| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.2 LAccepted-AOC | L1 | Accepted-AOC Bidder quoted lowest bid value | |
| 2 | L2₹21.0 L+₹46,139 (2.25%)Rejected-AOC 179 143 1 INDA NEAR SHAKTI BHAVAN KHARAGPUR 721305 | KHARAGPUR | PASCHIM MIDNAPORE | WEST BENGAL | 721305 | L2 | Rejected-AOC Bidder quoted highest bid value |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
13 Sept 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE (AF) KALAIKUNDA
CWE (AF) KALAIKUNDA, KALAIKUNDA AIR FIELD POST, DIST-WEST MEDINIPORE, WB, 721303
REPAIRS MAINT OF HT CABLES, REPAIR TO VCBs, RMUs, SWITCH GEARS, HT FEEDERS AND OTHER ALLIED WORKS
2022_MES_545526_1
8606/KKD/03/E8
Open Tender
Electrical and Maintenance Works
Item Rate
150 days
AF STATION KALAIKUNDA
Class E, Category b (ii)
2 documents required · 2 mandatory
₹500
GE (AF) KALAIKUNDA
₹40,000
Yes
28 Sept 2022
16 Aug 2022
15 Sept 2022
16 Aug 2022
13 Sept 2022
30 Aug 2022
17 Aug 2022 - 23 Aug 2022
Amount
Material & labour for servicing/overhauling , Calibration and decarbonising of 11 KV PIX panel with breaker + Relay ) and setting of Relay parameters VCB of capacity 800/630 Amps, indoor/out door type , taking shut down from 33 KV MRS and taking out breaker from VCB panel and checking of auxillary supply and control voltage, Physical checking of gears, checking of fixed and moving contacts, checking of close and trip coil, cleaning the gear thoroughly, lubricating the gear if necessary, applying grease on required parts,checking of spring charging motor/mechanism, checking of manual spring charging, physical check of wear and tear if any and rectification of the same, physical checking of epoxy housing, checking of control circuit and tighten the cinnections if any. Special attention is to be given for adjustment of the part/ assembly responsible for lower/raise and locking of the trolley including replacement of un-serviceable spares, greasing of revolving assembly and movable parts in VCB chamber, checking of all DC supply system, electrical circuit to make it functional complete all as specified and directed . Make of VCB`s of which Serviceing and repairing has to be carry out is Schneider/Crompton/Alstom / Kirloskar Note :- (i) : Spare parts/components required for replacement of above VCB`s shall be measured and paid separately. (ii) Unit rate quoted against this item shall also include labour required for fixing of replaced items (iii) For item No. 2 to 27 below, fixing charges of items are considered and included in item No 1 herein. (iv) Location of VCB`s is in Tech and Domestic area at AF stn KKD and DDK Range.
Supply only micom P 127 Relay for Schneider VCB and as existing model in Cromton and Kisloskar make VCB`s. complete al as specified and as diretced. Make :- Scneider
Supply only Isolating contact 630A Complete all as specified and as directed. Make - Schneider Cat No - MVIG00134-01 of Schneider Make VCB or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Supply only Vacuum Interrupter Complete all as specified and as directed. Make - Schneider Cat No. VG2 Cat No - DRCVG2002-01 for Schneider Make VCB or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Supply only Closing coil 110V DC Complete all as specified and as directed. Make - Schneider Cat No. ECO27SN117900FN for Schneider Make VCB or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Supply only Triping Coil 110V DC Complete all as specified and as directed. Make - Schneider Cat No. ECO27SOG83800FN for Schneider Make VCB or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Supply only Breaker auxillary swtich 6 No + 6NC Complete all as specified and as directed. Make - Schneider Cat No -MVIE00114-01 for Schneider Make VCB or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Supply only Motor cut off switch Complete all as specified and as directed. Make - Schneider Cat No - EVU27S0307600NA for Schneider Make VCB or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Supply only Trip Fork Linkage assembly Complete all as specified and as directed. Make - Schneider Cat No -MVIE00072-01 for Schneider Make VCB or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Supply only Trip prop support Assembly. Complete all as specified and as directed. Make - Schneider Cat no- MVIE00023-01 for Schneider Make VCB or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Supply only Charging pawl complete all as specified and as directed. Make - Schneider Cat no MST27SSD28500BL_S for Schneider Make VCB or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Supply only Buffer for spring complete all as specified and as directed. Make - Schneider Cat no-MVIE00060-01 for Schneider Make VCB or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Supply only Over ride stop complete all as specified and as directed. Make - Schneider Cat no- MVIE00013-09 for Schneider Make VCB or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Supply only Over ride stop pin complete all as specified and as directed. Make - Schneider Cat no- MVIE00232-01 for Schneider Make VCB or Equivalent model in Crompton /Kirloskar for Crompton /Kirloskar Make VCB`s
Supply only limit switch 4 terminal 10 Amps comlete all as specified and directed .
Supply only R Phase Bus Bar Spout Complete all as specified and as directed. Make - Schneider Cat no- MVIF00072-02 for Schneider Make VCB or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Supply only Y Phase Bus Bar Spout complete all as specified and as directed. Make - Schneider Cat no- MVIF00070-02 for Schneider Make VCB or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Supply only B Phase Bus Bar Spout complete all as specified and as directed. Make - Schneider Cat no- MVIF00066-02 for Schneider Make VCB or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Supply only housing for VCB complete all as specified and directed . Make: Schneider Make VCB or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Supply only Top stem complete all as specified and directed . Make: Schneider Make VCB or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Supply only Bottom stem complete all as specified and directed . Make: Schneider Make VCB or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Supply only Spring charging motor 110 volt complete all as specified and directed . Make: Schneider Make VCB, Cat No. VDRE00100-01 or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Supply only TNC switch complete all as specified and directed . Make: Schneider make VCB or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Supply only HRC fuse 4 Amp complete all as specified and directed .
Supply only HRC fuse 10 Amp complete all as specified and directed .
Supply only HRC fuse 16 Amp complete all as specified and directed .
Supply only Indicator (LED type) complete all as specified and directed . Make: Schneider make VCB or Equivalent model in Crompton /Kirloskar/ Alstom for Crompton /Kirloskar/ Alstom Make VCB`s.
Material & labour for servicing/overhauling , Calibration and decorbonising of 33/11 KV, out door PCVCB and control panel (RTCC Panel) for 1 MVA transformer , replacement of un-serviceable spares, and serviceability check from remote operation, checking of all DC supply system, electrical circuit including connection of control cables to make it functional in all respect all as specified and directed . Make of control panel and RTCC : Andrew Yule. Note :- (i) Spare parts/components required to replaced of above control panel shall be measured and paid separately under relevant items. (ii) Unit rate quoted against this item shall also include labour required for fixing of replaced items, making the control panel serviceable and making all electrical connecto,. (iii) For item No. 29 to 30 below, fixing charges of items are considered and included in item No 28 herein.
Supply only closing coil (control) assembly 35 volt DC complete all as specified and directed
Supply only triping coil (control) assembly 35 volt DC complete all as specified and directed
Supply and spray Moisture absorbing spray WD-40 on electric terminals of VCB Breaker and panel and allied equipment complete all as specified and directed
Supply replacement and topping up new Transformer oil EHV grade as per IS 335 of 1993 Part II having die electric strength not less than 40 KV in the Transformers at various location complete all as specified and direct by EIC. Make of Transformer oil : Transol/Power oil/any brand of Indian oil corporation). Note : Transformer oil should be heated and should having dielectic strength 60 KV (ii) Transformer oil shall be bring in sealed barrel having proper test certificate from manufacturer.
Material & labour in repair for Filteration and dehydration of HV grade transformer oil of distribution and Power transformer of out door type of 11/.433 KV, 100 KVA to 750 KVA and Power transformer of 33/11 KV 1000KVA to 4000KVA min three cycle to achive die elctric strength of 40 KV to 60KV for 1 Minute at 4 mm gap as per relevent IS with portable filteration plant, testing the oil for die elctric strength, break down voltage before filteration and after filteration complete all as specified and directed . Note : Filteration to be done by Dehydration machine till the desired level of dielectric strength of tranformer oil comes to 60 KV . (ii) The contractor will test the dielectric strength of oil of each Tranformer & voltage stabilizer before starting dehydration & filteration and after completion of dehydration & filteration process and he will submit a record of same. (iii) Each sample of oil will be tested with a transformer oil test machine at site in presence of concerned JE's/Engr-in-charge and test result will be submitted accordingly). (iv) Centrifugal machine with all T&P and Testing Machine , oil required shall be arranged by contractor. (v) Oil required for topping up the transformer oil will be measured and paid seperately in relvent item.
Material & labour for rectifying of transformer oil leakage problem from LT termernial, taking shut down, tracing out the cause of leakage , removing cable, draining out oil, removing of transformer top cover, replacement of seal, recitifying oil leakge, changing all gaskets, tightening of transformer core, tightening / replaceing of bushing/stud, refilling the oil, replacement of top cover gasket, reconnecting cables etc and testing and commissioning complete all as specified and directed up to the entire satisfication of Engr in charge/GE.
Material & labour for Cable jointing kit for 11 KV (Earthed) grade cable for straight through Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 35 Sqmm all as specified and directed including taking down unsv one.
Material & labour for Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm all as specified and directed including taking down unsv one.
Material & labour for Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm- 185 Sqmm all as specified and directed including taking down unsv one.
Material & labour for Cable jointing kit for 11 KV (Earthed) grade cable for indoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 Sqmm- 95 Sqmm all as specified and directed including taking down unsv one.
Material & labour for Cable jointing kit for 11 KV (Earthed) grade cable for indoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm- 185 Sqmm all as specified and directed including taking down unsv one.
Material & labour for Cable jointing kit for 11 KV (Earthed) grade cable for out door end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 Sqmm- 95 Sqmm all as specified and directed including taking down unsv one.
Material & labour for Cable jointing kit for 33 KV (Earthed) grade cable for out door end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 Sqmm- 240 sqmm Sqmm all as specified and directed including taking down unsv one.
Material & labour for Cable jointing kit for 33 KV (Earthed) grade cable for indoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 Sqmm- 240 Sqmm all as specified and directed including taking down unsv one.
Material & labour for detecting of fault in 11KV (E) HT cable of any size(within 1-3 km length) , 3 core laid in trenches/ducts with the help of electronic fault locating machine comprising of surge generator pulse, echo fault locator with high frequency distance calculator etc and exposing the cable fault, removal of deteriorated portion of cable, treating the cable including making it ready for jointing work complete all as directed . Note: - (i) The quoted rate shall deemed to include for the cost of earthwork excavation as required. (ii) Cable if replaced & Jointing kit shall be measured & paid separately. (iii) As the work is releated to maintenance, the work of fault detection has to be carry out on Priority and on requirement basis as on occurance of fault within 24 hrs so as to rectify the fault and to restore the electric supply of station. If contractor delay the job, necessary penalty at the rate of Rs 1000.00 per hrs (after 24 hrs) will be impose on contractor.
Supply, Install, testing and commissioning of 33 KV single phase outdoor type oil cooled ,dead tank type CT of ratio 160-80/5-5-1 Amp accuracy class 0.5 for metering equipment of burden 15 VA as per IS:2705 including connection CT terminal to control panel through control cable and taking down unsv one complete all as specified and directed . Note:(i) Control cable if required will be paid under relevant item. (ii) Contractor has to make all arrangement for mounting/ placing CT`s in existing system without any extra cost.
Supply, install, testing and commissioning 33 KV single phase outdoor type oil cooled,dead tank type PT of ratio 33 KV /√3 : /110V/√3-110V/√3 ,accuracy class 0.5, Burden 150 VA conforming to IS:3156 including connection PT terminal to control panel through conntrol cable and taking down unsv one complete all as specified and directed. Note: Note:(i) Control cable if required will be paid under relevant item. (ii) Contractor has to make all arrangement for mounting/ placing PT`s in existing system without any extra cost.
Materila & labour for fixing flexible control cable PVC insulated 4 core of size 2.5 sqmm FR PVC sheathed multistraded, cable with bright annealed electrolytic bare copper conductor for voltage grade upto 1100 Volt for connecting control panel to VCB including taking down unsv one complete all as specified and directed.
Material & labour for fixing flexible control cable PVC insulated 10 core of size 2.5 sqmm FR PVC sheathed multistraded cable with bright annealed electrolytic bare copper conductor for voltage grade upto 1100 Volt for connecting control panel to VCB including taking down unsv one complete all as specified and directed.
Materila & labour for fixing flexible control cable PVC insulated 8 core of size 2.5 sqmm FR PVC sheathed multistraded cable with bright annealed electrolytic bare copper conductor for voltage grade upto 1100 Volt for connecting control panel to VCB including taking down unsv one complete all as specified and directed.
Taking out old unserviceable HT under ground cable of any size and rating complete all as specified and directed.
Supply, laying, testing and commencing of HT cable XLPE insulated screnned PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts (Earth grade) , of size 95 Sq mm 3 core complete all as specified and directed.
Material & labour for taking out old unserviceable defective HT bushings in repairs on site from distribution transformers outdoor /indoor type of 11/0.433 KV, 100 KVA to 750 KVA and Supply and fix porcelain bushing with brass studs, nuts and washers connecting to winding, testing and commissioning complete all as specified an directed .
Material & labour for taking out old unserviceable defective LT bushings in repairs on site from distribution transformers outdoor /indoor type of 11/0.433 KV, 100 KVA to 400 KVA and Supply and fix porcelain bushing with brass studs, nuts and washers connecting to winding, testing and commissioning complete all as specified an directed.
Taking out saturated silica gel from existing breather and Supply and replace silica gel crystal 3/4 mesh, 6 mm to 9mm, (Blue to Pink to white) in breather of transformers complete all as specified and directed .
Taking out old unserviceable breather and Supply and replace silica gel breather assy 250 gms , made up of aluminium TOP ,Powder coated, Transaparent Centre Portion made of Polycarbonate of size 80 mm x 80 mm, Nitirle rubber O ring connection1/2 " BSP thread, filled with Silica Gel Blue (including silica gel crystal) suitable for transformer of capacity 100 KVA to 200 KVA complete all as specified and directed .
Taking out old unserviceable breather and Supply and replace silica gel breather assy 500 gms , made up of aluminium TOP, Powder coated, Transaparent Centre Portion made of Polycarbonate of size 90 mm x 140 mm, Nitirle rubber O ring connection1/2 " BSP or 3/4 " thread, filled with Silica Gel Blue (including silica gel crystal) suitable for transformer of capacity 250 KVA to 630 KVA complete all as specified and directed .
Taking out old unserviceable breather and Supply and replace silica gel breather 1500 gms , made up of aluminium TOP, Powder coated, Transaparent Centre Portion made of Polycarbonate of size, Nitirle rubber O ring connection1/2 " BSP or 3/4 " thread, filled with Silica Gel Blue (including silica gel crystal) suitable for transformer of capacity 1000 KVA complete all as specified and directed
M&L for laying 100 mm bore GI pipe, light grade with all fittings, in crossing road/path and in pole up to junction box including necessary clamping etc. complete all as specified and as directed .(Note : Boring under road/path will be measured and paid under respective item )
M&L for GI pipe light grade 80mm bore dia with all fittings to be laid in trenches or in floors, complete including taking down rusted one all as specified and as directed.
M&L for GI pipe light grade 50mm bore dia with all fittings to be laid in trenches or in floors, complete including taking down rusted one complete all as specified and as directed.
Supply and replace in repair Pin Insulator porcelain vitreous, white brown or green , 150 mm height, 150 mm dia including one galvanised mild steel spindle, two galvanised washers and one galvanised iron nut for conductor working pressure 11000 volt grade complete all as specified and directed including taking down old unserviceable.
Supply and replace in repair Post Pin Insulator porcelain vitreous, white brown or green including one galvanised mild steel spindle, two galvanised washers and one galvanised iron nut for conductor working pressure 33000 volt grade complete all as specified and directed including taking down old unserviceable .
Excavation in trenches not exceeding 1.50 m wide and n.exc1.5 m in depth for foundation of poles, cable etc, not exc 10 sqm on plan and getting out in soft/loose soil including taking out brick protection etc complete all as specified and directed. Note :Excavation for laying of cable to be done manualy carefully without distrubing existing cable or water pipe lines. If any damaged occured to exiting cable and pipe line during excavation contractor has to repair it with in time limit without any extra cost. If contractor delayed in repairing Panality @ of 500/- per hour to be charghed if repairing is not carry out in 12 hours. In this GE's decision will be full and final.
Returning, filling in, of soil including spreading leveling, watering and well ramming in layers not exceeding 25 cm complete all as specified and directed .
Removing excavated material to a distance n.exc 50M and deposited/ spreaded where directed at a level n. exc 1.5 M above the starting point complete all as specified and as directed .
Materials and labour for sand filling around the cable with approved quality coarse sand for sand cushioning of Under ground cable including spreading and punning down to 18 cm thickness complete all as specified and as directed.(Compacted thickness shall be measured)
Supply & Fixing burnt clay fly ash bricks old size designation 75 (kg/cm2) in trenches on cable as cable protection across the length of the cable (width wise) complete all as specified and as directed.
Boring under roads with mechanical arrangement with 80 mm dia GI tubing without disturbing the top surface of the road for passing the cable across the road complete all as specified and directed. Note : (i) All the precaution to be taken by the contractor before drilling the bore. The contractor has to take plan of existing cables any type and pipe line in existing area before drilling the bore. (ii) Any damage to existing cables any type and pipe line in the way of drilling the bore will be repaired and make good by the contractor. No extra cost will be paid in this account. (iii) Contractor has to get the survey of route, length and depth for boring before quoting the rate.
M&L for Maint and cleaning of surrounding area of MRS 33 KV by cutting seasonal grass, bushes etc,including spreading of strong herbicides in order to stop the fast growth of grass/bushes around the feeder pillars and panels by employing skilled mazdoor including using own T&P as required to do the job and taking all precaution while men on working in sub station being dange zone all as specified and directed by Engr-in-charge. Note : As vegitation growth is very high in the Stn due to humid climate, area cleaning of installations can be repeated and to be done twice/thrice as per the requirement and directed .
General Note: (i) Being Maintenace contract of HT supply system contractor has to attended all breakdown occur in system immediately. If contractor fails to attend the break down within 4 Hours suitable Panelity will imposed and @ Rs 500 Per hour will be charged from contractor. (ii) Being Maintenace contract of HT supply system contractor should not force for full site to be handover at one time for repair. Site will be given as per complaint received and reuirement for repairing of cables / fault detections etc. However maint of VCB`s and maint of 33 KV Grid to be done in planed manner with in time limit with minimum shut downs.
STAR ENTERPRISES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .