Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.7 LAccepted-AOC 00 DEY ENTERPRISE SODEPUR 9 10 PITS COLLIERY ASANSOL BARDHAMAN WEST BENGAL 713372 | PASCHIM BARDHAMAN | WEST BENGAL | 713372 | L1 | Accepted-AOC L1-Accepted | |
| 2 | L2₹20.6 L+₹90,522.52 (4.60%)Rejected-Finance BIBIGRAM SOUTH NEAR JALALIA GIRLS HIGH SCHOOL MALDA ENGLISHBAZAR 732101 | ENGLISHBAZAR | MALDA | WEST BENGAL | 732101 | L2 | Rejected-Finance Higher than L1. | |
| 3 | L3₹20.7 L+₹99,383.21 (5.05%)Rejected-Finance BANDARAILAH MALDA | MALDA | MALDA | WEST BENGAL | L3 | Rejected-Finance Higher than L1. |
Tender Value
Refer Docs
EMD Value
₹41,010
Closing Date
7 Apr 2022, 2:30 pmClosed
EXECUTIVE ENGINEER, MALDA MECHANICAL DIVISION,PHED
Office of the Executive Engineer, Malda Mechanical Division, PHE Dte. Doulatpur PHE complex, P.O. Maliha, Dist. Malda, PIN 732102
Repairing and rectification of different PMCC cum PDB panel at Intake Pump House of Balupur raw water pumping station and Chemical House, Filter House and other working station at WTP of Balupur Water Supply Scheme under MLMD, PHE Dte.
2022_PHED_371528_2
WBPHED/EE/MLMD/NIeT_13 of 2021-2022
Open Tender
Electrical Work/ Equipment
Item Rate
45 days
Doulatpur PHE complex, P.O. Maliha, Dist. Malda
Please refer Tender documents.
5 documents required · 5 mandatory
₹41,010
Yes
10 Sept 2025
22 Mar 2022
11 Apr 2022
22 Mar 2022
7 Apr 2022
22 Mar 2022
Amount
PART-A - INTAKE PUMP HOUSE:
Charges for necessary disconnection of power line and dismentling of existing damaged electrical and electronics spares following necessary precautions from each individual Panel installed at Intake Pump House and PDB Panel of DG set all complete upto entire satisfaction of EIC.
Supply, delivery and storage at site of following materials for Main Incomer Panel at Intake Pump House:
200 A, 415 V ,4 Pole MCCB of Breaking capacity 36kA with fixed thermal and fixed magnetic setting incl. spreader link broadened with phase barriers, Extended door mounted rotary operator
160 A, 415 V, 4 Pole MCCB of Breaking capacity 36kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator.
63 A, 415 V,4 Pole MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator
32 A, 415 V , 4 Pole MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator
6 A, 240/415 V SP MCB of Breaking capacity 10 kA & C characteristics
Digital time switch
96 sqmm, 3 Phase digital Voltmeter with LED indicators having current accuracy 0.5 as per latest IEC 61010-1.
96 sqmm, 3 Phase digital Ammeter with LED indicators having current accuracy 0.5 as per latest IEC 61010-1.
LED type indicating lamp (Red 1 no Green 1 no. & Yellow 1 no)
Charges for fitting fixing of supplied spares in sl. no. 3.01 to 3.09 along with necessary mechanical and electical hardware as supplied by agency (such as screws, nut-bolts, washers, cable tie, pvc tape, sockets etc) making internal connection by supplied Cu wire in sl. no. 6.01 to 6.06 along with reconnection of power cable up to the entire satisfaction of EIC.
Supply, delivery and storage at site of following materials for PDB cum PMCC Panel at Intake Pump House:
160 A, 415 V, 4 P MCCB of Breaking capacity 25 kA with fixed thermal and fixed magnetic setting, spreader link broadened with phase barriers and extended door mounted rotary operator all complete.
100A, 415 V, 4P Microprocessor base MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator
63 A, 415 V, 4 Pole MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator
32 A, 415 V, 4 Pole MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator
16 A, 415 V, 4 Pole MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator
38 Amp. 3 pole power contactor having AC coil voltage 240V, 50Hz.
Additional contact block suitable for above contactors (NO 15 nos. & NC 9 nos.)
22-32 Amp. over load realy with kit
Motor protection relay-300 (16-44A)
6 A, 240/415 V SP MCB of Breaking capacity 10kA & C characteristics
25 A, 240/415 V TP MCB of Breaking capacity 10kA & C characteristics
Capacitor duty contactor having AC coil voltage 230V, 50Hz.
10 KVAR, 440 V heavy duty cylindrical type power factor correction capacitors.
5 Amp Auxiliary Contactor (2NO+2NC)
On/OFF Auxiliary switch
Star-Delta timer (3 sec-60sec)
96 sqmm, 3 Phase digital Voltmeter with LED indicators having current accuracy 0.5 as per latest IEC 61010-1.
96 sqmm, 3 Phase digital Ammeter with LED indicators having current accuracy 0.5 as per latest IEC 61010-1.
LED type indicating lamp (Red 13 nos. Green 13 nos. & Yellow 4 nos.)
Push button switches (start/stop) with 1 NO/ 1 NC Block (Red 3 nos. & Green 3 nos.)
250 A 3 way terminal
150 A 3 way terminal
Charges for fitting fixing of supplied spares in sl. no. 4.01 to 4.23 along with necessary mechanical and electical hardware as supplied by agency (such as screws, nut-bolts, washers, cable tie, pvc tape, sockets etc) making internal connection by supplied Cu wire in sl. no. 6.01 to 6.06 along with reconnection of power cable up to the entire satisfaction of EIC.
Supply,delivery and storage at site of following materials for PDB Panel for DG:
100 Amp, 415 V 4 Pole Panel mounted Changeover
63 Amp. 4 pole power contactor having AC coil voltage 240V, 50Hz.
250 A 4 way terminal
Digital time switch
6 A, 240/415 V SP MCB of Breaking capacity 10kA & C characteristics
96 sqmm, 3 Phase digital Voltmeter with LED indicators having current accuracy 0.5 as per latest IEC 61010-1.
96 sqmm, 3 Phase digital Ammeter with LED indicators having current accuracy 0.5 as per latest IEC 61010-1.
LED type indicating lamp (Red 3 nos. Green 3 nos. & Yellow 3 nos.)
Charges for fitting fixing of supplied spares in sl. no. 5.01 to 5.09 along with necessary mechanical and electical hardware as supplied by agency (such as screws, nut-bolts, washers, cable tie, pvc tape, sockets etc) making internal connection by supplied Cu wire in sl. no. 6.01 to 6.06 along with reconnection of power cable up to the entire satisfaction of EIC.
Supply, delivery and storage at site of following FRL wire for different PDB panel as in sl no. 3.00 to 5.00 at Intake site:
1.5 sqmm 1.1 kv grade PVC insulated copper flexible FR wire (90m/coil)
2.5 sqmm 1.1 kv grade PVC insulated copper flexible FR wire (90m/coil)
6sqmm 1.1 kv grade PVC insulated copper flexible FRL wire (90m/coil)
10 sqmm 1.1 kv grade PVC insulated copper flexible FR wire (90m/coil)
16 sqmm 1.1 kv grade PVC insulated copper flexible FR wire(90m/coil)
50 sqmm 1.1 kv grade PVC insulated copper flexible FR wire(100m/coil)
Testing and comissioning of the different PDB panel as in sl no. 3.00 to 5.00 at Intake site under load condition (8 hrs. continuous running) by checking motor current data ( Delta operation) or other releavent operating parameters all complete as per entire satisfaction of EIC.
PART-B - WATER TREATMENT PLANT:
Charges for necessary disconnection of power line and dismentling of existing damaged electrical and electronics spares following necessary precautions from each individual Panel installed at WTP PMCC Room, Chlorination Room, Chemical House and PDB Panel at Administrative Room all complete upto entire satisfaction of EIC.
Supply,delivery and storage at site of following materials for MCC cum PDB Panel for Clear Water Pump House:
125 A, 415 V 4P Microprocessor base MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator and Spreader link broadened with phase barriers
100A, 415 V 4P Microprocessor base MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator
32 A, 415 V Four Pole MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator
16 A, 415 V Four Pole MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator
On/OFF Auxiliary switch
LED type indicating lamp (Red 15 nos. Green 15 nos. & Yellow 1 nos.)
Charges fitting fixing of supplied spares in sl. no. 10.01 to 10.06 along with necessary mechanical and electical hardware as supplied by agency (such as screws, nut-bolts, washers, cable tie, pvc tape, sockets etc) making internal connection by supplied Cu wire in sl. no. 16.01 to 16.05 along with reconnection of power cable up to the entire satisfaction of EIC.
Supply,delivery and storage at site of following materials for PDB Panel for Chlorination Room:
100A, 415 V 4P Microprocessor base MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator
63 A, 415 V Four Pole MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator
32 Amp. 3 pole power contactor having AC coil voltage 230V, 50Hz.
22 Amp. 3 pole power contactor having AC coil voltage 230V, 50Hz.
10-16 Amp. Motor protection circuit breaker
14-20 Amp. Thermal over load realy with kit
3.5-5 Amp. Thermal over load realy with kit
Star-Delta timer (3 sec-60 sec)
Additional contact block suitable for above contactors (NO 7 nos. & NC 6 nos.)
10 A, 240/415 V SPN MCB of Breaking capacity 10kA & C characteristics
6 A, 240/415 V SP MCB of Breaking capacity 10kA & C characteristics
96 sqmm, 3 Phase digital Voltmeter with LED indicators having current accuracy 0.5 as per latest IEC 61010-1.
96 sqmm, 3 Phase digital Ammeter with LED indicators having current accuracy 0.5 as per latest IEC 61010-1.
LED type indicating lamp (Red 6 nos. Green 6 nos. & Yellow 6 nos.)
Push button switches (start/stop) with 1 NO/ 1 NC Block (Red 5 nos. & Green 5 nos.)
Charges for fitting fixing of supplied spares in sl. no. 11.01 to 11.03 along with necessary mechanical and electical hardware as supplied by agency (such as screws, nut-bolts, washers, cable tie, pvc tape, sockets etc) making internal connection by supplied Cu wire in sl. no. 16.01 to 16.05 along with reconnection of power cable up to the entire satisfaction of EIC.
Supply,delivery and storage at site of following materials for MCC cum PDB Panel- I for Chemical House:
100A, 415 V 4P Microprocessor base MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator
63 A, 415 V Four Pole MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator
32 A, 415 V Four Pole MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator
32 Amp. 3 pole power contactor having AC coil voltage 230V, 50Hz.
22 Amp. 3 pole power contactor having AC coil voltage 230V, 50Hz.
Additional contact block suitable for above contactors (NO 5 nos. & NC 5 nos.)
5.5-8 Amp. Thermal over load realy with kit
1.8-2.5 Amp. Thermal over load realy with kit
On/OFF Auxiliary switch
6 A, 240/415 V SP MCB of Breaking capacity 10kA & C characteristics
Digital time switch
96 sqmm, 3 Phase digital Voltmeter with LED indicators having current accuracy 0.5 as per latest IEC 61010-1.
96 sqmm, 3 Phase digital Ammeter with LED indicators having current accuracy 0.5 as per latest IEC 61010-1.
LED type indicating lamp (Red 12 nos. Green 12 nos. & Yellow 8 nos.)
Push button switches (start/stop) with 1 NO/ 1 NC Block (Red 2 nos. & Green 2 nos.)
Charges for fitting fixing of supplied spares in sl. no. 13.01 to 13.15 along with necessary mechanical and electical hardware as supplied by agency (such as screws, nut-bolts, washers, cable tie, pvc tape, sockets etc) making internal connection by supplied Cu wire in sl. no. 16.01 to 16.05 along with reconnection of power cable up to the entire satisfaction of EIC.
Supply,delivery and storage at site of following materials for MCC cum PDB Panel- II for Chemical House:
63 A, 415 V Four Pole MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator
32 A, 415 V Four Pole MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator
12 Amp. 3 pole power contactor having AC coil voltage 230V, 50Hz.
Additional contact block suitable for above contactors (NO 7 nos. & NC 7 nos.)
1.8-2.5 Amp. Thermal over load realy with kit
6 A, 240/415 V SP MCB of Breaking capacity 10kA & C characteristics
96 sqmm, 3 Phase digital Voltmeter with LED indicators having current accuracy 0.5 as per latest IEC 61010-1.
96 sqmm, 3 Phase digital Ammeter with LED indicators having current accuracy 0.5 as per latest IEC 61010-1.
LED type indicating lamp (Red 8 nos. Green 8 nos. & Yellow 8 nos.)
Push button switches (start/stop) with 1 NO/ 1 NC Block (Red 7 nos. & Green 7 nos.)
150 A 3 way terminal
LED type indicating lamp (Red 28 nos. Green 28 nos. & Yellow 3 nos.)
Charges for fitting fixing of supplied spares in sl. no. 14.01 to 14.12 along with necessary mechanical and electical hardware as supplied by agency (such as screws, nut-bolts, washers, cable tie, pvc tape, sockets etc) making internal connection by supplied Cu wire in sl. no. 16.01 to 16.05 along with reconnection of power cable up to the entire satisfaction of EIC.
Supply,delivery and storage at site of following materials for PDB panel at Administrative Building:
160 A, 415 V Four Pole MCCB of Breaking capacity 25 kA with fixed thermal and fixed magnetic setting, spreader link broadened with phase barriers and extended door mounted rotary operator all complete.
125 A, 415 V 4P Microprocessor base MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator.
100A, 415 V 4P Microprocessor base MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator
63 A, 415 V Four Pole MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator
32 A, 415 V Four Pole MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic setting incl. extended door mounted rotary operator
38 Amp. 3 pole power contactor having coil voltage 240V, 50Hz.
On/OFF Auxiliary switch
6 A, 240/415 V SP MCB of Breaking capacity 10kA & C characteristics
Digital time switch
96 sqmm, 3 Phase digital Voltmeter with LED indicators having current accuracy 0.5 as per latest IEC 61010-1.
96 sqmm, 3 Phase digital Ammeter with LED indicators having current accuracy 0.5 as per latest IEC 61010-1.
LED type indicating lamp (Red 9 nos. Green 9 nos. & Yellow 1 nos.)
Charges fitting fixing of supplied spares in sl. no. 15.01 to 15.12 along with necessary mechanical and electical hardware as supplied by agency (such as screws, nut-bolts, washers, cable tie, pvc tape, sockets etc) making internal connection by supplied Cu wire in sl. no. 16.01 to 16.05 along with reconnection of power cable up to the entire satisfaction of EIC.
Supply, delivery and storage at site of following FR wire for different PDB panel as in sl no. 10.00 to 15.00 at WTP site
1.5 sqmm 1.1 kv grade PVC insulated copper flexible FR wire (90m/coil)
2.5 sqmm 1.1 kv grade PVC insulated copper flexible FR wire (90m/coil)
6 sqmm 1.1 kv grade PVC insulated copper flexible FR wire (90m/coil)
16 sqmm 1.1 kv grade PVC insulated copper flexible FR wire (90m/coil)
50 sqmm 1.1 kv grade PVC insulated copper flexible FR wire (100m/coil)
Testing and comissioning of the different PDB panel as in sl no. 10.00 to 15.00 at WTP site under load condition (8 hrs. continuous running) by checking motor current data ( Delta operation) or other releavent operating parameters all complete as per entire satisfaction of EIC.
MAKE AS PER DEPARTMENTAL APPROVED VENDOR LIST CIRCULATED VIDE MEMO NO.PHE/IV/2277/W-181/19 DATED- 25/09/2019
Add GST @12%
Add Cess @ 1%
HANNAN BUILDERS PRIVATE LIMITED
NABAUDYAG ELECTRICAL ENGINEERING CO OP. SOC. LTD.
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .