Loading…
Loading…
Tender Value
₹47.6 L
EMD Value
₹95,120
Closing Date
30 Jul 2026, 6:00 pm4d left
GE (West) Jabalpur
Garrison Engineer (West) Jabalpur Supply Marg Post Box No. 54 Jabalpur Cantt-482001 (MP)
SPL REPAIR TO REPLACEMENT EXTERNAL SECURITY/STREET LIGHTS, CABLES, JUNCTION BOXES WITH STEEL TUBULAR POLES AND ALLIED WORKS UNDER AOR OF GE (WEST) JABALPUR
2026_MES_749766_2
8994/E8
Open Tender
Civil Works
Item Rate
180 days
GE (West) Jabalpur
As per tender documents
6 documents required · 6 mandatory
₹500
GE (West) Jabalpur
₹95,120
9 Jul 2026
9 Jul 2026
6 Aug 2026
10 Jul 2026
30 Jul 2026
23 Jul 2026
10 Jul 2026 - 18 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Dismantling of steel poles/struts of any size complete all as specified and as directed. | 10 | Each | - | - |
| - | Taking down old UNSV earthing of any type any size complete all as specified and as directed. .
Note: Excavation & earth work where required shall be measured & paid separately under relevant items. | 10 | Each | - | - |
| - | Taking down of old unsv cable of any type and any size for repair or replacement incl pipes & bricks etc complete all as specified and directed by engr-in-charge.
Note: Excavation & earth work where required shall be measured & paid separately under relevant items. | 4,550 | RM | - | - |
| - | Supply and erecting steel tubular poles complete with cast iron base plate, finial taper plug , bolts Nuts & screws complete all as specified type 410SP 31 of 9 mtr long including painting of pole with one coat red oxide primer & two coats of aluminum paint & emedded portion shall be painted with two coat of black bituminous paint all as specified and directed.
Note : Pole shall be numbered with yellow shade on black base using synthetic enamel paint having height of words exceeding 5 cm complete all as specified and as directed. | 10 | Each | - | - |
| - | Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level,connected to galvanised iron strip 32×6mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion including the material and labour of the following : -
(a) Excavation and earth work for drilling hole for electrode in any type of Soil.
(b) PCC pit in cement concrete 1:2:4 type B-1, Pre cast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than1.87 Kg/ Sq meter.
(c) Funnel with watering pipe of GI 20 mm nominal bore light grade and lugs etc complete all as specified and directed
(d) 15 mm nominal bore medium grade GI protection pipe 5 meter long for protection of earthing lead complete all as specified and directed.
(e) Requisite quantity of common salt and charcoal.
(f) Testing of earthing. | 10 | Each | - | - |
| - | Supply , laying and testIng cable XLPE insulated , screened, PVC bedded , galvanized , steel strip or wire armoured, electric power cables ( Heavy duty ) 1100 volts grade with stranded aluminium conductor of size 4 core 10 Sqmm complete all as specified and directed by Engineer in charge | 1,400 | RM | - | - |
| - | Supply , laying and testIng cable XLPE insulated , screened, PVC bedded , galvanized , steel strip or wire armoured, electric power cables ( Heavy duty ) 1100 volts grade with stranded aluminium conductor of size 4 core 16 Sqmm complete all as specified and directed by Engineer in charge | 1,250 | RM | - | - |
| - | Supply , laying and testIng cable XLPE insulated , screened, PVC bedded , galvanized , steel strip or wire armoured, electric power cables ( Heavy duty ) 1100 volts grade with stranded aluminium conductor of size 4 core 25 Sqmm complete all as specified and directed by Engineer in charge | 1,050 | RM | - | - |
| - | Supply , laying and testIng cable XLPE insulated , screened, PVC bedded , galvanized , steel strip or wire armoured, electric power cables ( Heavy duty ) 1100 volts grade with stranded aluminium conductor of size 4 core 50 Sqmm complete all as specified and directed by Engineer in charge | 850 | RM | - | - |
| - | Supply, fixing, connecting and testing of Automatic Street light switch using infrared Sensor based Nature Switch for automatic switching of street lights, Nature switch operation should be based on Natural light lux level. Required illumination level for switching on is < 30 lux and for switching off > 10 lux. The sensor should also have part night operation facility for 4 - 12 hours. The sensor alongwith suitable power contactor, incoming-outgoing MCBs should be enclosed in a pole/wall mounted hensel enclosure made out of Rust proof, electric shock proof, termite proof and FR grade SMC junction box conforming to IP-66, The circuit should be suitable enough to take 8 KW single phase load with contactor 63 Amps conforming to IEC-60947-4-1/IS-13947-4-1 & incoming and outgoing MCBs of rating 63 Amps conforming to IEC-60898/IS-8828 and circuit wiring of minimum 16sqmm coper conductor wire in and including providing of 50x6mm flat iron clamp, necessary nuts and bolts complete incl taking down of existing arrangement complete all as specified and as directed. | 5 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.24 MB
8994GP.pdf
Tender Documents • 0.43 MB
Tender8994SPPS.pdf
Tender Documents • 1.28 MB
BOQ_870719.xls
BOQ • 0.30 MB
SCH8994.pdf
Additional Documents • 0.09 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].