| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.5 CrAccepted-Finance GR 8 ADDA BUILDING 1ST FLOOR CITY CENTRE DURGAPUR 16 | DURGAPUR | PASCHIM BARDHAMAN | WEST BENGAL | ₹1.5 Cr | L1 | Accepted-Finance Quoting Lowest Rate |
| 2 | L2₹1.6 Cr+₹10.4 L (6.88%)Rejected-Finance 448 MUZAFFAR AHMED STREET KOLKATA 700 016 | KOLKATA | KOLKATA | WEST BENGAL | 700016 | ₹1.6 Cr+₹10.4 L (6.88%) | L2 | Rejected-Finance Quoting highest Rate |
| 3 | L3₹1.6 Cr+₹14.0 L (9.31%)Rejected-Finance | ₹1.6 Cr+₹14.0 L (9.31%) | L3 | Rejected-Finance Quoting highest Rate |
| Sl No | Description | Qty | Unit | JAYBEECO L3 | RASH ELECTRICAL WORKS L2 | DURGAPUR POWER L1 |
|---|---|---|---|---|---|---|
| 1.00SITC of 3-Panel HT-VCB | ||||||
| 1.01 | Supply, Installation, testing & Commissioning of 11 KV 800 A,short-circuit capacity of 26.3 KA for 1 sec, 3-panel HT Gear withVCBs. The Vacuum Circuit Breaker should comply as perIS:13118& IEC:62271-100 for Circuit Breaker & IS:3427 &IEC:62271-200/IEC 694, IEC-61850 for Indoor panel.The HT panel is rated at 11 KV, 3-Phase 800A, BreakingCurrent/short-circuit capacity of 26.3kA for 1 sec, 50c/s andshall be of floor-mounting, sheet steel clad, free-standing metalenclosed air insulated switchgear cubicle with VCB inside. The Vacuum Circuit Breaker is horizontal isolation & horizontal drawout/Vertical isolation & horizontal draw out with 3 compartmentsand is made of 2mm CRCA sheet for load bearing members withvermin & moisture proof along with automatic shutterarrangement for complete isolation of bars, cable sockets & otherlive parts etc. when the removable portion is withdrawn. Thebreaker is arranged for hand operation through front of the panel push buttons & spring charging mechanism and also electricalmotor which will be energized by 230V AC. Closing and trippingcoils are rated for 110V DC to be made available from the station400 V 3 phase 50 C/s A.C. source with remote operationcompatibility. All trip coils shall be of shunt trip type energizedfrom a suitable rectifier condenser source supply is required.There is a remote operation through multi core arrangement forclosing & tripping. The shutter shall be gravity operated | 1 | Item | 15,72,000 ₹15,72,000 Lowest | 16,92,000 ₹16,92,000 | 18,88,560 ₹18,88,560 |
| 1.02INCOMING CIRCUITBREAKER | ||||||
| 1.03a) 3 Phase Star- Star 3 limb draw type line PT 11KV/√3 /110V/√3 , 100VA Cl - 1 with fuses for primary & secondary circuit - 1 no. b) Epoxy Cast, Dual Core Delta/Y-Y CT having CT ratio 150/100/5+5 ,with CORE1:15VA Class-1.0 CORE2 -:15VA, Class- 5P10, STC - 26.3ka for 1 sec- 3 nos. c) Shunt Trip Coil of 110V DC- 1 no. d) LED type indicating lamp for VCB ON/OFF, CB Trip, Springe Charge, Trip Ckt Healthy- 5 nos. e) LED type RYB Phase indication lamps-- 1 set f) Cubicle Panel illumination lamp.- 1 set g) Push Button for Emergency Trip- 1 no. h) Digital Voltmeter with Selector switch- 1 no. i) Digital Ammeter with Selector switch- -- 1 no. j) Digital Multi-Function Meter- 1 no. k) Combined Numerical Relay of SCADA-compatibility incl. providing necessary software with following protection function:-50, 50N, 51, 51N, 37, 46, 46BC, 49, 50BF, 64N,68,86& 95 with programmable in-built LED indicating lamp --- 1 set. (Siemens/ ABB/ Crompton Greaves/ L&T/Alstom) l) Master Trip Relay - 1 no. m) Trip circuit Supervision relay - 1 no. n) Anti pumping relay-- 1 no. o) 6/8 Window Annunciator -- 1 set p) Local Remote/T-N-C/Motor On- Off/Heater On-Off Switch- 4 set. q) MCB for control supply- AC/DC -- 2 sets r) HRC control fuse & link as per scheme-- 1 set s) 110V DC Hooter- 1 no. t) Power Pack with 220V AC input & 110V DC continuous output should be capable of taking O-C-O operation with its battery backup. Charging unit for system, complete with suitable inter-connection with 2.5 sq.mm FRLS insulated copper conductor cable etc. as required -1 set u) Panel space heater with thermostat-- 1 no. v) Panel Illumination lamp. | ||||||
| 1.04OUTGOING CIRCUITBREAKER | ||||||
| 1.05a) Epoxy Cast, Dual Core Delta/Y-Y CT having CT ratio 100- 50/5+5A with CORE1:15VA Class-1.0 CORE2 -:15VA, Class- 5P10. The CT should have at least 25% over capacity than total connected load. STC - 40ka for 1 sec- 3 nos. b) Shunt Trip Coil of 110V DC- 1 no. c) LED type indicating lamp for VCB ON/OFF, CB Trip, Springe Charge, Trip Ckt Healthy- 5 nos. d) LED type RYB Phase indication lamps-- 1 set e) Cubicle Panel illumination lamp.- 1 set f) Push Button for Emergency Trip- 1 no. g) Digital Voltmeter with Selector switch- 1 no. h) Digital Ammeter with Selector switch--- 1 no. i) Digital Multi-Function Meter- 1 no. j) Combined Numerical Relay of SCADA-compatibility incl. providing necessary software with following protection function:-50, 50N, 51, 51N, 37, 46, 46BC, 49, 50BF, 64N,68,86 & 95 with programmable in-built LED indicating lamp --- 1 set. (Siemens/ ABB/ Crompton Greaves/ L&T/ Alstom) l) Master Trip Relay - 1 no.(Make - Siemens/ABB/ Crompton Greaves/L&T/Alstom) m) Trip circuit Supervision relay - 1 no. n) Anti pumping relay-- 1 no. o) 6/8 Window Annunciator -- 1 set p) Local Remote/T-N-C/Motor On- Off/Heater On-Off Switch- 4 set. q) MCB for control supply- AC/DC -- 2 sets r) HRC control fuse & link as per scheme-- 1 set s) 110V DC Hooter- 1 no. t) Panel space heater with thermostat-- 1 no. u) Panel Illumination lamp. | ||||||
| 1.06BUSBAR | ||||||
| 1.07The spacious bus bar compartment is provided on the top of the cubicle. The main bus bar can carry current up to 1000A and are made of electrolytic grade copper & shall be vertically placed one after another. The bus bars should be air insulated but must be HT PVC sleeved & color coded for R-Y-B. No live parts should be accessible. All joints should be covered with monoplast compound and color coded for easy identification. The feeder connection to the bus bars is preferred to be encapsulated. | ||||||
| 1.08Front Door | ||||||
| 1.09The front door of the breaker should not be set as front. High- Voltage door during switching operations, the high-voltage door should remain closed and mechanical interlock should prevent opening of door when the switching device is in service and is switched ON. The position of the withdraw-able section, the CLOSED/OPEN switch position of the switching device, the operating cycle counter and the “spring charged” indication should be visible through pressure-resistant inspection windows in the high-voltage door. The panel front door can be closed with the breaker in isolated position. The degree of protection in the panel is IP-43 as per Indian Standard IS 3427. | ||||||
Tender Value
Refer Docs
EMD Value
₹2.9 L
Closing Date
13 Apr 2026, 11:00 amClosed
Sr.Superintending Engineer
Office of the Sr. Superintending Engineer, Western Electrical Circle , PWD, Purta Bhavan, 1st floor, Burdwan-713103
Sub-Station up gradation electrical work under the campus of Asansol Court Complex, Paschim Bardhaman.....Sub-Station installation Work.
2026_WBPWD_1022660_1
WBPWD/SSEWEC /AED /NIQ-113 /2025-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
120 days
Pashim Bardhaman
Please refer Tender documents.
6 documents required · 6 mandatory
₹2.9 L
Office of the Sr. Superintending Engineer, Western
9 Jun 2026
14 Mar 2026
16 Apr 2026
14 Mar 2026
13 Apr 2026
2 Apr 2026
14 Mar 2026 - 1 Apr 2026
1 Apr 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1SITC of 3-Panel HT-VCB | |||||
| 1.01 | Supply, Installation, testing & Commissioning of 11 KV 800 A,short-circuit capacity of 26.3 KA for 1 sec, 3-panel HT Gear withVCBs. The Vacuum Circuit Breaker should comply as perIS:13118& IEC:62271-100 for Circuit Breaker & IS:3427 &IEC:62271-200/IEC 694, IEC-61850 for Indoor panel.The HT panel is rated at 11 KV, 3-Phase 800A, BreakingCurrent/short-circuit capacity of 26.3kA for 1 sec, 50c/s andshall be of floor-mounting, sheet steel clad, free-standing metalenclosed air insulated switchgear cubicle with VCB inside. The Vacuum Circuit Breaker is horizontal isolation & horizontal drawout/Vertical isolation & horizontal draw out with 3 compartmentsand is made of 2mm CRCA sheet for load bearing members withvermin & moisture proof along with automatic shutterarrangement for complete isolation of bars, cable sockets & otherlive parts etc. when the removable portion is withdrawn. Thebreaker is arranged for hand operation through front of the panel push buttons & spring charging mechanism and also electricalmotor which will be energized by 230V AC. Closing and trippingcoils are rated for 110V DC to be made available from the station400 V 3 phase 50 C/s A.C. source with remote operationcompatibility. All trip coils shall be of shunt trip type energizedfrom a suitable rectifier condenser source supply is required.There is a remote operation through multi core arrangement forclosing & tripping. The shutter shall be gravity operated | 1 | Item | - | - |
| 1.02 | INCOMING CIRCUITBREAKER | - | - | - | - |
| 1.03 | a) 3 Phase Star- Star 3 limb draw type line PT 11KV/√3 /110V/√3
, 100VA Cl - 1 with fuses for primary & secondary circuit - 1 no.
b) Epoxy Cast, Dual Core Delta/Y-Y CT having CT ratio
150/100/5+5 ,with CORE1:15VA Class-1.0 CORE2 -:15VA, Class-
5P10, STC - 26.3ka for 1 sec- 3 nos. c) Shunt Trip Coil of 110V
DC- 1 no. d) LED type indicating lamp for VCB ON/OFF, CB Trip,
Springe Charge, Trip Ckt Healthy- 5 nos. e) LED type RYB Phase
indication lamps-- 1 set f) Cubicle Panel illumination lamp.- 1 set
g) Push Button for Emergency Trip- 1 no. h) Digital Voltmeter
with Selector switch- 1 no. i) Digital Ammeter with Selector switch-
-- 1 no. j) Digital Multi-Function Meter- 1 no. k) Combined
Numerical Relay of SCADA-compatibility incl. providing necessary
software with following protection function:-50, 50N, 51, 51N, 37,
46, 46BC, 49, 50BF, 64N,68,86& 95 with programmable in-built
LED indicating lamp --- 1 set. (Siemens/ ABB/ Crompton
Greaves/ L&T/Alstom) l) Master Trip Relay - 1 no. m) Trip circuit
Supervision relay - 1 no. n) Anti pumping relay-- 1 no. o) 6/8
Window Annunciator -- 1 set p) Local Remote/T-N-C/Motor On-
Off/Heater On-Off Switch- 4 set. q) MCB for control supply-
AC/DC -- 2 sets r) HRC control fuse & link as per scheme-- 1 set
s) 110V DC Hooter- 1 no. t) Power Pack with 220V AC input &
110V DC continuous output should be capable of taking O-C-O
operation with its battery backup. Charging unit for system,
complete with suitable inter-connection with 2.5 sq.mm FRLS
insulated copper conductor cable etc. as required -1 set u) Panel
space heater with thermostat-- 1 no. v) Panel Illumination lamp. | - | - | - | - |
| 1.04 | OUTGOING CIRCUITBREAKER | - | - | - | - |
| 1.05 | a) Epoxy Cast, Dual Core Delta/Y-Y CT having CT ratio 100-
50/5+5A with CORE1:15VA Class-1.0 CORE2 -:15VA, Class-
5P10. The CT should have at least 25% over capacity than total
connected load. STC - 40ka for 1 sec- 3 nos. b) Shunt Trip Coil of
110V DC- 1 no. c) LED type indicating lamp for VCB ON/OFF, CB
Trip, Springe Charge, Trip Ckt Healthy- 5 nos. d) LED type RYB
Phase indication lamps-- 1 set e) Cubicle Panel illumination lamp.-
1 set f) Push Button for Emergency Trip- 1 no. g) Digital Voltmeter
with Selector switch- 1 no. h) Digital Ammeter with Selector
switch--- 1 no. i) Digital Multi-Function Meter- 1 no. j) Combined
Numerical Relay of SCADA-compatibility incl. providing necessary
software with following protection function:-50, 50N, 51, 51N, 37,
46, 46BC, 49, 50BF, 64N,68,86 & 95 with programmable in-built
LED indicating lamp --- 1 set. (Siemens/ ABB/ Crompton
Greaves/ L&T/ Alstom) l) Master Trip Relay - 1 no.(Make -
Siemens/ABB/ Crompton Greaves/L&T/Alstom) m) Trip circuit
Supervision relay - 1 no. n) Anti pumping relay-- 1 no. o) 6/8
Window Annunciator -- 1 set p) Local Remote/T-N-C/Motor On-
Off/Heater On-Off Switch- 4 set. q) MCB for control supply-
AC/DC -- 2 sets r) HRC control fuse & link as per scheme-- 1 set
s) 110V DC Hooter- 1 no. t) Panel space heater with
thermostat-- 1 no. u) Panel Illumination lamp. | - | - | - | - |
| 1.06 | BUSBAR | - | - | - | - |
| 1.07 | The spacious bus bar compartment is provided on the top of the
cubicle. The main bus bar can carry current up to 1000A and are
made of electrolytic grade copper & shall be vertically placed one
after another. The bus bars should be air insulated but must be
HT PVC sleeved & color coded for R-Y-B. No live parts should be
accessible. All joints should be covered with monoplast compound
and color coded for easy identification. The feeder connection to
the bus bars is preferred to be encapsulated. | - | - | - | - |
| 1.08 | Front Door | - | - | - | - |
| 1.09 | The front door of the breaker should not be set as front. High-
Voltage door during switching operations, the high-voltage door
should remain closed and mechanical interlock should prevent
opening of door when the switching device is in service and is
switched ON. The position of the withdraw-able section, the
CLOSED/OPEN switch position of the switching device, the
operating cycle counter and the “spring charged” indication
should be visible through pressure-resistant inspection windows
in the high-voltage door. The panel front door can be closed with
the breaker in isolated position. The degree of protection in the
panel is IP-43 as per Indian Standard IS 3427. | - | - | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 17.49 MB
BOQ_2513325.xls
BOQ • 0.39 MB
new2911.pdf
Additional Documents • 0.51 MB
MakeList.pdf
Tender Documents • 0.12 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .