EE (SDW) VII
NSTP Coronation Pillar Delhi 110009
Renovation of LT Panel Board and allied electrical works at Bharola SPS
2022_DJB_227908_1
NIT No 10 (2022-23)
Open Tender
Miscellaneous Works
Works
30 days
NSTP Coronation Pillar
Please refer Tender documents.
4 documents required · 4 mandatory
₹500
Online
₹6,600
5 Sept 2022
18 Aug 2022
26 Aug 2022
18 Aug 2022
26 Aug 2022
18 Aug 2022
Renovation of LT Panel installed at Bharola SPS by carrying out the following works: Supply of Digital ammeters, 3 digit, AC, 50 Hz, Size 96 mm2, Make: AE / L&T / BCH/ Schneider / C&S
Supply of Digital Voltmeter, 3 digit, AC, 50 Hz, Size 96 mm2, Make: AE / L&T / BCH/ Schneider / C&S
Supply of Indicating Lamps of Red, Yellow, Green Colour Make: Vaishno/ L&T / BCH / Schneider / C&S
Supply of Indicating Lamps of Blue Colour Make: Vaishno/ L&T / BCH / Schneider / C&S
Supply of Push Button for ON/OFF. Make: Vaishno/ L&T / BCH / Schneider / C&S
Supply of Power Contactor 110 Amp, AC3, 3 Pole, 220 Volt, Make: GE / L&T / BCH/ Schneider / C&S
Supply of Power Contactor 90 Amp, AC3, 3 Pole, 220 Volt, Make: GE / L&T / BCH/ Schneider / C&S
Supply of Thermal Over load Relay, 54-65 Amp, Make: GE / L&T / BCH/ Schneider / C&S
Supply of Star Delta Timer, Make:L&T / BCH/ Schneider / C&S
Supply of 125 A, 36 KA, 3 Pole MCCB with spreader terminals and adjustable thermal megnatic release Make: L&T / BCH/ Schneider
Supply of 6 Amp, 10 Ka, SP MCB. Make : L&T / BCH/ Schneider
Dismantling of the existing defective switchgears and measuring instruments installed in the LT Panel.
Complete dusting of the LT Panel, cleaning of contact points, decabonising of joints, alighnment of doors, checking of all nuts & bolts etc as required at site.
Fixing of the above supplied MCCB’s, voltmeters, ampere meters & indicating lamps in the panel board. Making their complete wiring connections by supply and laying of copper flexible wire as per requirement. The job also includes replacement of defective control wiring
Renovation of allied Electrical Works by carrying out the following works: Supply of 380 mm dia, 900 rpm, exhaust fan. (DJB SOR 2022 Code 20.2.2) Make: Amonard / Khaitan / Crompton / Havells.
Supply of 450 mm sweep Air Circulator fan. (DJB SOR 2022 Code 20.3.1) Make: Amonard / Khaitan / Crompton / Havells.
Supply of 1200 mm sweep ceiling fan. (DJB SOR 2022 Code 20.1.2) Make: Amonard / Khaitan / Crompton / Havells.
Supply of 45 watt, pressure die-cast aluminium IP66 LED street light luminaries. Make: Bajaj/ Havells/ Other DJB Approved make DJB SOR 2022 Code 19.10.5
Supply of Surface and wall mounted 4 feet long, 24 W 6500 K LED batten, extruded aluminium housing provided for efficient heat dissipation with polycarbonate diffuser & integrated electronic driver. (DJB SOR 2022 Code 19.3.1). Make: Osram / Havells / Bajaj / Crompton.
Supply of SMC junction boxes anti-corrosive water resistant, UV protected, High temp resistant, weatherable and suitable for all kinds of climatic conditions. Self-colour fire retardant and high dielectric strength maintenance free Make: Bajaj / Hensel / C&S / Binani / Syntex /Other DJB approved make
Supply of Connection Box with connection plate for the 40 HP KEC make three phase induction motor with Frame No SC200L.
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep (Electrical DSR 2018 : Item No 1.50.1.) The job also includes fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. (Electrical DSR 2018 : Item No 1.51)
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. DJB SOR 2022 Code 31.44
Supplying and fixing of 32 mm dia X 2.00 metres long G.I. pipe (medium class) bracket for mounting of fluorescent / HPMV / HPSV street light fitting on pole including bending the pipe to the required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts, bolts and washer, painting the flat iron with primer and finish paint etc. as required. DSR-2018 ITEM CODE:- 12.34
Installation of junction boxes on the each pole / wall with the help of clamps, nut & bolts etc. The junction boxes should have Mini SP C-series MCB of 6 A
Fixing the new 45 W LED street light on the arm with the help of nut & bolts etc, including its connection with copper conductor single core wire up to street light to junction box (work including making arrangement of tolls & tackles for carrying out the work and taking all safety measures during work at site). Make of wire : Gloster Universal/ / Grandly/ DJB approve make
Supply of 2 core 10 Sq mm armored aluminium conductor PVC insulated and PVC sheathed / XLPE cable for working voltage upto 1.1 KV. Make:- Gloster/ ICL/ ICC/ Universal/ CCI/ Havells/ Grandly
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on wall surface as required. Upto 35 sq. mm DJB SOR 2022 Code 37.7.1
Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 & 15/16 A socket outlet and 15/16 A piano type switch, connections, painting etc. as required. DJB SOR 2022 Code 31.30
Supplying and fixing following piano type switch/ socket on existing switch box/ cover including connections etc. as required. DJB SOR 2022 Code 31.23 5/6 A switch
3 pin 5/6 A socket outlet
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. DJB SOR 2022 Code 31.14 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. DJB SOR 2022 Code 31.17 2 X 1.5 sq. mm
2 X 2.5 sq. mm
RP Electricals
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .