HQ Chief Engineer, HQ 31 Zone PIN 914631 C/o 56 APO
AUGMENTATION AND IMPROVEMENT OF EXISTING ELECTRIC SUPPLY INFRASTRUCTURE AT BB CANTT SRINAGAR (PHASE-II)
2022_MES_502811_1
800123/2021
Open Tender
Electrical and Maintenance Works
Item Rate
1075 days
Srinagar
As per NIT
12 documents required · 12 mandatory
₹3,000
Garrison Engineer 864 EWS
₹7.0 L
Yes
14 Mar 2022
22 Jan 2022
10 Mar 2022
22 Jan 2022
8 Mar 2022
21 Feb 2022
22 Jan 2022 - 23 Feb 2022
Amount
Dismantling existing unserviceable insulators of any type and size 11 KV from pole including pins complete all as specified and as directed.
Taking down old unserviceable steel tubular pole of any type complete all as specified and directed
Taking up / down old unserviceable LT underground cable 300 to 400 sqmm 3.5 core from the existing trench / duct / pole etc complete all as specified and directed.
Taking up / down old unserviceable LT underground cable 185 to 240 sqmm 3.5 core from the existing trench / duct / pole etc complete all as specified and directed.
Taking up / down old unserviceable LT underground cable 25 to 120 sqmm 3.5 core from the existing trench / duct / pole etc complete all as specified and directed.
Dismantling air break gang operated switches vertical/ horizontal mounted including insulators and operating mechanism and insulators for repair/ replacement of broken/ worn out component and insulators etc complete all as specified and directed.
Taking down/dismantling of old unserviceable earth wire complete all as specified and directed
Taking down/dismantling of old unserviceable cross arm of any size complete all as specified and directed
Taking down/dismantling of old unserviceable Stay assembly of any size complete all as specified and directed
Taking down old unserviceable lightning arrester set of any size complete all as specified and directed.
Taking down existing unserviceable LT/HT over head ACSR conductor of any size / description complete all as specified and directed.
Taking up / down defective / faulty HT underground cable 11000 volts grade 95 sqmm 3.00 core from the existing trench / duct / pole etc and re-laying the same in trenches, duct, along poles or passing through roads etc. after rectification of defects including meggering of cable, provn of cable lugs, glands, thimble, insulation tape and connecting up with existing control gears, panels etc. as per site requirement complete all as specified and directed. Note :a) Excavation, returning filling etc shall be measured and paid separately. b) Material such as HT jointing Kit and accessories (indoor/outdoor) shall be measured and paid for separately.
Excavating in trenches, n exc 1.5 m wide or n exc 10 sq m on plan and n exc 1.5 m in depth for laying of cables, poles , pipes, foundation, etc. and getting out in soft/loose soil complete all as specified and directed.
Excavating in trenches, n exc 1.5 m wide, or n exc 10 sq m on plan, depth exc 1.5 m but n exc 3.0 m for foundation, etc. or for laying of cables, poles , pipes etc. and getting out in soft/loose soil complete all as specified and directed. Note for 13.00 and 14.00 :- Entire excavation shall be carried out manually only , not through JCB/excavator to avoid damage of existing electric supply / water supply / signal assets. This aspect shall be noted while quoting the Bid.
Returning filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cm all as specified and directed.
Removing of excavated soil to a distance n. exc. 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed.
Material and labour for Cement concrete (1:4:8) type D-2 (using 40 mm graded crushed stone aggregate) as in foundation , filling and mass concrete including necessary steel form work and finishing the surface fair in forms for poles etc, complete all as specified and directed.
Material and labour for Cement concrete (1:3:6) type C-2 (using 40 mm graded crushed stone aggregate) as in foundation , filling and mass concrete including necessary steel form work and finishing the surface fair in forms for poles etc, complete all as specified and directed.
Material and labour for Cement concrete (1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) in benching, coping / plinth blocks for poles and the like including weathering, slightly rounded or chamfered angles and throating, as directed including necessary Steel form work and finishing the surfaces fair in forms poles etc. complete all as specified and directed.
Material and labour for brick work with sub class 'B' bricks old size, straight or curved on plan exc 6.0 m mean radius built in cement mortar (1:4) complete all as specified & directed.
Material and labour for 15mm thick rendering in cement mortar 1:4 on fair faces of brick work or concrete surfaces, finished even and smooth without using extra cement complete all as specified & directed.
Material and labour for sand cushioning to under ground cables, with a layer of fine sand 8 cm thick before laying of cable and 15 cm thick after laying of cable punned down upto 18cm and stretching the cable complete all as specified and directed. Note:- Measurement shall be taken only after punning down sand cushioning.
Supply and laying un-reinforced precast PCC cable Cover on the cable in the trench, ISI marked, class LV, type-1, size 250mm x 150mm x 40mm (for 1100 volts LT cable) laid dry flat on sand cushioning complete all as specified and directed. Note: Sand cushioning shall be measured and paid for separately under respective item of this schedule.
Supply and laying un-reinforced precast PCC cable Cover on the cable in the trench, ISI marked, class HV, type-1, size 300mm x 180mm x 40mm (for 11KV HT cable) laid dry on sand cushioning complete all as specified and directed. Note: Sand cushioning shall be measured and paid for separately under respective item of this schedule.
Supply and laying Reinforced precast PCC cable Cover, ISI marked, class EHV, type- 1 with peak, size 450mm x 230mm x 50mm (for 33KV HT cable) laid dry on sand cushioning complete all as specified and directed. Note: Sand cushioning shall be measured and paid for separately under respective item of this schedule.
Supplying, transporting, erecting and fixing of Steel tubular swaged pole type 410, SP-55, 11.00 metre long, complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified including painting with two coats of aluminium paint heat resistant type over one coat of red oxide primer and making 06 Nos bands/ straps with yellow and black colour (15 cm wide each) synthetic enamel paint over one coat of red oxide primer at a distance 15 cm from coping block and numbering of poles with black bitumenous synthetic enamel paint in 2.5 cm height including tarring one coat on steel surface embedded in concrete foundation complete all as specified and directed.
Material and labour for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under-coat and one finishing coat of aluminium paint complete all as specified and directed.
Supplying, installation, commissioning and testing of transformer step down 11/0.433KV capacity 200 KVA, out door type copper wound 3 phase, 4 wire, 50 cycles per second, oil immersed naturally cooled external cooling tube core type delta connection on primary side (HV side) and star connection on secondary side (LV side) having tapping in the step of 2.5% for correction of voltage at secondary side upto + 7.5% to be charged by means of hand operated, off load/tap changing gear including first filling of new transformer oil till the desired level of conservator of dielectric strength not less than 60 KV with standard fittings such as two earting terminals for body and one additional for neutral brought out inbushing, oil level gauge indicator for level minimum and maximum, lifting lugs, rating and terminal plate, plain breather device with silica gel to prevent ingress of rain water and inserts, drain cum sampling valve 20mm bore steel with plug,dial type thermo meter, oil filling hole 32mm threaded with plug. The transformer shall be powder coated for water/dust and vermin proof. Note :- a) Transformer oil shall be conforming to requirements of IS-335-1993 rev -2005 ;specification for new insulating oil for transformers. b) The transformer shall be IS-1180 (Part-I) 2014 with maximum total losses as per energy efficiency level-2 of IS:1180 (Part-I) 2014.
Supplying, installation, commissioning and testing of transformer step down 11/0.433KV capacity 63 KVA, out door type copper wound 3 phase, 4 wire, 50 cycles per second, oil immersed naturally cooled external cooling tube core type delta connection on primary side (HV side) and star connection on secondary side (LV side) having tapping in the step of 2.5% for correction of voltage at secondary side upto + 7.5% to be charged by means of hand operated, off load/tap changing gear including first filling of new transformer oil till the desired level of conservator of dielectric strength not less than 60 KV with standard fittings such as two earting terminals for body and one additional for neutral brought out inbushing, oil level gauge indicator for level minimum and maximum, lifting lugs, rating and terminal plate, plain breather device with silica gel to prevent ingress of rain water and inserts, drain cum sampling valve 20mm bore steel with plug,dial type thermo meter, oil filling hole 32mm threaded with plug. The transformer shall be powder coated for water/dust and vermin proof. Note:- a) Transformer oil shall be conforming to requirements of IS-335-1993 rev-2005 specification for new insulating oil for transformers. b) The transformer shall be IS-1180 (Part-I) 2014 with maximum total losses as per energy efficiency level-2 of IS:1180 (Part-I) 2014.
Material and labour for construction of platform for single transformer of size 3.50m x 2.50 m x 1.20 m high from natural ground level with brick walling including steps, XPM fencing fixed with MS angle iron fencing posts upto 2.45 metre height above ground level with MS gate and locking arrangement incld necessary earthwork and excavation having following specifications:- (a) Foundation in PCC (1:4:8) type D-2 (using 40 mm graded crushed stone aggregate) (b) Burnt brick work in CM 1:4 having wall thickness not less than 230mm (c) Filling under floors of approved rammed earth. (d) 100 mm thick PCC (1:5:10) type E-2 (using 40 mm graded crushed stone aggregate) (e) 50mm thick PCC flooring PCC (1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) finished even and smooth with using extra cement. (f) 10 mm thick cement plasted in CM 1:6 finshing fair and even without using extra cement. (g) 2 coats of cement base paint on plastered surfaces. (h) 2 coats of synthetic enamel paint over a coat of red oxide primer on steel surfaces. (j) Excavation and earth work in any type of soil including removal of surplus soil to a distance not exe 50 mtr. (k) Any other item as directed by GE. (l) Height as shown on drawings Note:- All details shall be as shown in Drg No. CESZ/TD-1110/2011 sh 1/2 & 2/2 except size.
Supply and fixing Switch air break gang operated Triple pole, mechanically operated from ground level mounted on 12 insulators outdoor type suitable for vertical installations single break provided with locking arrangement for operating handle including seven levers "Navtal" lock consisting of Mild Steel channel HT post top insulator copper alloy high pressure assembly with drop out expulsion fuses for phases, operating rod of 25mm dia medium grade G.I. pipe suitable to operate from the ground level complete conformimg to IS : 1018-1972 with continous current rating 200 Amps 11 KV grade complete all as specified and as directed.
Supply and fixing of HT 33KV out door type Switch air break gang operated, Triple pole, horizontal or vertical mounting fixed type complete with 09 insulators copper alloy high pressure assembly with drop out expulsion fuses for phases, operating rod of 25mm dia medium grade G.I. pipe suitable to operate from the ground level complete conformimg to IS : 1018-1972 with continous current rating 200 Amps 33 KV grade complete all as specified and as directed.
Supply and fixing lightening arrestor 11 KV non linear type with all fittings, transmission class, discharge capacity 10 KA peak complete all as specified and directed.
Supply and fixing lightening arrestor HT 33 KV with all fittings, station class , discharge capacity 30KA complete all as specified and directed.
Supply, laying , jointing and testing underground LT cable XLPE insulated heavy duty, galvanised steel strip or wire armoured, PVC sheathed multistranded,1100 Volts grade, of cross sectional area 630 sqmm 3.5 core with aluminium conductor as per IS 7098 (Part-I) along with suitable size aluminium cable lugs (bottle neck /eye let/ ring type as per ground requirement) and cable gland joint etc. laid in trenches, along poles, passing through pipes, laid under floors, fixed on walls/roofs and passing under road complete all as specified and directed.
Supply, laying , jointing and testing underground LT cable XLPE insulated heavy duty, galvanised steel strip or wire armoured, PVC sheathed multistranded,1100 Volts grade, of cross sectional area 500 sqmm 3.5 core with aluminium conductor as per IS 7098 (Part-I) along with suitable size with aluminium cable lugs (bottle neck /eye let/ ring type as per ground requirement) and cable gland joint etc. laid in trenches, along poles passing through pipes, laid under floor, fixed on walls/roofs and passing under road etc complete all as specified and directed.
Supply, laying , jointing and testing underground LT cable XLPE insulated heavy duty, galvanised steel strip or wire armoured, PVC sheathed multistranded,1100 Volts grade, of cross sectional area 400 sqmm 3.5 core with aluminium conductor as per IS 7098 (Part-I) along with suitable size with aluminium cable lugs (bottle neck /eye let/ ring type as per ground requirement) and cable gland joint etc. laid in trenches, along poles passing through pipes, laid under floor, fixed on walls/roofs and passing under road etc complete all as specified and directed.
Supply, laying , jointing and testing underground LT cable XLPE insulated heavy duty, galvanised steel strip or wire armoured, PVC sheathed multistranded,1100 Volts grade, of cross sectional area 240 sqmm 3.5 core with aluminium conductor as per IS 7098 (Part-I) along with suitable size with aluminium cable lugs (bottle neck /eye let/ ring type as per ground requirement) and cable gland joint etc. laid in trenches, along poles passing through pipes, laid under floor, fixed on walls/roofs and passing under road etc complete all as specified and directed.
Supply, laying , jointing and testing underground LT cable XLPE insulated heavy duty, galvanised steel strip or wire armoured, PVC sheathed multistranded,1100 Volts grade, of cross sectional area 185 sqmm 3.5 core with aluminium conductor as per IS 7098 (Part-I) along with suitable size with aluminium cable lugs (bottle neck /eye let/ ring type as per ground requirement) and cable gland joint etc. laid in trenches, along poles passing through pipes, laid under floor, fixed on walls/roofs and passing under road etc complete all as specified and directed.
Supply, laying , jointing and testing underground LT cable XLPE insulated heavy duty, galvanised steel strip or wire armoured, PVC sheathed multistranded,1100 Volts grade, of cross sectional area 150 sqmm 3.5 core with aluminium conductor as per IS 7098 (Part-I) along with suitable size with aluminium cable lugs (bottle neck /eye let/ ring type as per ground requirement) and cable gland joint etc. laid in trenches, along poles passing through pipes, laid under floor, fixed on walls/roofs and passing under road etc complete all as specified and directed.
Supply, laying , jointing and testing underground LT cable XLPE insulated heavy duty, galvanised steel strip or wire armoured, PVC sheathed multistranded,1100 Volts grade, of cross sectional area 120 sqmm 3.5 core with aluminium conductor as per IS 7098 (Part-I) along with suitable size with aluminium cable lugs (bottle neck /eye let/ ring type as per ground requirement) and cable gland joint etc. laid in trenches, along poles passing through pipes, laid under floor, fixed on walls/roofs and passing under road etc complete all as specified and directed.
Supply, laying , jointing and testing underground LT cable XLPE insulated heavy duty, galvanised steel strip or wire armoured, PVC sheathed multistranded,1100 Volts grade, of cross sectional area 95 sqmm 3.5 core with aluminium conductor as per IS 7098 (Part-I) along with suitable size with aluminium cable lugs (bottle neck /eye let/ ring type as per ground requirement) and cable gland joint etc. laid in trenches, along poles passing through pipes, laid under floor, fixed on walls/roofs and passing under road etc complete all as specified and directed.
Supply, laying , jointing and testing underground LT cable XLPE insulated heavy duty, galvanised steel strip or wire armoured, PVC sheathed multistranded,1100 Volts grade, of cross sectional area 70 sqmm 3.5 core with aluminium conductor as per IS 7098 (Part-I) along with suitable size with aluminium cable lugs (bottle neck /eye let/ ring type as per ground requirement) and cable gland joint etc. laid in trenches, along poles passing through pipes, laid under floor, fixed on walls/roofs and passing under road etc complete all as specified and directed.
Supply, laying , jointing and testing underground LT cable XLPE insulated heavy duty, galvanised steel strip or wire armoured, PVC sheathed multistranded,1100 Volts grade, of cross sectional area 50 sqmm 3.5 core with aluminium conductor as per IS 7098 (Part-I) along with suitable size with aluminium cable lugs (bottle neck /eye let/ ring type as per ground requirement) and cable gland joint etc. laid in trenches, along poles passing through pipes, laid under floor, fixed on walls/roofs and passing under road etc complete all as specified and directed.
Supply, laying , jointing and testing underground LT cable XLPE insulated heavy duty, galvanised steel strip or wire armoured, PVC sheathed multistranded,1100 Volts grade, of cross sectional area 35 sqmm 3.5 core with aluminium conductor as per IS 7098 (Part-I) along with suitable size with aluminium cable lugs (bottle neck /eye let/ ring type as per ground requirement) and cable gland joint etc. laid in trenches, along poles passing through pipes, laid under floor, fixed on walls/roofs and passing under road etc complete all as specified and directed.
Supply, laying , jointing and testing underground LT cable XLPE insulated heavy duty, galvanised steel strip or wire armoured, PVC sheathed multistranded,1100 Volts grade, of cross sectional area 25 sqmm 3.5 core with aluminium conductor as per IS 7098 (Part-I) along with suitable size with aluminium cable lugs (bottle neck /eye let/ ring type as per ground requirement) and cable gland joint etc. laid in trenches, along poles passing through pipes, laid under floor, fixed on walls/roofs and passing under road etc complete all as specified and directed.
Supply, laying , jointing and testing underground LT cable XLPE insulated heavy duty, galvanised steel strip or wire armoured, PVC sheathed multistranded,1100 Volts grade, of cross sectional area 16 sqmm 4 core with aluminium conductor as per IS 7098 (Part-I) along with suitable size with aluminium cable lugs (bottle neck /eye let/ ring type as per ground requirement) and cable gland joint etc. laid in trenches, along poles passing through pipes, laid under floor, fixed on walls/roofs and passing under road etc complete all as specified and directed.
Supply, laying , jointing and testing underground LT cable XLPE insulated heavy duty, galvanised steel strip or wire armoured, PVC sheathed multistranded,1100 Volts grade, of cross sectional area 10 sqmm 2 core with aluminium conductor as per IS 7098 (Part-I) along with suitable size with aluminium cable lugs (bottle neck /eye let/ ring type as per ground requirement) and cable gland joint etc. laid in trenches, along poles passing through pipes, laid under floor, fixed on walls/roofs and passing under road etc complete all as specified and directed.
Supply, laying, jointing, testing and commissioning underground HT cable XLPE insulated, heavy duty, galvanised steel strip or wire armoured, PVC bedded, earthed electric power cable with aluminium conductor 33000 Volts grade of cross sectional area 300 sqmm 3.0 core as per IS 7098 (Part-II) including both side connection along with suitable size aluminium cable lugs, laid in trenches, along poles or passing through pipes or laid under floor or through walls, passing under roads etc. complete all as specified and directed.
Supply, laying, jointing, testing and commissioning underground HT cable XLPE insulated, heavy duty, galvanised steel strip or wire armoured, PVC bedded, earthed electric power cable with aluminium conductor 11000 Volts grade of cross sectional area 95 sqmm 3.0 core as per IS 7098 (Part-II) including both side connection along with suitable size aluminium cable lugs, laid in trenches, along poles or passing through pipes or laid under floor or through walls, passing under roads etc. complete all as specified and directed.
Supply, laying, jointing, testing and commissioning underground HT cable XLPE insulated, heavy duty, galvanised steel strip or wire armoured, PVC bedded, earthed electric power cable with aluminium conductor 11000 Volts grade of cross sectional area 120 sqmm 3.0 core as per IS 7098 (Part-II) including both side connection along with suitable size aluminium cable lugs, laid in trenches, along poles or passing through pipes or laid under floor or through walls, passing under roads etc. complete all as specified and directed.
Supply, laying, jointing, testing and commissioning underground HT cable XLPE insulated, heavy duty, galvanised steel strip or wire armoured, PVC bedded, earthed electric power cable with aluminium conductor 11000 Volts grade of cross sectional area 185 sqmm 3.0 core as per IS 7098 (Part-II) including both side connection along with suitable size aluminium cable lugs, laid in trenches, along poles or passing through pipes or laid under floor or through walls, passing under roads etc. complete all as specified and directed.
Supply, laying, jointing, commissioning and testing of Arial bunched conductor having phase conductor of stranded compacted circular aluminium conductor screen of extruded semi conducting compound extruded XLPE insulated 11000 volts grade, insulation screen of screen of ectruded semi conducting compound over all metallic screen of copper tape extruded PE sheathed twisted around bare aluminium alloy messenger generally as per IS 7098 Part -II, with upto date rev, of sze 3x95 sqmm + 1x70 sqmm on existing HT pole 11 mtr long including hook and MS clamps and nuts , bolts complete all as specified and directed. Note:- 3x95 sqmm + 1x70 sqmm conductor together shall be cosidered one metre.
'Supply and fixing cable jointing kit for 33 KV (Earthed) grade cable for outdoor termination Heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured, aluminium conductor cable of size 300 Sqmm complete all as specified and directed.
'Supply and fixing cable jointing kit for 33 KV (Earthed) grade cable for Straight through Heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured, aluminium conductor cable of size 300 complete all as specified and directed.
'Supply and fixing cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination Heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured, aluminium conductor cable of size 95 Sqmm complete all as specified and directed.
'Supply and fixing cable jointing kit for 11 KV (Earthed) grade cable for Straight through Heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured, aluminium conductor cable of size 95 Sqmm complete all as specified and directed.
'Supply and fixing cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination Heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured, aluminium conductor cable of size 120 Sqmm complete all as specified and directed.
'Supply and fixing cable jointing kit for 11 KV (Earthed) grade cable for Straight through Heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured, aluminium conductor cable of size 120 Sqmm complete all as specified and directed.
'Supply and fixing cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination Heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured, aluminium conductor cable of size 185 Sqmm complete all as specified and directed.
'Supply and fixing cable jointing kit for 11 KV (Earthed) grade cable for Straight through Heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured, aluminium conductor cable of size 185 Sqmm complete all as specified and directed.
'Supply and fixing cable jointing kit for LT 1.1 KV grade cable for outdoor / indoor termination heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured, aluminium conductor cable of size 400 to 630 Sqmm 3.5 core complete all as specified and directed.
'Supply and fixing cable jointing kit for LT 1.1 KV grade cable for outdoor / indoor termination heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured, aluminium conductor cable of size 240 to 300 Sqmm 3.5 core complete all as specified and directed.
'Supply and fixing cable jointing kit for LT 1.1 KV grade cable for outdoor / indoor termination heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured, aluminium conductor cable of size 150 to 185 Sqmm 3.5 core complete all as specified and directed.
'Supply and fixing cable jointing kit for LT 1.1 KV grade cable for outdoor / indoor termination heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured, aluminium conductor cable of size 70 to 120 Sqmm 3.5 core complete all as specified and directed.
'Supply and fixing cable jointing kit for LT 1.1 KV grade cable for outdoor / indoor termination heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured, aluminium conductor cable of size 25 to 50 Sqmm 3.5 core complete all as specified and directed.
Supply, installation, testing and commissioning out door type cubical cable joint box board outer shell made out of 3.15 mm thick MS sheet of size 500mm x 500mm x300 mm MS sheet and MS angle section 25 x25 x5 mm on PCC 1:2:4 type B-1 platform 70 cm above the ground level and 45 cm below the ground level, frame factory fabricated with front open able double door system lockable/open able by Keys having chromium plated 19 mm dia fancy lock, louvers and air vent gasket for natural flow of air “U” type gasket shall be used to make the outer shell completely vermin proof, suitable for 3 phase 4 wire 415 Volt, 50 Hz, factory fabricated (Factory approved from CPRI) having modern fabrication and followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof with IP 54 and general construction confirming to IS:8623/93 comprising of the Aluminium bus bar 500 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators complete all as specified and directed. Note:- Cost of PCC incld necessary earth work and excavation shall be deemed to be included in quoted rate.
Supply, install, testing and commissioning of HT 12 KV, 3 phase, 50 Hz, totally enclosed metal clad SF6 switchgear having rupturing capacity upto 630 A, RMU, Rated voltage 11 KV, Rated power frequency withstand voltage - 12 KV, Rated lightning impulse withstand voltage - 75 KV, rated current for ring main feeder 630 A , (one incoming and two outgoing) rated short time current - 21 KA/3 sec non extensible, manually operated, out door type rated short circuit current 50 KA, Front cable termination and bottom cable entry, copper busbar, motorised operated, outdoor, extensible, in single unit 04 Nos fixed manual 630 Amps load breaker switch in SF6 insulated stainless steel enclosure, without metering, ambient temperature (from -9 to +40 degree C) with IP 54 including necessary foundation complete all as specified and directed. Note : The RMU shall be suitable for operations at a height of 1550 mtr above or below sea level (suitable for srinagar).
Total Number of modules 04 Pcs STANDARDS AND MECHANICAL DATA: Metal Enclosed switchgear : IEC 60298 General Purpose switches : IEC 60265 Disconnectors and Earthing switches : IEC 60129 Circuit Breakers : IEC 60056 Common clauses : IEC 60694 Pressure of SF6 Gas : 1.4 bar at 20 degree C Cable bushings : DIN 47636 Temperature class : -25 deg C to +40 deg C Degree of protection : - SF6 tank : IP67 Busbars : 240 mm2 Cu Earth bar (external) : 120 mm2 Cu - Bolt dimension : M10 Thickness of stainless steel tank : 3.0mm Colours : - Front cover : RAL 7012 - Side and cable cover : RAL 7035
ELECTRICAL DATA: 12kv - 28kv - 1 MIN Rated current busbars : 630 A Rated current cable switch disconnector : 630 A Short time withstand current (3 sec) cable switch disconnector : 20 kA rms Short time withstand current (3 sec)vaccum circuit breaker : 20 kA rms Rated current for transformer T-off : 630 A Impulse withstand voltage : To earth and between phases : 75 KV Insulation level : - Power frequency 1 min : 28 KV CT ratio 300-150/5 or 1 15 VA Suitable PT for measuring voltage Self powered relay over current and earth fault protection as manufacturer's recommendation Suitable power pack. All other accessories like indicator, digital voltmeter, digital ammeter as per IS.
Load Break Switch - 04 Nos SafePlus C is a cable switch module with a three position load break switch and earthing switch, busbars, interlocking and earthbar. 1. SafePlus type C : Cable switch 12 KV, 630A; 20 KA for 3 sec 2. Snap action mech for manual operation 3. Cable bushings 400 series bolted, 630 A, standard 4. Cable cover standard. 5. Capacitive voltage indication fixed type VPIS 9-15 KV
Supply, install, testing and commissioning of HT 36 KV, 3 phase, 50 Hz, totally enclosed metal clad SF6 switchgear having rupturing capacity upto 630 A, RMU, Rated voltage 33 KV, Rated power frequency withstand voltage - 36 KV, Rated lightening impulse withstand voltage - 75 KV, rated current for ring main feeder 630 A , rated short time current - 28 KA/3 sec, copper busbar, manually operated, out door, non extensible, two LBS and two VCB in single unit ( 2 x LBS + 2 x VCB) without metering, ambient temperature (-9 to +40 degree C) with IP 54 including necessary foundation complete all as specified and directed. Note : The RMU shall be suitable for operations at a height of 1550 mtr above or below sea level (suitable for srinagar).
Total Number of modules 04 Pcs STANDARDS AND MECHANICAL DATA: Metal Enclosed switchgear : IEC 62271-200 General Purpose switches : IEC 60265-1 Disconnectors and Earthing switches : IEC 62271-102 Switch Fuse Combination : IEC 62271-105 Common clauses : IEC 60694 Pressure of SF6 Gas : 1.4 bar at 20 degree C Cable bushings outside cone : CENELEC EN 50181 interface C Temperature class : -25 deg C to +40 deg C indoor Degree of protection : - SF6 tank : IP67 - Front cover : IP 2X - Cable cover : IP 3X Busbars : 306 mm2 Cu Earth bar (external) : 120 mm2 Cu - Bolt dimension : M10 Thickness of stainless steel tank : 2.0mm Colours : - Front cover : RAL 7035 - Side and cable cover : RAL 7035
ELECTRICAL DATA - 36 KV Normal voltage : 33 KV Rated frequency : 50 Hz Rated current for busbars : 630 A Rated current cable switch disconnector : 630 A Short time withstand current (1 sec) cable switch disconnector : 25 kA rms Short time withstand current (1 sec) V-module vacuum circuit breaker : 25 kA rms Rated current for transformer T-off : 630 A Impulse withstand voltage : To earth and between phases : 170 KV Insulation level : - Power frequency 1 min : 70 KV CT ratio 300-150/5 or 1 15 VA Suitable PT for measuring voltage Self powered relay over current and earth fault protection as manufacturer's recommendation Suitable power pack. All other accessories like indicator, digital voltmeter, digital ammeter as per IS.
A01 C - Load Break Switch - 02 Nos SafePlus C is a cable switch module with a two position load break switch, earthing switch, busbars, interlocking and earthbar. 1 SafePlus type C : Cable switch 36 KV, 630A; 25 KA 1 Manometer 1 Cable compartement standard 1 Snap action mech for manual operation 1 Cable bushings interface C (400 bolted), 630 A, standard 1 Single cable connection 1 Capacitive voltage indication fixed type VPIS
A03 V - Vacuum Circuit Breaker - 02 Nos SafePlus 36V is a Vacuum Circuit breaker module with vaccum circuit breaker with vacuum circuit breaker, stored energy spring mechanism, two-position operating mechanism for the isolator and earthing switch, busbars, interlocking and earthbar. 1. SafePlus type V : Vacuum circuit breaker 36 KV, 630A; 25 KA 2. Padlocking device push buttons for EL3 standard 3. Cable compartment standard 4. Cable bushings interface C (400 bolted), 630 A, standard 5. Single cable connection 6. Capacitive voltage indication fixed type VPIS 7. Stored energy mechanism for manual operation 8. Self-powered Relay - Ashida Make - ADR241S
Material and labour for Cradles, hexagonal/rectangular, fabricated with galvanised steel wire 3.15 or 4mm dia complete all as specified and directed.
Supply and fixing pin type, porcelain, vitrous white, brown or green insulator including 01 M.S.spindle, two galvanised iron washers and one galvanised iron nut etc,150 mm height, 150 mm dia for 11000 volts grade complete all as specified and directed.
Supply and fixing Disc type insulator, porcelain, vitrous white, brown or green, 145mm height and 255mm dia, ball and socket type, single disc assembly for tension with tension clamps for conductors, working pressure 11000 volts with GI nut, straps etc complete all as specified and as directed.
Supply and laying / fixing for GI tubing light grade of 50mm bore including all necessary fittings such as elbow, bends, clamps including nut and bolts for cable protection along poles, wall surface, under ground or road crossing etc complete all as specified and directed .
Supply and laying / fixing for GI tubing light grade of 80mm bore including all necessary fittings such as elbow, bends, clamps including nut and bolts for cable protection along poles, wall surface, under ground or road crossing etc complete all as specified and directed .
Supply and laying / fixing for GI tubing light grade of 100mm bore including all necessary fittings such as elbow, bends, clamps including nut and bolts for cable protection along poles, wall surface, under ground or road crossing etc complete all as specified and directed .
Supply and laying / fixing for GI tubing light grade of 150mm bore including all necessary fittings such as elbow, bends, clamps including nut and bolts for cable protection along poles, wall surface, under ground or road crossing etc complete all as specified and directed .
Supply, installation, testing and commissioning of HT 11 KV, 630 Amp outdoor type load break switch with 200 Amp DO set and earth switch outdoor type floor mounted provision of over current and earth fault protection, alongwith factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15mm thick with ingress protection of IP-54 grade having heat shrinkable sleeves, louvers and air vent gasket for natural flow of air shall be used to make the outer shell completely vermin proof including mounted on angle iron stand made out of MS angel size 50x 50 x 6mm grouted in PCC foundation in cement concrete 1:2:4 type B-1 platform 70 cm above the ground level and 45 cm below the ground level (using 20mm graded crushed stone aggregate), including accomodating the complete gears and accessories as reqd as per IS for installation complete all as specified and directed. Note:- Cost of PCC incld necessary earth work and excavation shall be deemed to be included in quoted rate.
Supply, installation, testing and commissioning of HT 11 KV, 630 Amp outdoor type load break switch with earth switch outdoor type floor mounted provision of over current and earth fault protection, alongwith factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15mm thick with ingress protection of IP-54 grade having heat shrinkable sleeves, louvers and air vent gasket for natural flow of air shall be used to make the outer shell completely vermin proof including mounted on angle iron stand made out of MS angel size 50x 50 x 6mm grouted in PCC foundation in cement concrete 1:2:4 type B-1 platform 70 cm above the ground level and 45 cm below the ground level (using 20mm graded crushed stone aggregate), including accomodating the complete gears and accessories as reqd as per IS for installation complete all as specified and directed. Note:- Cost of PCC incld necessary earth work and excavation shall be deemed to be included in quoted rate.
Supplying and fixing Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20cm x 15cm size complete all as specified and directed.
Supplying and fixing Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25cm x 20cm size complete all as specified and directed.
M&L for boring of holes under roads, pavements, hard standing by trenchless technology using ultra sound technique & necessary machine including HDPE pipe of 6 kg/sqmm of 150 mm dia suitable for 0.4 Mpa working pressure complete all as specified and directed. Note - The rate quoted shall be deemed to include the cost of provn of HDPE pipe.
Road cutting in trenches, n. exc 1 m wide and n. exc 1.5m in depth upto 6 Mtr long; for laying of cables, pipes, etc. and getting out Hard/dense soil and repair the same after laying the pipes/cables of any size and specification by means of suitable quality Cement concrete (1:2:4) type B-1 using 20 mm graded crushed stone aggregate as in benching, coping, etc for repair of existing structure of roads complete including necessary form work complete all as specified and directed. Note : Cost of material for making good shall be included in the quoted rates.
Material and labour for earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth plate not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 metre below normal ground level, connected to and including Galvanized Iron wire 4mm thick as earthing lead by means of steel bolts, nuts, check nuts and washers test points made of GI Strip 32x6mm, 10 cm long, PCC (1:2:4) type B-1 in pit, angle iron 25x25x3mm frame work with precast RCC (1:2:4) type B-1 cover reinforced with 8mm dia TMT bars @ 150mm c/c both ways and 12mm dia MS fabricated handle, medium grade GI watering pipe 20mm bore with funnel, wire mess and light grade GI protection pipe 15mm bore upto 5m length for drawing in earth lead, salt, charcoal, etc including excavation and earth work in any type of soil, removal of surplus soil to a distance not exceeding 50m complete all as shown in electrical plate No. 3 of SSR Part-I and connecte complete all as directed by GE including testing on completion. Note : The quoted rate of earthing shall be deemed to include cost of Galvanized Iron wire upto 7.5 meter and protection pipe and watering pipe. Any variation in length of earth wire shall be adjusted through deviation order.
Material and labour for earthing complete with copper plate electrode 600mm x 600mm x 3.15 mm thick buried directly in ground (earth plate not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 metre below normal ground level, connected to and including copper strip 20x3mm thick as earthing lead by means of brass bolts, nuts, check nuts and washers test points made of copper Strip 20x3mm, 10 cm long, PCC (1:2:4) type B-1 in pit, angle iron 25x25x3mm frame work with precast RCC (1:2:4) type B-1 cover reinforced with 8mm dia TMT bars @ 150mm c/c both ways and 12mm dia MS fabricated handle, medium grade GI watering pipe 20mm bore with funnel, wire mess and light grade GI protection pipe 40mm bore upto 5m length for drawing in earth lead, salt, charcoal, etc including excavation and earth work in any type of soil, removal of surplus soil to a distance not exceeding 50m complete all as shown in electrical plate No. 3 of SSR Part-I and connecte complete all as directed by GE including testing on completion. Note : The quoted rate of earthing shall be deemed to include cost of copper strip upto 7.5 meter and protection pipe and watering pipe. Any variation in length of earth wire shall be adjusted through deviation order.
Material and labour for earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth plate not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 metre below normal ground level, connected to and including Galvanized Iron strip 32x6mm thick as earthing lead by means of steel bolts, nuts, check nuts and washers test points made of GI Strip 32x6mm, 10 cm long, PCC (1:2:4) type B-1 in pit, angle iron 25x25x3mm frame work with precast RCC (1:2:4) type B-1 cover reinforced with 8mm dia TMT bars @ 150mm c/c both ways and 12mm dia MS fabricated handle, medium grade GI watering pipe 20mm bore with funnel, wire mess and light grade GI protection pipe 40mm bore upto 5m length for drawing in earth lead, salt, charcoal, etc including excavation and earth work in any type of soil, removal of surplus soil to a distance not exceeding 50m complete all as shown in electrical plate No. 3 of SSR Part-I and connecte complete all as directed by GE including testing on completion. Note : The quoted rate of earthing shall be deemed to include cost of Galvanized Iron strip upto 7.5 meter and protection pipe and watering pipe. Any variation in length of earth wire shall be adjusted through deviation order.
Supply and fixing earth continuity conductor or main earthing lead, 32 x 6 mm galvinised iron strip, fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required complete all as specified and directed.
Supply and fixing earth continuity conductor or main earthing lead, 20 x 3 mm copper strip, fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required complete all as specified and directed.
Supply & fix in replacement MCCB 4 pole, 415 Volt, adjustable type, with thermal based release 630 Amp with breaking capacity 50 KA alongwith extension terminals/thimbles or connected accessories required at site for installation / fixing complete all as specified and directed.
Supply & fix in replacement MCCB 4 pole, 415 Volt, adjustable type, with thermal based release 500 Amp with breaking capacity 36 KA alongwith extension terminals/thimbles or connected accessories required at site for installation / fixing complete all as specified and directed.
Supply & fix in replacement MCCB 4 pole, 415 Volt, adjustable type, with thermal based release 400 Amp with breaking capacity 36 KA alongwith extension terminals/thimbles or connected accessories required at site for installation/fixing complete all as specified and directed.
Supply & fix in replacement MCCB 4 pole, 415 Volt, adjustable type, with thermal based release 350 Amp with breaking capacity 36 KA alongwith extension terminals/thimbles or connected accessories required at site for installation/fixing complete all as specified and directed.
Supply & fix in replacement MCCB 4 pole, 415 Volt, adjustable type, with thermal based release 250 Amp with breaking capacity 36 KA alongwith extension terminals/thimbles or connected accessories required at site for installation/fixing complete all as specified and directed.
Supply & fix in replacement MCCB 4 pole, 415 Volt, adjustable type, with thermal based release 200 Amp with breaking capacity 36 KA alongwith extension terminals/thimbles or connected accessories required at site for installation/fixing complete all as specified and directed.
Supply and fixing, cable route marker for HT cable duly engraved (HT 33 KV cable) on 150mm dia MS round plate 10mm thick, duly painted with red colour paint and fixed on MS angle of size 40mmx40mmx5mm with nuts and bolts and embedded in PCC (1:2:4) concrete block of size 230mmx230mmx150mm, including necessary excavation & earth work complete all as specified and directed.
Supply and fixing, cable route marker for HT cable duly engraved (HT 11 KV cable) on 150mm dia MS round plate 10 mm thick, duly painted with brown colour paint, and fixed on MS angle of size 40mmx40mmx5mm with nuts and bolts and embedded in PCC (1:2:4) concrete block of size 230mmx230mmx150mm, including necessary excavation & earth work complete all as specified and directed.
Supply and fixing, cable route marker for HT cable duly engraved (LT 1.1 KV cable) on 150mm dia MS round plate 10 mm thick, duly painted with yellow colour paint, and fixed on MS angle of size 40mmx40mmx5mm with nuts and bolts and embedded in PCC (1:2:4) concrete block of size 230mmx230mmx150mm, including necessary excavation & earth work complete all as specified and directed.
Supply and fixing street light bracket 1.5 metre long made out of 40mm bore GI pipe light grade bent to shape, incl necessary welding etc and fixing on existing LT pole with 40 x 6mm flat iron MS clamps including necessary nuts, bolts and washers etc and painting with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed
Material and labour for junction box, pole mounted of size 230mm x 170mm x 110mm made out of engineering plastic comprising 60 Amps, 4 pole aluminium bus bar mounted on DMC insulator, 1 No SP MCCB 6 Amps, 10 KA, junction box should be mounted on pole with MS flat iron of sizes 40mm x 6mm including nuts, bolts and washers complete all as specified and directed. Note: Quoted rates shall be deemed to be inclusive of 1.5 sqmm 3 core flexible copper cable from junction box to street light as per site requirement.
Suppy and fixing street light panel 6 KW confirming to IS/ IES 60947-4-1 suitable for single phase MCB rating 40 amps on /off timer Astronomical, contactor rating 32 amp including internal wiring in built short circuit protection, IP-54 complete all as specified and directed.
Suppy and fixing street light panel 6 KW confirming to IS/ IES 60947-4-1 suitable for three phase MCB rating 63 amps on /off timer Astronomical, contactor rating 63 Amp including internal wiring in built short circuit protection, IP-54 complete all as specified and directed.
Supply and fixing LED light fitting, 70 watt pressure dia cast alumunium alloy for housing (heat sink) for effective thermal management sturdiness, excellent corriosion resistance long life and pheatobioligically safe LED's , No harmful UV & IR radiations, instant light with low running temperature, operating temperature (-10ºc) to (+50ºc) with system lumen >/110 Lm/W high efficiency long life LED made with SMD LED pakage mounted MCPCB confirming to IP 65/66 protectiion . Powered with integral Electric LED driver (SMPS based) over voltage protection , surge voltage protection 10KV with SPD & other safety as per IS 15885 Part-II Sec 13 complete all as per specified and directed.
ALCO ENGINEERSPVT LTD
M/S ABDUL REHMAN WANI
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .