Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹14.1 LAdmitted-Finance 1853 2ND FLOOR BHAGIRATH PALACE SURYA BAZAR CHANDI CHOWK NORTH DELHI DELHI 110006 | NORTH | DELHI | 110006 | -38.88% | ₹14.1 L | L1 | Admitted-Finance |
| 2 | L2₹14.7 LAdmitted-Finance | -36.30% | ₹14.7 L | L2 | Admitted-Finance |
| 3 | L3₹15.2 LAdmitted-Finance A 6 MANDAWALI UNCHEPAR DELHI 110092 | SHAHDARA | DELHI | 110092 | -34.30% | ₹15.2 L | L3 | Admitted-Finance |
| 4 | L4₹16.7 LAdmitted-Finance GROUND FLOOR G 1154 A MANSAROVAR PARK SHAHDARA DELHI 110032 | SHAHDARA | DELHI | 110032 | -27.98% | ₹16.7 L | L4 | Admitted-Finance |
Tender Value
₹23.1 L
EMD Value
₹46,243
Closing Date
23 Feb 2026, 3:00 pmClosed
Executive Engineer (Elect.)
EE (E), PWD NES/ M-251, LM Bund Road, Ramesh Park
SH- Day to day operation and maintenance/repair of Electrical and Mechanical services and Electrical works at Circle M-21, M-23, Horticulture Div.-214, for Divn. M-211, Civil Divn. M-231,Electrical Divn. M-251)
2026_PWD_287059_1
100/EE(E)/PWD NES ED/2025-26
Open Tender
Electrical Works
365 days
Under Sub Div-I/M-2511
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹46,243
Yes
25 Feb 2026
16 Feb 2026
23 Feb 2026
16 Feb 2026
23 Feb 2026
16 Feb 2026
Sub Head-I (Opt. & Maint) Providing Services of Wireman cum Operator for attending day to day complaint related to all electrical installation in circle M-21, M-23, Horticulture Divn., in general shift on all working day excluding Sunday & holiday. Wireman cum operator -1 Nos. Khallasi -01 Nos. (9 AM to 5 PM)
Providing Services of Wireman cum Operator for attending day to day complaint related to all electrical installation in M-214, Road Divn, M-211, Civil Divn. M-231, Electrical Divn. M-251, M-213 in general shift on all working day excluding Sunday & holiday. Wireman cum operator -1 Nos. Khallasi -01 Nos. (9 AM to 5 PM)
Sub Head-II (E.I. Works)
Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/recessed steel/PVC conduit including dismantling as required. "GROUP C"
Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
3 x 1.5 sq. mm
3 x 4 sq. mm
3 x 6 sq. mm
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
5/6 A switch
3 pin 5/6 A socket outlet
15/16 A switch
6 pin 15/16 amp socket outlet
Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required.
6 Module (200 mmX75 mm)
12 Module (200 mmX150 mm)
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
100 Amp, 16 KA, TPMCCB
250 A,50KA,FPMCCB
125 A, 16 KA,TPMCCB
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
8 way , Double door
6 way , Double door
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
12 way (4 + 36), Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Double pole
Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% 53 DELHI SCHEDULE OF RATES (E&M)-2025 as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).
100 watt Watt LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 and <135 lm/Watt).
Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K(As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. completein all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)
18- 22 Watt (LED Batten light (System lumen efficacy ≥120 <135 lm/Watt))
Supplying, Installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) <19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)
36 watt LED Panel light 2x2 ft. (System lumen efficacy ≥120 <135 lm/Watt)
Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. (Brush Less Direct Current (BLDC) Fan without Remote)
1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum)
Supplying , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as perCPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature) .2.0 TR with 5 Star BEE Rating
Providing and fixing pole box of size 250mm X 200mm X 105mm with side openable hinged cover complete with two strip aluminium bus-bar of 100 amps capacity mounted on DMC bus support and 1 no. of SPMCB of 6 amps 'C' series capacity with din rail on the existing street light pole with the help of two nos. MS clamps of suitable size, including making hole to insert the cable and dismantling the worn out MS box etc. complete as required.
Supplying, Installation, testing and commissioning of 36 to 40 watt surface/recess mounted LED Luminaries of size 1200 mm (Length) x 300 mm (Width) housing made with white powder coated CRCA sheet metal and polycarbonate diffuser suitable for operation on 150 to 265V single phase A.C. supply, having system efficiency not less than 100 luman per watt. and colour temperature of 5700-6500 K, CRI >80 with APFC driver having power factor > 0.90, THD <20% and efficiency > 85% driver should be IC Compliant, with minimum 2.5 KV surge protection, LED life with L-70 criteria shall be not less than 50000 burning hours etc. including connection with 1.5 sq. mm. PVC insulated copper conductor FRLS cable with the help of 4 nos. fastener Hook, Clutch wire and sleeve etc. i/c making connections, testing, commissioning etc. complete as required.
Supplying and Fixing 300 mm 1400 rpm dia ventilation type Exhaust fan M.S type suitable for operation on 230 volt, ±10%, 50 Hz supply to fixed on wall i/c connection with 1.5 Sq.mm PVC single core cable i/c testing etc. as reqd.
Supplying & Laying of one Number Following size. XLPE insulated PVC outer sheathed armoured with galvanized round steel wire or strip cables with standard aluminium conductor suitable for rated voltage of 1.1 KV grade ISI marked confirming to IS 7098 / (Pt.-I)/88 with ammendment No. 1, suitable clamp in following manners.
3.5 x 35 sq. mm (On Surface) (Clamped upto 1 mm thick saddle)
3.5 x 50 sq. mm (On Surface) clamped with 25x3 mm MS flat Clamp)
Supplying and Fixing of Oil Filled Room Heater with 11fins, Power Consumption up to 2400 watt, Heating Modes: 3, Over Heat Protection: Yes, Efficient & Fast Heating etc. connection, testing etc. as reqd.
Supplying and Fixing of 2.5 MFD Capacitor for ceiling fans etc. connection, testing etc. as reqd.
Supplying of 15/16 Amp 3 Pin Power Top Plug etc. as reqd. at site.
Credit for old dismantle materials like Fitting, Cable, Fans, MCCB's, Gear Box, Rope Wire, switch and socket, pole box, Capacitor etc.
Associated Batten Fitting
Associated 2' x 2' Fitting
Associated Surface mounted fitting
Associated Fan
Associated Exhaust Fan
Associated Cable
Associated MCCB
Associated Switch & socket
Associated Pole box
Associated Capacitor
Associated AC
Associated Room Heater
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 3.84 MB
BOQ_380252.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid