Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹85.3 LAccepted-AOC SCF 15 HUDA COMPLEX 184 NEW IDC 124001 | ROHTAK | HARYANA | 124001 | L1 | Accepted-AOC L1 | |
| 2 | L2₹94.9 L+₹9.6 L (11.3%)Rejected-Finance 164 A 11 GALI NO 3 RISHI NAGAR KAITHAL 136027 | KAITHAL | HARYANA | 136027 | L2 | Rejected-Finance L2 | |
| 3 | L3₹97.0 L+₹11.7 L (13.7%)Rejected-Finance KHASRA NO 183 10 SHYAM VIHAR HISAR HISAR HARYANA 125001 | HISAR | HARYANA | 125001 | L3 | Rejected-Finance L3 | |
| 4 | L4₹1.1 Cr+₹19.8 L (23.2%)Rejected-Finance | L4 | Rejected-Finance L4 | |
| 5 | L5₹1.1 Cr+₹20.0 L (23.5%)Rejected-Finance 62 PINK ROSE COLONY KAIMARI ROAD 125001 | HISAR | HARYANA | 125001 | L5 | Rejected-Finance L5 |
Tender Value
₹82.5 L
EMD Value
₹1.7 L
Closing Date
14 Jun 2021, 5:00 pmClosed
Executive Engineer Elect. Division PWD B and R Br.
Executive Engineer Elect. Division PWD B and R Br., Hisar
CONSTRUCTION OF 50 BEDDED TO 100 BEDDED HOSPITAL AT NARNAUND IN DISTT. HISAR (PDG. ELECTRIC SUBSTATION ONLY).
2021_HRY_173652_1
D/Elect-GGN/Elect-HSR/100198
Open Tender
Electrical Works
Works
120 days
HISAR
Please refer Tender documents.
2 documents required · 2 mandatory
₹5,000
₹1.7 L
9 Dec 2021
1 Jun 2021
15 Jun 2021
1 Jun 2021
14 Jun 2021
1 Jun 2021
Amount
Moulded case Circuit breakers:(C) HSR 31.12 Supply and erection of moulded case circuit breakers on wall or on existing pedestal including bonding to earth and necessary connections. iii) 250 amp. 415 V , 35 KA 3-phase.
iv) 300 amp. to 400 amp. 415 V , 35 KA 3-phase.
v) 500 amp. to 600 amp. 415 V , 35 KA 3-phase.
Pipe Laying: (P) HSR 31.21 Supply and erection of pipe for wiring purposes including bends inspection boxes etc. where necessary and painting as required. vii) Galvanized iron pipe 65 mm dia on surface.
Supply and erection of PVC pipe of 6 kg. pressure laid 1 meter below ground level complete including digging refilling of the trench with jointing etc. xxx) PVC pipe 120 mm dia.
(Q) Earthing HSR 31.22 ) Earthing with GI earth pipe 4.5 m long and 40 mm dia with masonry enclosure on the top etc. as required
ii) Extra for using salt and charcoal / coke for pipe earth electrode as required.
iii) Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt ) complete as equired.
iv) Earthing with tinned copper earth plate 600 mm x 600 mm x 3 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) complete as required.
v) Extra for charcoal or coke and salt for G.I. Plate or copper plate earth electrode.
xi) Pdg. and fixing 25 mm x 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode as required .
xiv) Pdg. and fixing 25 mm x 5 mm copper strip on surface or in recess for connections etc. as required with all labour and material.
xv) Pdg. and fixing 25 mm x 5 mm G.I. Strip on surface or in recess for connections etc. as required with all labour and material.
xix) Supply and erection of 20 mm x 3 mm thick G.I. tape fixed with suitable G.I. staples of same size.
Under Ground Cables: (S) HSR 31.25 Supply and erection of under ground cable 1 meter below ground level covered with sand and bricks including necessary connections, digging and refilling of trenches. xxx) 120 Sq. mm 3.5 Core Ard.Cable .
xxxi) 150 Sq. mm 3.5 Core Ard. Cable .
xxxii) 185 Sq. mm 3.5 Core Ard. Cable .
xxxiii) 240 Sq. mm 3.5 Core Ard. Cable .
xxxv) 400 Sq. mm 3.5 Core Ard. Cable .
Supply and erection of under ground cable ,loose in existing pipe or trenches complete with necessary connections. HSR 31.26. xxix) 95 Sq. mm 3.5 Core Ard. Cable.
xxx) 120 Sq. mm 3.5 Core Ard. Cable.
xxxi) 150 Sq. mm 3.5 Core Ard. Cable.
xxxii) 185 Sq. mm 3.5 Core Ard. Cable .
xxxiii) 240 Sq. mm 3.5 Core Ard. Cable .
xxxv) 400 Sq. mm 3.5 Core Ard. Cable .
Supply and erection of suitable compression type brass cable glands for underground Cable. HSR 31.28 iv) 70 Sqmm to 95 Sqmm Cable 3 to 3.5 Core .
v) 120 Sqmm to 185 Sqmm Cable 3 to 3.5 Core
vi) 240 Sqmm Cable 3 to 3.5 Core .
vii) 300 Sq mm to 400 Sqmm Cable 3 to 3.5 Core .
Street Light. HSR 31.30 VI) Supply and erection of prestressed cement concrete pole as per IS : 1678-1960. \iii) 11 meters long 152 mm x 203 mm at top and 152 mm x 368 mm at bottom with working load of 360 Kg. buried 2.20 m in ground.
Miscellaneous (X) HSR 31.35xi) Supply and erection of cable route marker made of 50 cm long 10 mm dia M.S.rod welded / revitted at the top with 10 cm. Dia 5 mm thick G.I.plate inscribed with `cable' world on it , having a cross arm 30 cm. long of the same dia welded at the bottom , in existing trench 45 cm. below ground level .
Supply installation testing and commissioning of wall/ free standing floor mounting dust and vermin proof compartmentalized cubical panel made out of 2mm thick CRCA street, required hardware 3 mm thick bakelite sheet provided all along with bus bar and cable alley separating switches compartment and supporting suitable channel duly painted by 2 coat of zinc/ Red oxide primer followed by 2 coat of powder coating in gray or required shade after rising. The panel having PU/Neoprene rubber gasket of not less than 3 mm thickness separate detachable gland plate MS base channel hinged door with inter locking agreement for equipment / switch wear. Transparent acrylic sheet shall be provided in front of bus bar compartment to prevent direct access to bus bar bakelite sheet 3 mm thick for separately cable alley to BBC from switch chamber Extended solid copper bars upto cable alleys shall be provided for outgoing connection which shall be paid as extra items. Side walls and cable alley compartments shall be having bolted type doors with detachable extension type structure. the panel will be complete with control wiring (copper) and fuse protection ( only outer area on all sides shall be measured) HSR 31.63
Supplying and fixing of copper bus bar duly tinned by means of SMC / BMC type insulatter high tensile nuts and bolts spring washer fixing to same in existing pannel including bending, cutting in required shape and size and insulation with colour coding heat shrinkable PVC insulation complete in all respect. HSR 31.64
Supply and errection of double walled corrugated (DWC) HDPE pipe laid 1 meter below ground level including diging and refilling of earth including cost of suitable size socket / cuppler for HDPE pipe including the cost of the labour and material required to complete the job in all respect upto the entire satisfaction of Engineer-in-Charge of the work.HSR 31.67 ii) HDPE pipe 90/75 mm outer dia / inner dia
iii) HDPE pipe 145/123 mm outer dia / inner dia
S/E of XLPE (E) 11 KV HT aluminum conductor armoured cable ISI mark laid in existing pipe /trenches/surface with all labour and material including required to complete the job in all respect upto the entire satisfaction of the Engineer-in-charge of the work..HSR 31.71 iv) 95 sqmm 3 core XLPE cable
v) 120 sqmm 3 core XLPE cable
Supply and erection of indoor type end termination jointing box heat shrinkable type suitable for 70 to 120 sqmm 3 core 11 K.H.V.T. XPLE cable with epoxy cast bushing including making necessary connection with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. HSR 31.72 i) Suitable for 70 to 120 sqmm 3 core XLPE Cable
Supply and erection of outdoor type end termination jointing box heat shrinkable type suitable for 70 to 120 sqmm 3 core 11 K.H.V.T. XPLE cable with epoxy cast bushing including making necessary connection with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. HSR 31.73 ii) Suitable for 70 to 120 sqmm 3 core XLPE Cable
Non Schedule Items: Supply and erection of Rubber Mat 1mx2mx 12mm thick suitable for 11/33 KVA as per IS No. 15652C/M/L 3017739 as per approved by Chief Electrical inspector, Govt. of Haryana
Transformer: Supply, and erection, testing and commissioning of Oil Cooled transformer of 1250 KVA 11/0.433 KV 3 Phase 50 cycle copper wound Outdoor type up to the entire satisfaction of the engineer of the work as per detail specification given as under with required plate form & fancing etc. As per Latest BIS-1180-Level-2. Make. Voltamp/ Kirloskar/ Crompton/ ABB/ Siemens/ Alstom/ / Bhart Bijli NO load voltage ratio 11/0.433 KV No. of Phases = 3Type = Double wound core type copper wound,Cooling = ONANDuty = OutdoorVector Group/ISS-DYN-11/IS: 1180- Level -2.Tapping on HV Winding for HV Variation + 5% to - 10% in steps of 2.5%.Tape changer - Off circuitTemperature rise (oil/res. 0c to 50/55 C)Altitude up to 1000M above M.S.L.Frequency Cycle 50 Hz.Fitting / accessories provides = Off circuit tape changerExternally hand operatedOil conservator with filling hole & cap.Plain oil level gauge with minimum level marking.Thermometer pocket.4 Nos. plain roller Uni-directionalSilica-Gel-BreatherIst filling of oilDrain-cum-filter valveRating & Diagram plateTwo earthing terminalsLifting arrangementExploson ventAir release plugOil temperature indicator with alarm & trip indicator.Winding Temperature indicator with alarm & trip contact.TERMINATIONS : HV=3 pole single glands cable box suitable for reception of 1 No. 3 core up to to 120sqmm XPLE cable copper lugs/thimble.L.V. = 4 pole 3 glands cable boxes suitable for 3 Nos. 400 sqmm. 3.5 core PVC cable having extended copper bars of requisite capacity duly tinned from L.T. bushing for making connection with cable including cost of copper lugs and thimbles.L.V. Neutral suitable box for earthing provided.
Transformer: Supply, and erection, testing and commissioning of Oil Cooled transformer of 800 KVA 11/0.433 KV 3 Phase 50 cycle copper wound Outdoor type up to the entire satisfaction of the engineer of the work as per detail specification given as under with required plate form & fancing etc. As per Latest BIS-1180-Level-2. Make. Voltamp/ Kirloskar/ Crompton/ ABB/ Siemens/ Alstom/ Bhart Bijli. NO load voltage ratio 11/0.433 KV No. of Phases = 3Type = Double wound core type copper wound,Cooling = ONANDuty = Outdoor Vector Group/ISS-DYN-11/IS: 1180- Level -2. Tapping on HV Winding for HV Variation + 5% to - 10% in steps of 2.5%.Tape changer - Off circuit Temperature rise (oil/res. 0c to 50/55 C) Altitude up to 1000M above M.S.L.Frequency Cycle 50 Hz.Fitting / accessories provides = Off circuit tape changerExternally hand operatedOil conservator with filling hole & cap.Plain oil level gauge with minimum level marking.Thermometer pocket.4 Nos. plain roller Uni-directional Silica-Gel-BreatherIst filling of oil Drain-cum-filter valveRating & Diagram plate Two earthing terminalsLifting arrangementExploson vent Air release plugOil temperature indicator with alarm & trip indicator.Winding Temperature indicator with alarm & trip contact.TERMINATIONS : HV=3 pole single glands cable box suitable for reception of 1 No. 3 core up to to 120sqmm XPLE cable copper lugs/thimble.L.V. = 4 pole 3 glands cable boxes suitable for 3 Nos. 400 sqmm. 3.5 core PVC cable having extended copper bars of requisite capacity duly tinned from L.T. bushing for making connection with cable including cost of copper lugs and thimbles. L.V. Neutral suitable box for earthing provided.
Supply Erection testing & Commissioning of 11 KV HT metering panel complete with C.Ts P. Ts. Cubical and electronic meter with accuracy class as per requirement/approved by DHBVN at the time of installation, consisting of the following. (As per Approved by DHBVPNL). Cubical panel free standing floor mounting type made out of sheet steel 14 SWG CRCA sheet with channel iron base frame spray painted with strong synthetic light grey enamel paint as per size and design approved by the DHBVNL 3 Nos. 11 KV CTS of rating as approved by DHBVNL for indoor installation of appd. Make of 1 Nos. 11 KV PTs 11000/110 Volts Oil filled suitable for indoor installation of approved make DHBVNL. Space for Digital Electronic Meter 3 phase 4 wires recording in KWH and rating and accuracy as by DHBVNL with push button display operating system of different kind of readings. The cubical panel will be completed in all respect including intter connection, internal wiring with PVC copper cable, its testing and approval of all item by DHBVNL including cost of all testing/ approval charges of all items of DHBVNL with a guarantee of one year from the date of commissioning including cost of all labour and material required to complete the job but excluding the cost electronic meter in all respect up to the entire satisfaction of the engineer in charge of the work.
POWER FACTOR PANEL 400 KVAR: Supply erection, testing & commissioning of cubical type panel dust & vermin proof. L.T. automatic power factor control panel 400 KVAR capacity suitable for automatic operation & control of power factor within the set limits free standing floor mounting made out of 14 guage mild steel with channel iron base frame painted with stove synthetic light grey enamelled paint suitable for operation on 3 phase 4 wire 50 cycle per second 400/440 volts A.C. supply equipped with the following as per diagram attached: 1 No. automatic power factor control relay of EE Co./ L&T make.Power factor meter size 96 x 96mm of AE make.Space for incomer 200 amp. triple pole moulded case circuit breaker.A set of pilot lamps (3 Nos.) phase indicating lamp of L&T make.Iron clad bus bar chamber suitable for 200 amp. 440 volts having 4 No. copper bars of cross section 25 mm x 5mm duly tinned and insulated with PVC sleeves.Connection from incomer moulded case circuit breaker to bus bar by means of solid copper strip of requisite capacity duly tinned & insulated with PVC sleeving.3 Nos. 3 phase 20KVAR dry capacitor of MPP type iemens / L &T make (totaled 60 KVAR)2 Nos. 3 phase 10 KVAR dry capacitor of MPP type Siemens/ L&T make(totaled 20 KVAR)2 Nos. 3 phase 32 amp. contactor for 10 KVAR capacitor of L&T /Siemen make 3 Nos. 3 phase 63 amp. contactor for 20 KVAR capacitor of L&T /Siemen make 6 Nos. 32 amp. HRC fuse with holder of L&T /GE make.12 Nos. 63 amp. HRC fuse with holder of L&T /GE make.3 Nos. indication Lamps 220 volts for ON indicator of respective capacitor of L&T make.12 Nos. push button ON/OFF manual operation of L&T make Earthing copper bus bar of cross section 20 mm x 3 mm duly tinned and insulated throughout the lenght of panel. The panel will be complete with all internal wiring with PVC copper wire, inter connection etc. with all labour and material require to complete the job in all respect without cost of MCCB upto the entire satisfaction of the Engineer-in-charge of the work
POWER FACTOR PANEL 250 KVAR: Supply erection, testing & commissioning of cubical type panel dust & vermin proof. L.T. automatic power factor control panel 250 KVAR capacity suitable for automatic operation & control of power factor within the set limits free standing floor mounting made out of 14 guage mild steel with channel iron base frame painted with stove synthetic light grey enamelled paint suitable for operation on 3 phase 4 wire 50 cycle per second 400/440 volts A.C. supply equipped with the following as per diagram attached:1 No. automatic power factor control relay of EE Co./ L&T make.Power factor meter size 96 x 96mm of AE make.Space for incomer 200 amp. triple pole moulded case circuit breaker.A set of pilot lamps (3 Nos.) phase indicating lamp of L&T make.Iron clad bus bar chamber suitable for 200 amp. 440 volts having 4 No. copper bars of cross section 25 mm x 5mm duly tinned and insulated with PVC sleeves.Connection from incomer moulded case circuit breaker to bus bar by means of solid copper strip of requisite capacity duly tinned & insulated with PVC sleeving.3 Nos. 3 phase 20KVAR dry capacitor of MPP type iemens / L &T make (totaled 60 KVAR) 2 Nos. 3 phase 10 KVAR dry capacitor of MPP type Siemens/ L&T make (totaled 20 KVAR)2 Nos. 3 phase 32 amp. contactor for 10 KVAR capacitor of L&T /Siemen make 3 Nos. 3 phase 63 amp. contactor for 20 KVAR capacitor of L&T /Siemen make 6 Nos. 32 amp. HRC fuse with holder of L&T /GE make.12 Nos. 63 amp. HRC fuse with holder of L&T /GE make.3 Nos. indication Lamps 220 volts for ON indicator of respective capacitor of L&T make.12 Nos. push button ON/OFF manual operation of L&T make Earthing copper bus bar of cross section 20 mm x 3 mm duly tinned and insulated throughout the lenght of panel. The panel will be complete with all internal wiring with PVC copper wire, inter connection etc. with all labour and material require to complete the job in all respect without cost of MCCB upto the entire satisfaction of the Engineer-in-charge of the work.
(a) 1 No. 630 Amps motorised Vacumm Circuit Breaker triple pole, single break 3 position as incomer (On, Off and earth having STC capacity 20 KA for 3 seconds with copper bus bar and copper earth bar fitted with fixed type voltage indicator device as per IEC 61958-1, fully rated with earth switch, spring assisted mechanism, Red/ Green Push Button for On/ Off operation. Arc proof hinged type cable cover interlocked with earth switch. Air insulated cable boxes and boots suitable for bottom entry front termination of 3 core cable 95/120/185 Sqmm. (b) 2 Nos. 630 Amps manual Vacumm Circuit Breaker triple pole, single break 3 position as outgoing (On, Off and earth having STC capacity 20 KA for 3 seconds with copper bus bar and copper earth bar fitted with fixed type voltage indicator device as per IEC 61958-1, fully rated with earth switch, spring assisted mechanism, Red/ Green Push Button for On/ Off operation. Arc proof hinged type cable cover interlocked with earth switch. Air insulated cable boxes and boots suitable for bottom entry front termination of 3 core cable 95/120/185 Sqmm.(c) 3O/C + IE/F self powered relay with low and high set for over current and earth fault. Relay should have LCD (16 x 2). Relay should have facility to trip the breaker from remote commands without shunt trip coil, Last 5 fault record with time stamp, battery pack replaceable from front. Make of RMU : ABB/siemens/Schneider/ Voltamp. Interconnection between HT switchgear & transformer using AI. Armoured XLPE single core cable & interconnection between transformer & LT switchgear using copper bus bars. Internal earthing connections by 50 x 6mm Copper strips = 1 Set.
S/E of fire bucket 9 Ltrs Capacity of G.I. sheet of 24 gauge write with " FIRE" as per fire specification.
S/E of MS bucket stand suitable for six Nos. fire buckets (but without buckets) including the cost of welding & painting with all cost of red oxide and two coat of enameled paint of red colour completion all respect.
Supply and erection of stay wire suitable for 9/11 M. long RCC pole make out of 7/8 SWG GI wire with U type MS rod 5/8" dia duly threaded by means of angle iron of size 50 mm x 6 mm x 30 cm and 6 ft. long MS rod 5/8" dia 5' buried in the ground after fixing with cross channel size 75 mm x 40 mm x 60 cm. The stay wire will be binded on the top of the pole with help of suitable size of double U type MS clamps and stay fixed with nuts& bolts. The stay wire shall be insulated in the middle point with the help of egg. Insulator and complete with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-Charge of the work.
Supply and erection of 11 KV pin insulator with pin make with all labour and material required to complete the job including fixing the same on existing channels up to the entire satisfaction of Engineer-in- Charge of the work.
Supply and erection of 11 KV gang operated Drop out switch make conforming to IS with latest amendment including suitable size of copper blade erection of same on the existing 'H' pole with the help of 3 No. channels of size 75 mm x 40 mm x 6 mm, 1.8 M long fixed with suitable size of MS clamp, nuts and bolts including cost of 6 No. 11 KV insulator with GI pin R.D. fuses and painting with 2 coat of approved paint and one cost of red oxide and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-Charge of work.
Supply and erection of 11 KV disk insulator with all labour and material required to complete the job including fixing the same on existing channels up to the entire satisfaction of Engineer-in- Charge of the work
Supply and erection of lightening arrester module suitable for 11 KV G.O. switch with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-in-Charge of the work.
Supply and erection of fencing of transfer for safety precaution made out with the help to 50 cm x 50 cm x 6 mm angle iron, M.S. plate 50 mm x 6 mm, M.S. Jaal the perportionate quantities required in 1 sqm duly painted with red enameled paint including one coat of red oxide. The fencing angle shall be embedded in ground with C.C. mixture at least 60 cm in ground level including all labour and material required to complete the job up to the entire satisfaction of Engineer-in-charge of the work.
S/E angle iron, channel & clump with nut & bolts of various sizes required for made the platform & G.O. switch etc.
M R CONSTRUCTION COMPANY
M/s JSB Enterprises
Ecs Engineering Chd. Pvt. Ltd.
J.B.S.Electrical Co.
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .