet steel with double door and locking arrangement, duly painted with anti corrosive high quality post office red colour, suitable for 22 KV, 3 Phase, 50 Hz, 630 Amps, AC system to loop one incoming and one outgoing 3 x 120 Sqmm XLPE cable with all accessories complete comprising the following specifications :- (a) The HT feeder pillar shall have front and rear compartments, front compartment shall be connecting the terminals of cables and rear for terminations, backelite sheet 12mm thick shall provide for separation cable termination at front. (b) Adequate ventilation by means of louvers with wire mesh on both sides and at the top and bottom of feeder pillars. (c) Asbestos sheets fo at least 6mm thick shall be provided on inside of all doors. (d) Enamelled name plate mentioning name of manufacturer, serial number and date of installation shall be displayed on front door.(e) Two Nos of earthing bolts shall be provided with the cubicle at front and rear side of feeder pillar. (f) Cable entry shall be from rear side of pillar. Removable gland plate of 10 SWG MS sheet shall be provided. Cable chamber shall be provided with perforated metal sheet separate for each chamber. (g) Teh set of bus bar 630 Amps rated shall be made up of electrlytic grade copper and provided with heat shrinkable PVC sleeve for RYB codes. (h) The insulating material used shall be Epoxy type insulator with uniform equally spaced rings, suitable for 33 KV class insulation. Make :- M/s Super Panel/Hupen/Switch Build Engg India Pvt Ltd/ Pune switch gears/SV power system Mumbai.
Supply and fix following spares of Horizantal type GOD 22 KV grade, 400 Amps rating of make - M/s Pactil/ ATLAS/ in position as in repairs including testing after repairs:- (a). Male contact
(b). Female contact
(c). Copper rod/Plate
(d) Copper Bure conductor of 4 SWG
(e) Copper Bure conductor of 6 SWG
Material and labour for Do fuse Element stranded silver/Tin coated copper wire soldered joint with ferrule and fire resistant tube type rating 2.5 Amps complete all as specified.
- ditto- as per srl item No. 180, but rating 5 Amps
- ditto- as per srl item No. 180, but rating 10 Amps
- ditto- as per srl item No. 180, but rating 15 Amps
- ditto- as per srl item No. 180, but rating 20 Amps
- ditto- as per srl item No. 180, but rating 30 Amps
- ditto- as per srl item No. 180, but rating 40 Amps
- ditto- as per srl item No. 180, but rating 60 Amps
- ditto- as per srl item No. 180, but rating 80 Amps
- ditto- as per srl item No. 180, but rating 100 Amps
Supply and filling in layers n.exc 25cm thick with 40mm graded coarse aggregates in structures complete all as specified and directed.
Material and labour for fixing of GI Nut and Bolts with washer of different sizes in HT structures complete all as specified and directed.
Material and labour for self bonding electrical HT tape of size 1.9cmX9.15mX0.076cm for cable joints, transformers, HT structure joints. Make : 3M
Material and labour for HT lugs in the rectification of HT faults of size 95 Sqmm
Material and labour for HT lugs in the rectification of HT faults of size 120 Sqmm
Material and labour for HT lugs in the rectification of HT faults of size 150 Sqmm
Material and labour for HT lugs in the rectification of HT faults of size 185 Sqmm
Material and labour for HT lugs in the rectification of HT faults of size 240 Sqmm
Material and labour for Petroleum Jelly in HT Nut bolt joints, T- joints, U joints in CTs and PTs on the HT structure.
Supply only for HT gloves for 22 KV HT line.
Dismantling wrought iron or mild steel work of any description not otherwise provided complete all as specifedand directed
Dismantling posts or struts (Wood, steel or RCC) any section, including taking out embedded portion and making good disturbed ground (posts embedded in in concrete, brick work, masonry work, etc. )
Dismantling fencing wire mesh any type complete all as specified and as directed
Demolition of cement concrete (unreinforced) in ground floors and paving not exceeding 15 cm thickness (below or above ground level) complete all as specified and directed.
Supply and fix, steel work as in tubular trusses including special shaped washer etc complete using ERW or induction butt welded tubes confirming to IS 1161 1979 grade St 240 complete all specified and directed.
S&F for rolled sections of FE 410W (Gde-E-250)as in main and cross beams, hip and jack rafters; purlins where connected to common rafters and running rails and guides for sliding doors; fixed with angle cleats , Steel Door frame and shutter or other connecting plates complete all specified and directed.
Supply & fixing of framed work such as grills, gratings, cooler stands etc., with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work conforming to Fe 290 Gde E-165 incl necessary fixing to walls as directed.
Supply and Fix MS plate Fe 410-W (Gde E-250 quality A) (Plane/Chequered) 5 mm and over as open drain covers with 02 Nos of 150mm handle in each plate etc complete all as specified and directed by Engr-in-Charge.
Excavating in post holes (or similar holes) each n exc 0.5 cum, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25cm, watering, and removing surplus soil to a distance n exc 50 m and making good surface hard or dence soil complete all as specified and directed
Supply and fix, posts and struts in fencing including cutting tops to shape as directed, drilling holes,notching for wire mesh, etc.; flat iron fillets( for securing wire mesh etc.) including all necessary drilling, bolting or riviting, etc., and similar work conforming to Fe-290 Gde E-165 complete all as specified and directed
Supply and Fix mild steel screw bolts (machine made) with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square but, length of boltexc 5cm but n exc 10cmlong.(Diameter of neck in 11 to 15 mm) complete all as specified and directed
Supply and fix, Pre- painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws including dismanlting of old Sheet as specified etc complete all as specified and directed.
Supply and fix, Pre-painted galvalume aluminum zinc coating GI based Plain steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified etc complete all as specified and directed.
Material and labour, Preparation of new previously untreated steel and iron surfaces of any description not other wise described over 10 centimetre width or girth and applying two coats of synthetic enamel paint over a coat of red oxide zinc chrome complete all as specified and as directed.
Supply and Fix, mild steel security chain link fencing 60mmx60mm with PVC coated mesh made out of 3.0 mm dia MS wire and 1.00mm thick PVC Complete all as specfied and directed.
Taking down and refixing of chain link fencing in same position after replacing of damage of fencing post complete all as specified and directed by Engineer–in-Charge
Taking down existing angle iron from wall embadded in PCC and refixing in the same opening/position complete all as specified and as directed by Engr-in-Charge.
Material and labour, Preparation of new previously untreated steel and iron surfaces of any description not other wise described over 10 centimetre width or girth and applying two coats of synthetic enamel paint over a coat of red oxide zinc chrome complete all as specified and as directed.
Material and labour for cement concrete type D-2 1:4:8 using 40mm graded crushed stone aggregate as in foundation, filling and mass concrete etc as specified and directed.
Material and labour, chequered cement concrete tile 30cmX30cmX 20 to 25mm thick set jointed and pointed in neat cement siurry in floor with grey cement and pig ments over 20mm thick screed bed or bedding layer of CM (1:4) including dismentling of old tiles complete all as specified and as directed.
Material and labour, for Machine pressed precast concrete interlocking paver block any shape and size confirming to IS 15658-2006 of 80 mm thickness M-40 Grade including dismentling of old tiles complete all as specified & directed .
Material and labour, for Machine pressed precast concrete interlocking paver block any shape and size confirming to IS 15658-2006 of 60 mm thickness M-35 Grade including dismentling of old tiles complete all as specified & directed .
Taking down old paver blocks any shape, size and thickness from the existing surface and refixing at the same place after levelling the ground by using sand caushion for maintaing camber and slope all as per directed by Engr-In Charge Note:- Sand Cushion will be paid separately.
Material and labour for sand cushioning for laying interlocking paver block complete all as specified and directed.
Supply and fix, green marble 18-20 mm thick machine cut, jointing and pointing with white cement slurry including 20mm thick screed bed or bedding layer of mortar in CM 1:6 including dismentling of oldstone slab / tiles complete all as specified and directed.
Material and labour, 75 mm thick cement concrete type C-1 1:3:6 using 20mm graded crushed stone aggregate as in plinth protection finished fair even laid in bays n.exc 2m in length and joints filled with bitumen mastic 1:3 complete all as specified and directed
Material and labour, 100mm thick cement concrete type B-2 1:2:4 using 40mm graded crushed stone aggregate as in path/floor finished fair even and smooth without using extra cement, laid in alternate panels of size not exc 4 sqm each including bitumen filling in joints complete all as specified and as directed by Engr-in-Charge.
Taking down cement plaster on brick or stone walls, etc., including raking out joints, hacking for key, scrubbing down with water, etc.
Material and labour, pre-cast cement concrete block masonry with solid blocks, exc. 10 cm in width in type B1 (1:2:4) (20mm graged stone aggregate )and setting in mortar (1:6) including demolition of old PCC Block complete all as specified and as directed
Material and labour, brickwork with sub class 'B' bricks , straight or curved on plan exc 6m mean raidus built in cement mortar 1:6 including demolition of old brick work complete all as specified and directed
Material and labour, rendering 15 mm thick in CM 1:4 on fair faces of brick/concrete surfaces with two coats i.e (10 mm thick backing coat and 5mm thick finishing coat) , finished even and smooth complete all as specified and directed. (Note:- Item rate shall be include any height of Bldgs for scafolding as all arrangement.)
Material and labour, rendering 10 mm thick in CM 1:6 on fair faces of brick work or concrete surfaces finished even and smooth complete all as specified. (Note:- Item rate shall be include any height of Bldgs for scafolding as all arrangement.)
Material and labour, PCC (1:2:4) type B0 (using 12.5mm graded aggregate) in coping, bed black etc including nessesary form work complete all as specified and directed.
Supply and fix, Steel rolling shutters, with out ball bearing, thickness of laths 1.00mm as specified including top cover, anchoring rod, hasp and staple and erected in position as indicated,complete: push pull or manual type including taking down of old Shutter complete all as specified and directed by Engr-in-Charge
Material and labour, preparing new or previously untreated steel surface of any decription over 10cm in width or girth and applying 2 coats of aluminium paint over one coat of red oxide primer complete all as specified and directed.
Material and labour, preparing old painted steel surface of any decription over 10cm in width or girth and applying one coats of aluminium paint complete all as specified and directed
Please Enable Macros to View BoQ information
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.09 MB
SOC.pdf
Additional Documents • 0.38 MB
BOQ_846134.xls
BOQ • 0.51 MB
Tenderpages.pdf
Tender Documents • 0.42 MB
Download all tender documents and submit your bid