| 1 | L1₹11.6 CrAccepted-AOC | ₹11.6 Cr | L1 | Accepted-AOC Being lowest bidder |
| 2 | L2₹12.0 CrRejected-Finance | ₹12.0 Cr | L2 | Rejected-Finance Not Being Lowest Bidder |
| 3 | Rejected-Technical | - | - | Rejected-Technical Not Recommended Due to adverse remarks in the WLR circulated by HQ CENC for QE Mar 2025. |
| Sl No | Description | Qty | Unit | DES RAJ AND SONS BUILDERS PVT LTD L2 | SHIV CHARAN GUPTA AND SONS L1 |
|---|---|---|---|---|---|
| 1.00NOTE: Schedule ‘A’ Part - I to Part -XII are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only. | |||||
| 1.01 | Total amount of Sch 'A' Part - I (BUILDINGS) | 1 | LUMP SUM | 7,33,26,775.63 ₹7.3 Cr | 7,20,02,172.45 ₹7.2 Cr |
| 1.02 | Total amount of Sch 'A' Part - II (SITE CLEARANCE WORKS) | 1 | LUMP SUM | 14,42,026.2 ₹14.4 L | 13,33,874.24 ₹13.3 L |
| 1.03 | Total amount of Sch ‘A’ Part - III (PROTECTIVE WORK) | 1 | LUMP SUM | 6,91,751.33 ₹6.9 L | 8,28,581.27 ₹8.3 L |
| 1.04 | Total amount of Sch ‘A’ Part - IV (ROAD WORKS) | 1 | LUMP SUM | 86,20,064.12 ₹86.2 L | 87,10,012.61 ₹87.1 L |
| 1.05 | Total amount of Sch ‘A’ Part - V (SEWAGE DISPOSAL WORKS) | 1 | LUMP SUM | 2,02,247.01 ₹2.0 L | 2,61,958.03 ₹2.6 L |
| 1.06 | Total amount of Sch ‘A’ Part - VI (INTERNAL WATER SUPPLY WORKS) | 1 | LUMP SUM | 46,470.27 ₹46,470.27 | 56,963.56 ₹56,963.56 |
| 1.07 | Total amount of Sch ‘A’ Part - VII (INTERNAL ELECTRIC SUPPLY WORKS) | 1 | LUMP SUM | 14,61,794.81 ₹14.6 L | 16,42,466.09 ₹16.4 L |
| 1.08 | Total amount of Sch ‘A’ Part - VIII ( EXTRNAL WATER SUPPLY WORKS) | 1 | LUMP SUM | 5,34,052.66 ₹5.3 L | 5,56,709.44 ₹5.6 L |
| 1.09 | Total amount of Sch 'A' Part - IX (EXTRNAL ELECTRIC SUPPLY WORKS) | 1 | LUMP SUM | 1,00,37,126.16 ₹1.0 Cr | 78,56,647.03 ₹78.6 L |
Tender Value
₹11.8 Cr
EMD Value
₹9.1 L
Closing Date
20 Aug 2025, 6:00 pmClosed
HQ CE Leh Zone
HQ CE Leh Zone
PROVN OF KEY LOCATION PLAN KLP FOR ZONAL WORKSHOP AT LEH PH I OF 3 PHASES UNDER GE I P NO 1 LEH
2025_MES_707619_1
180103/E8
Open Tender
Civil Works
900 days
LEH
As per Tender documents
8 documents required · 8 mandatory
₹3,000
Yes
GE (I) (P) No 1, Leh
₹9.1 L
Yes
HQ CE Leh Zone
30 Sept 2025
10 May 2025
27 Aug 2025
10 May 2025
20 Aug 2025
21 Jul 2025
10 May 2025 - 17 May 2025
20 May 2025
Amount
NOTE: Schedule ‘A’ Part - I to Part -XII are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only.
Total amount of Sch 'A' Part - I (BUILDINGS)
Total amount of Sch 'A' Part - II (SITE CLEARANCE WORKS)
Total amount of Sch ‘A’ Part - III (PROTECTIVE WORK)
Total amount of Sch ‘A’ Part - IV (ROAD WORKS)
Total amount of Sch ‘A’ Part - V (SEWAGE DISPOSAL WORKS)
Total amount of Sch ‘A’ Part - VI (INTERNAL WATER SUPPLY WORKS)
Total amount of Sch ‘A’ Part - VII (INTERNAL ELECTRIC SUPPLY WORKS)
Total amount of Sch ‘A’ Part - VIII ( EXTRNAL WATER SUPPLY WORKS)
Total amount of Sch 'A' Part - IX (EXTRNAL ELECTRIC SUPPLY WORKS)
Total amount of Sch ‘A’ Part - X (LIGHTENING PROTECTION WORKS)
SCH 'A PART - XI (Miscellaneous B/R and E/M works for Sch 'A' Part-II to Part-X) Note: This schedule is not pre-priced by MES and the rate indicated as "Rs 0.00" under Col 5 signifies this fact only
M&L for 2mm thick thermoplastic paint after preparation of new bituminous surfaces of road by scratching spots,oils,greasy spots marking material strips confirming to british specification 3762 with 20 % glass beads having reflective index of 1.5 mm,75 % sptrical with indigenous or for foundation plan having sufficient strength to withstand heavy load without deformation and having softening point 25 to 30 of area in width of n exc 15 cm strip in white or golden yellow colour according to IRC 35-1970,complete all as specified and as directed by Engr-in-charge
S&L 30 users LLDPE septic tank designed to carry sewage and sludge water , excavation in any type of soil, PCC 1:4:8 below foundation, vent shaft , connection etc conventional type complete all as specified and shown on drawings.
S&L 10 users LLDPE septic tank designed to carry sewage and sludge water , excavation in any type of soil, PCC 1:4:8 below foundation, vent shaft , connection etc conventional type complete all as specified and shown on drawings.
Construction of soakage well 2.4m internal dia and 3.00m effective depth including excavation in any type of soil , foundation in PCC 1:3:6 type C-1 ( using 20mm graded crushed stone aggregates ), PCC Block honeycomb/ solid masonry in cement mortar (1:4) RCC M-30 design Mix cover Slab filled with stone boulders including intersepting chamber screen chamber and disposal of soil complete all as specified and shown on drawings.
Construction of soakage well 1.2m internal dia and 3.00m effective depth including excavation in any type of soil , foundation in PCC 1:3:6 type C-1 ( using 20mm graded crushed stone aggregates ), PCC Block honeycomb/ solid masonry in cement mortar (1:4) RCC M-30 design Mix cover Slab filled with stone boulders including intersepting chamber screen chamber and disposal of soil complete all as specified and shown on drawings.
Supply, Install, lowering, testing, and commissioning of submersible openwell pumping sets, centrifugal, electric driven,minium discharge of 23.46 LPM at 33 mtr head motor capacity minium 3 HP including 3 HP Starter complete all specified and directed.(One main + one standby)
Supply and fix submersible copper conductor cable 3 core, 4 sqmm 1100 volt flat industrial grade including nylon binding wire and accesories to clamp with column pipe at two places to each column pipe.
M&L for Construction of brick masonary valve pit of size.0.9X0.9X1.8 mtr (internal diamensions) including excavation and earth work in any type of soil, PCC 1:4:8 type B-2 in foundation brick work in CM 1:4, 15mm thick plastering in CM 1:4 internally and flush pointing externally in same mortar as the work process angle iron frame 40X40X6mm, with 3mm thick MS sheet cover with 12 mm dia handle and locking arrangement (including lock and two Keys) and two coats of synthetic enamel paint over a coat of red oxide primer, filling saw dust into the pit and providing extension rod 0.6 m long to operate sluice valve from top and welding it with sluice valve spindle .
Supply and fixing insulation on tubing of for 25 mm dia pipe and 13mm thick of nitrile rubber complete all as specified and directed.
S&F tracer wire 20W per mtr over pipe line/valves above freeze line complete all as directed by Engineer-in-Charge.
Supply and fixing Aluminium Cladding of 28SWG thickness on insulated pipe having 25 mm dia and 13mm thick nitrile rubber tube complete all as specified and directed.
Supply, installation, testing and commissioning out door type cubical panel board outer shell made out of 3.15 mm thick MS sheet and inner shell made out of 3.15 mm thick CRCA sheet and MS angle of suitable size on PCC 1:2:4 type B-1 platform frame factory fabricated with front and back open able double door system louvers and air vent gasket for natural flow of air “U” type gasket shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, factory fabricated (Factory approved from CPRI) having modern fabrication and followed by powder coated three phase powder coat painting comprising of the following:- (Feeder pillar No.2) (a) ACB 415 volts, 3P, 630 Amps 50 KA(O/G)-01 No (b) MCCB 415 volts 4P, 63 Amps 25 KA (O/G)-04 Nos (Gate office, Fuel Injecction & Ancillary section, Tech store, receipt and inspection, office for officers, spare) (c) MCB TP 32 Amps 25 KA (O/G)-06 Nos (Specilist-02) (d) MCB TP 32 Amps 16 KA(O/G)-02 Nos (Fuel Injection-02) (e) MCB TP 20 Amps 16 KA (O/G)-14 Nos (Ancillary-02, Specilist Shop-14) (f) MCB TP 16 Amps 10 KA (O/G)-02 Nos (Battery Charging Shop-02) (g) Bus bar chamber with and including aluminium strips (set 4 Nos) suitable for 1000 amps duly mounted on porcelain insulators -01 set (h) Digital Amp meter 3 ph programmebale type with suitable CT's 800 Amp - 01 Set (j) Digital volt meter 3 ph programmebale type suitable for 500 volts-01 set (k) LED Phase indicator R, Y&B -01 set
(f) Bus bar chamber with and including Aluminium strips (set 4 nos) suitable for 1000 amps duly mounted on porcelain insulators-01 Set (g) Digital Amp meter 3 ph programmebale type with suitable CT's 800 Amp - 01 Set (h) Digital volt meter 3 ph programmebale type suitable for 500 Volt -01 Set (j) LED Phase indicator R, Y&B -01 Set
Supply, installation, testing and commissioning out door type cubical panel board outer shell made out of 3.15 mm thick MS sheet and inner shell made out of 3.15 mm thick CRCA sheet and MS angle of suitable size on PCC 1:2:4 type B-1 platform frame factory fabricated with front and back open able double door system louvers and air vent gasket for natural flow of air “U” type gasket shall be used to make the outer shell completely vermin proof .suitable for 3 phase 4 wire 415 Volt, 50 Hz, factory fabricated (Factory approved from CPRI) having modern fabrication and followed by powder coated three phase powder coat painting comprising of the following:- (Feeder pillar No.1) (a) MCCB 415 volts 3P, 125 Amps 25 KA - 01 No (Incomer) (b) MCCB 415 volts 4P, 63 Amps 25 KA(O/G)-02 Nos (Workshop area, Inspection pit, radar component shop) (c) MCB 415 volts 3P, 32 Amps 25 KA(O/G)-01 No (Repair Bay) (d) MCB 415 volts 3P, 16 Amps 25 KA(O/G)-03 Nos (Workshop area, Inspection pit - 02) (e) MCB 16 Amps 10 KA (O/G)-04 Nos (Servicing bay, Sanitary Annexe and stair case - 02 Nos, Repair Bay) (f) Bus bar chamber with and including Aluminium strips (set 4 nos) suitable for 200 Amps duly mounted on porcelain insulators-01 Set
(g) Digital Amp meter 3 ph programmebale type with suitable CT's 200 Amp - 01 Set (h) Digital volt meter 3 ph programmebale type suitable for 500 Volt -01 Set (j) LED Phase indicator R, Y&B -01 Set
Supply, installation, testing and commissioning out door type cubical panel board outer shell made out of 3.15 mm thick MS sheet and inner shell made out of 3.15 mm thick CRCA sheet and MS angle of suitable size on PCC 1:2:4 type B-1 platform frame factory fabricated with front and back open able double door system louvers and air vent gasket for natural flow of air “U” type gasket shall be used to make the outer shell completely vermin proof .suitable for 3 phase 4 wire 415 Volt, 50 Hz, factory fabricated (Factory approved from CPRI) having modern fabrication and followed by powder coated three phase powder coat painting comprising of the following:- (Main LT Panel for 800 TR) (a) ACB 4 Pole, 415 V, 50 KA with Thermal Magnetic Release (Adjustable type) of capacity 2000 Amps (incoming) - 01 No (Incomer) (b) ACB 415 volts 3P, 1600 Amps 50 KA(O/G)-02 Nos (for DG Set Panel, Spare) c) MCCB 415 volts 3P, 630 Amps 50 KA(O/G)-01 Nos (for Feeder Pillar No.2) (d) MCCB 415 volts 3P, 25 Amps 16 KA(O/G)-01 Nos (for Pump) (e) Bus bar chamber with and including Aluminium strips (set 4 nos) suitable for 3000 amps duly mounted on porcelain insulators-01 Set
(f) Digital Amp meter 3 ph range 0-2500 Amp programmebale type with suitable CT's -01 Set (g) Digital volt meter 3 ph programmebale type suitable for 500 Volt -01 Set h) LED Phase indicator R, Y&B -01 Set
S&F in repairs, installation, commissioning and testing Junction boxes made of Lid PC and base is polystyrene. Junction Boxes Size 217 x 253 x 115 mm in Grey RAL 7035 colour. Junction Box IP 65 Thermoplastic PS Polystyrene weatherproof Junction Box with multi level knockouts for cable glands in different sizes. The pre-moulded knockouts shall be available on top and bottom of the junction box to enable cable entries from both direction. The junction box shall have an optional cable entry at the bottom up Cable Size 25 Sq mm of the box via pre-moulded knockout to enable pole mounting option. Lid fasteners self closed will be tool operated. it will be sealable with accessories. The junction box shall have elongated holes inside them for wall/pole mounting provision. The junction box with 4 Pole Terminal Strip and MCB SP 6 Amp 10 KA C Curve for LED light. The junction box shall fulfill the following standards Weatherproof : Rainwater proof, temperature resistant. IEC 60670-22 : Particular requirements for connecting boxes and enclosures. IEC 60695 – 2 – 11 : Flame – retardant & Self-extinguishing. Glow Wire tested at minimum 750 deg C.
IEC 60529 : IP 65 degree of protection. UV Resistant in accordance with IEC 61 439-1, Clause no 8.4.4 The Junction Box with Suitable Glands 3 Nos with each and chromium plated clamps, nut bolts complete all as per manufacturer’s instructions. Make : Cat Part :- KG 9003 of Hensel/Siemens/GE Power/Schneider/ L&T/ABB. Manufacturer should submit routine test certificate of CJB/PJB
Supply, Installation, Testing and Commissioning of Automatic Power Factor Correction unit 500KVAR (output) @440 Volt Ac. The APFC unit shall comply with IEC 61439-1&2 & IEC 61921, IS-16636-2017. The degree of Protection of enclosure system of the APFC Panel shall be minimum IP-4X in accordance with IEC 60529. The APFC Panel shall be indoor type conforming to IS 13341:1992 and IS 13440:1993 floor mounted design, weather, dust and vermin proof suitable for weather conditions of Leh. The Equipment shall be comprising of the following:- (a) Insulated bus bar pan assembly made from Aluminum and of rated capacity as per TTA design. The short circuit withstand capacity shall be 50KA/1Sec(low) for the mains bus bar and the rated impulse withstand voltage shall be 6KV. (b) The incomer of the APFC Panel shall be a 1000 Amp, ACB, 3P, 50KA TMD type With O/L & S/C protection, Ics=100%, MCCB shall have standard extended Rotary handle, spreaders, phase barrier, ACB shall be of certified design conforming to IEC 60947-1,2 & 3 proposed capacitor configuration shall be 100KVAR x 3 + 50KVAR x 2 + 25KVAR x 3 + 10 KVAR x 2 + 5 KVAR x 1. APFC relay shall be automatic microprocessor based 12 steps relay.
(c) Capacitor Units:- The Capacitor unit shall be metalized polypropylene film with Zn/ Al alloy. The capacitors shall be encapsulated in an aluminum can. The Capacitor unit shall have a rated voltage of 525V and shall have a maximum over current capacity of 2.5 In. The capacitor unit shall have a built in 3 phase over pressure protection and shall have discharge resistors (50V in 1 min) factory fitted and shall be tamper proof. Capacitor Tolerance -5%,+10%. Maximum permissible over voltage 1.1xUn,8 h every 24h. The capacitor unit shall be of Certified design confirming to IS-13340-1993,13341-1992 & IEC-60831-1&2. (D) Short circuit and Overload Protection :- Each stage of the APFC Panel shall have a suitably rated MCCB for short circuit and overload protection. The Over Current setting shall be adjustable & Breaking capacity Ics-36KA. The MCCB Shall be of certified design confirming to IEC 60947-1,2 &3.
(E) PF Regulator /APFC Relay: Advance Range PF Regulator/micro-processor based APFC Relay having multiple steps with a LCD Display, Voltage Range 90V 550V,50/60Hz, CT Input:1A/5A with a built in RS485 communication port. The PF Regulator shall be of certified design confirming to IEC 61326, should also have an energy server which would collect, store and provides web access and visualization toVarious energy parameters and enable remote supervision from BMS to ensure Maximum utilization, enable remote commissioning/trouble shooting of the capacitor bank, the energy server should monitor and display the following parameters remotely through a web page. Status of stages (open/close/faulty). Real time capacitance value of the connected stage. Initial capacitance value. Number of operation of stages (stage utilization/operation), energy parameter like: I.V.P.Q.S. operating PF, Target PF, Operating Temperature, Max Temperature, %THD V, % THD 1, Display of alarms, Trending curves of historical recorded data. (F) Stage Capacitor: The capacitor duty contactors shall be rated for 230 Volts AC and shall be 3 Pole type and shall be employed for switching ‘on’ and switching ‘off’ operations in capacitor banks. The contactor shall be AC-3 duty Type. The contactor shall be of certified design confirming to IEC 60947-1& 4-1.
(G) Ventilating fans if required shall be used to dissipate the heat produce by the capacitor bank components like the capacitor units, reactors, contactors, breakers etc In addition to above the APFC Panel shall be provided with Mains indicator in each phase, Capacitor On/Off Indicators, Start/Stop press button switches andauto/manual rotary switch for each stage capacitor Bank. Note:-The APFC Panel described as above complete in all respect as per specification enclosed, up to the entire satisfaction of engineer In Charge.To ensure safety, reliability and accountability of component co ordination, all the major capacitor bank components such as capacitor units, de tuning reactors, PF controllers, circuit breakers, contactors and the enclosure system called for in this specification should preferably be from a single manufacturer. The OEM shall preferably manufacturer PFC components and switchgear.
Labour for boring underground upto 100 mm bore for road crossing 3 mtr to 10 mtr not exceeding 1.5 mtr in depth for laying of electric cable and GI tubing in soft/loose soil complete all as specified.
Design, supply, erect test and commissioning of electrically operated over head traveling crane 2 MT capacity double girder type class-II with necessary steel structure track rails for LT & CT, electric motors and gear driven, long, cross travel/hoisting mechanism, VVVF control drives for normal and micro speed control (micro motion only for hoist), operated from floor with pendent push button controls, movable, independent of crab position including provision of track rail/square bar for a bay length 18.5 mtr approx for long travel and PVC coated DSL shrouded conductor system 415 volts, 3 phase, 4 wire of appropriate capacity including current collector, supporting brackets, insulators and other standard fixtures and fittings carriage with double flanged cylindrical wheels, standard hook black, steel wire rope, service platform, ladder, suitable brakes for all motions flexible trailing cable system for complete length with all standard fittings and fixtures, buffers including all safety devices and interlocking etc to meet the following requirment conforming to IS:3177, IS-807, IS-2148, IS-3938, IS-2062 and IS-3815 complete all as specified and directed:-
(i) Cross span : 8 m + 5% (ii) Long span : 18.5 m + 5% (iii) Class of duty : Class-II (indoor) Crane as per IS:2148 with latest amendments (iv) Location : Indoor (v) Controls : From floor level through pendent push button (vi) Lift : 5.00 m (approx) (vii) LT motor : Twin drive of suitable capacity each with gear box (viii) CT motor : of suitable capacity ((x) Long travel speed : 15 metre/minute (approx)ix) Hoisting motor : of suitable capacity (xi) Main Hoisting speed : 04 metre/minute (xii) Slow Hoisting speed : 0.2 metre/minute (Achieve through AC drive) (xiii) Cross travel speed : 15 metre/minute (approx) (xiv) Main Girder : Box type xv) Wheels : MS steel with bronze coating on tread
(xvi) Operation : Pendent push button switch from floor (xvii) Power supply : 415 volts 3 phase (xviii) Accessories for electric supply : Festoon type flame proof cables for LT& CT motion (xix) Speed control of Hoist motor shall be through VVVFD. (xx) 2 Nos of light in each crane, Auto stop facility, Anti collision device (xxi) Gantary rail ISMB of minimum size as recomended by manufacturer. alongwith suitable size of square bar welded on top of ISMB including M.S. base plate 16mm thick for fixing in column with suitable size of bolt, nuts , washers, total length of gantary as suitable for span for EOT crane.
(a) BRIDGE:- It shall be as per IS-807/IS-3177/IS-800 and standard I beam of MS rolled steel sections bolted to end bridge. Make:- SAIL/TISCO/ESSAR. (b) END CARRIAGES:- Box type and fabricated from rolled section. (c) LT WHEELS:- Two Nos, staright tread/type, EN-8 forged steel, double flanged LT wheels to be provided in each of the two end carriage, These wheels shall be supported on steel axles. (d) PINION/AXLES:- Made from EN-9, heat treated carbon alloy steel. (e) GEARS:- As per IS-4460, made from EN-8 and supported on ball bearing. (f) BEARINGS:- Two Nos heavy duty sealed ball bearings to be provided in each wheel for smooth fuctioning. (g) HOOKS:- Conform to IS-15560 made from forged steel C-20, C-30 or equivalent single shank, swivelling type in construction. (h) HOIST:- The hoisting drum shall be manufactured from mild steel and shall be driven by half an hour rating Crane duty. Squirrel cage induction motor through well cut, efficient gearing.
(xii) Quoted unit rate is deemed to include provision of suitable ladder (02 Nos) from FFL to crane level for easy access to crane. (xiii) One number of crane should be installed in in bldg have common long travel (18 mtr) (xiii) Suitable size of LT Walkway (one side) should be installed & Full length platform on one side of the bridge grinder & 02 short platforms another side.
Supply and fixing LED blub full dum 7 watt with rechargeble type, retrofit all as specified and directed by Engr-in-charge .
S&F Double door three phase prewired distribution board vertical DB TPN 6 way with acrylic door made out of CRCA sheets 1.6 mm thick, phosphatised powder coated with copper Bus Bar 250 Amps, 415 V,IP 43/IK09, Earth Stud, Din Rail, Polymide terminal blocks for incoming and outgoing circuits, inbuilt loose wire box ,ground terminal blocks ,duly prewired with thimbled flame retardant copper conductors and poly layer for protection in and including MCCB 4 pole 160 Amp rating repturing capacity 25 KA (Note:- Single Phase MCBs are to be measured and paid for seperately)
S&F Double door three phase prewired distribution board vertical DB TPN 6 way with acrylic door made out of CRCA sheets 1.6 mm thick, phosphatised powder coated with copper Bus Bar 200 Amps, 415 V,IP 43/IK09, Earth Stud, Din Rail, Polymide terminal blocks for incoming and outgoing circuits, inbuilt loose wire box ,ground terminal blocks ,duly prewired with thimbled flame retardant copper conductors and poly layer for protection in and including MCCB 4 pole 100 Amp rating repturing capacity 25 KA (Note:- Single Phase MCBs are to be measured and paid for seperately)
Supply and fix 16 Amps with inclosure industrial insulated plug & socket, 3 phase 415 volt, including 16 Amps TPN & internal wiring all as specified and directed by Engr-in Charge.
Supply and fix 20 Amps with inclosure industrial insulated plug & socket, 3 phase 415 volt, including 20 Amps TPN & internal wiring all as specified and directed by Engr-in Charge.
Supply and fix 32 Amps with inclosure industrial insulated plug & socket, 3 phase 415 volt, including 32 Amps TPN & internal wiring all as specified and directed by Engr-in Charge.
S&F 9/10 Watt Led LED Bulk head fitting complete IP 66 with IK 09 protection, High Presure die cast aluminium housing and milky diffuser single phase 230V all as specified and directed.
SCH 'A PART - XIII (CENTRAL HEATING SYSTEM) Note: This schedule is not pre-priced by MES and the rate indicated as "Rs 0.00" under Col 5 signifies this fact only
Electric Hot Water Generator : Supply, installation, testing and commissioning of package type electric Hot Water generator constructed out of MS sheet having top open-able cover for easy access and removal of heaters. The HWG shall be suitable for indoor mounting. The generator shall be provided with 50mm thick fibre glass insulation 32 kg density finished with 0.8mm / 22G aluminium cladding sheet. The generator shall have electrical capacity of 250 kW. The heater shall be electrical resistance type, copper tube with chromium plating. The generator shall be complete with float valve, pressure gauge with ball valve, master and bank thermostats, etc. The generator shall be suitable for 3 phase, 415+ 10% Volts, 50 Hz. AC supply. The generator shall complete with self-contained incoming isolation, ammeter, voltmeter, contactors for heater banks in three steps complete with manual/auto rotary switches.
(a) All neccassary accessories required for the proper fucntioning of Hot Water Genearator are included in price. (b) The prices should include lifting, shifting and positioning of units at Site. (c) Hot Water Genearator installation to done as per Manufacturer recommendation with all installation requirements i.e Foundation, Vibration Isolator,Insulation etc as recommended by Manufacturer for the Ambient Temperature of Site. ODU installation is included in ODU price which includes the Civil Struture, Mechanical Structure etc as recommended by Manufacturer. (d) The Contractor/OEM will shall submit the Hot Water Generator capacity/Burner Capacity as per ISO or equivalent standard. (e) OEM should submit the Installation and Maintenance Schedule/ Manual for the Boiler.
GLYCOL CIRCULATION CENTRIFUGAL PUMPS: Supply, Installation, Testing & Commissioning of PN16 rated Axial Split Coupled Vertical Inline water pump set with CI casing, Bronze Impeller, SS Shaft and externally flushed outside type balanced mechanical seal and non overloading motor, as per specifications and drawings. with Suitable HP, TEFC squirrel cage induction motor with EFF1 type class 'F' insulation, Motor shall be rating of IP 55, operating on 415 ±10% volts, 3 phase, 50Hz AC Supply. The external flush line must be used for the purpose of heat dissipation from the mechanical seal. Pumps with performance characteristics as given below: The internal components of pumps including mechanical seal shall be suitable to sustain a fluid temperature of -25 Degree Celcius to 120 Degree Celcius. Vendor shall be provide antivibration arrangement for pumps . The scope also shall include following below mentioned:
(i) Electrical by pass starter for pump set as recommended by OEM. (ii) 25 mm thick polyviny nitrile rubber insulation duly cladded between aluminium sheets of 0.5mm thickness and properly clamped to pump. (iii) 3 Nos.- 150 mm dia type pressure gauges (iv) Mounting frame with antivibration pads (In case pumps are inline, anti vibration system shall be as per Manufacturers recommendation) (v) RCC/Cement concrete foundation for the pump unit. (In case pumps are inline, foundation shall be as per Manufacturers recommendation). (vi) Pump capacity are as under: (vii) Capacity and pump head not less than flow 110 USGPM , Head 30 mtr each including the triple duct valve and End Suction guide. Make of Pump: Armstrong / Xylem /Grundfoss/Wilo. Note:- In 02 Nos working and 01 No standby configuration.
EXPANSION TANK and Pressurisation Unit: Supply, Installation, Testing and commissioning of INSULATED PRESSURISED CLOSED WATER EXPANSION TANK suitable for total volume of Glycol - Water Solution, circuit along with necessary accessories such as along with necessary accessories such as 2 Nos pumps (1working +1standby) with Pressure Transmitter and interconnecting Pipe & Isolating Valve complete with piping connections,
safety relief valve, drain valve, pressure gauge, automatic air purging arrangement, etc.with Pressure Transmitter and interconnecting Pipe & Isolating Valve complete with piping connections, safety relief valve, drain valve, pressure gauge, automatic air purging arrangement, etc. The tank shall be pre-charged. Expansion tank Shall be with replaceable heavy duty butyl rubber bladder. The tank connection's should be as per OEM recommendations and 20 mm drain and charging valve connection to facilitate the on site charging of nitrogen in the tank. The tank shall be fitted with lifting rings and a floor mounting skirt for vertical installation. The tank must be constructed in accordance with IS-STANDARD 2825-1969 (with lates Revision) and Rated at PN 16 and ASME Stamped. The complete system shall be sourced from single manufacturer and supplied and installed with all accessories and safety fixtures required for proper functioning of the complete hydronic system.
The tank shall be duly painted in approved colour shall be complete with pressure switches and power distribution and control panel IP55 Control Panel, Pressure Transmitter, interconnecting piping & wiring. (Tank capacity 1000 Ltrs). Hot Glycol - Water closed vessel pressurized expansion tank as described above shall be duly Insulated with 50 mm thick PUF/Nitrile Rubber insulating material or Equivalent U value Insulating Material and cladded with aluminium Sheet (20G).
(a) Expansion Tank of 1000 Lts capacity for Pocket-1
(b) PRESSURIZATION UNIT: for Pump Set -02 Nos (Ref. Point 3.05) with Control Panel and accessories for Pocket-1.
36 KW, ESP : 10 Pa (Reference Model No L: FUW040A/Equivalent)
Make Up TANK: Supply, installation, testing and commissioning of factory made Make up Water Tank, Rectangular/Circular shape, of 4 mm thick MS sheet (IS 2062), of capacity of 1000 litres for Pocket-1 complete with inlet, outlet, overflow, drain pipe of MS and vent with flame arrestor. Tank will be provided with supports made out of minimum 50mm angle iron duly painted, to keep tank base at minimum (1000mm) above FFL. Service platform shall be provided as per recommendations of OEM. The tank shall be provided with remote indication of levels provided level switches for on-off operation of tranfer pump. Extra high level and extra low level alarm shall be provided. Tank and structure shall be painted with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. Make up Water tank as described above should be duly Insulated with 50 mm thick PUF/Nitrile Rubber insulating material and cladded with aluminium Sheet (20G).
Supply, Installation, Testing and Commissioning of Ceiling/wall/floor Suspended Fan Coil Unit having casing with bottom return Air Plenum complete including Direct driven fan (three speed) motor, operated on 230 volts, single phase, 50Hz, AC supply. Unit to be provided with inbulit 2way valve with cordless remote. The Ball Valve with Strainer/ Shut off Value with Strainer at inlet and outlet of FCU should be provided. The Unit Capacity should be calculated as per BIS/ Eurovent Standard/AHRI Certification method. The below desired capacity should be calculated at Altitude of 3600 mts above sea level. Capacity calculation sheet to be provided to Engineer in Charge. The below mentioned capacity is at INLET TEMP: 65 Degree Celcius , OUTLET TEMP: 55 Degree Celcius and Below Mention External Static Pressure (ESP)
2.5 kW, ESP: 50 Pa (Reference Model No.: FWW200VC / Equivalent)
3 KW, ESP: 50 Pa (Reference Model No.: FWW200VC / Equivalent)
5 kW, ESP: 50 Pa (Reference Model No.: FWW500VC/Equivalent)
6 kW, ESP: 50 Pa (Reference Model No.: FWW500VC/Equivalent)
8 kW, ESP: 50 Pa ( Reference Model No.: FWW1000VC/Equivalent)
12 kW, ESP: 100 Pa ( Reference Model No.:FUW015A/Equivalent) (Electricain - 1 Qty)
18 kW, ESP: 100 Pa ( Reference Model No.: FUW020A/Equivalent) (Office for QC n Fuel Injection - 1 Qty)
40 kW, ESP: 100 Pa ( Reference Model No.: FUW040A/Equivalent) (Mech Section- 1 Qty)
M & L for Pre - insulated MS pipe,Class 'C' having minimum thicknes of PUF insulation as mentioned below and of density 36 Kg/Cum and 26 gauge GI/AL cladding complete suitable for above ground as per sizes shown.The pipes should be insulated with closed cell puf of density 36±2 Kg/Cum of below mentioned thickness.
The Pipe should be workable in the temp. range of -50 Degree Celcius to 120 Degreec Celcius. Note:-The Pipes size 150mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. And from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
Inside Building
125 mm with 50 mm PUF thicknes and 26 Gauge Al Cladding.
80 mm with 50 mm PUF thicknes and 26 Gauge Al Cladding.
65 mm with 50 mm PUF thicknes and 26 Gauge Al Cladding.
50 mm with 50 mm PUF thicknes and 26 Gauge Al Cladding.
40 mm with 40 mm PUF thicknes and 26 Gauge Al Cladding.
20 mm with 40 mm PUF thicknes and 26 Gauge Al Cladding.
Buried under ground/Exposed to Ambient:
125 mm with 50 mm PUF thicknes and HDPE Cladding, 26 Gauge Al Cladding.
80 mm with 50 mm PUF thicknes and HDPE Cladding, 26 Gauge Al Cladding.
Supply,Installation, Testing amd commissioning of PVC (minimum 15kg/sqcm pressure rated) drain water piping complete with fittings(elbows,tees, reducers,sockets,u trap etc.) supports, jointing insulated with XLPE class O tubular insulation and any other item required to make the system compelete. Nominal diameters of pipe in mms as inducated below:
25 mm dia pipe, Insulation thickness - 19 mm
32 mm dia pipe, Insulation thickness - 19 mm
40 mm dia pipe, Insulation thickness - 19 mm
CABLE TRAYS
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling/Ground/wall with M.S. suspenders including bolts & nuts, painting suspenders etc. as required
150 mm width X 50 mm depth X 1.6 mm thickness
VALVES :
Supplying, fixing, testing and commissioning of following diameter valves(PN-16 Rating) (Complete with Flanges integral or welded, fittings, Nuts, Bolts & Gaskets (PN-16 Rating), strainers (Complete with flanges integral or welded, fittings, Nuts, Bolts & Gaskets (PN-16 Rating), gauges etc for condenser water circulation as per specifications. Insulation thickness of valves should be equal to the Insulation of PUF and GI Cladding of Pipe Section as specified. Butterfly Valve ( Insulated Valves) with CI body SS disc nitrile sheet & O ring, Complete with fittings, Nuts, Bolts & Gaskets.
125 mm dia Butterfly Valve
80 mm dia Butterfly Valve
65 mm dia Butterfly Valve
Y - STRAINER (Insulated Valves) of Ductile CI Body flanged ends with stainless steel strainer for hot water circulation including Insulation thickness of valves should be equal to the Insulation of PUF and GI Cladding of Pipe Section as specified.
80 mm dia Y STRAINER
NON - RETURN VALVE (Insulated Valves) with duel plate of CI body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for hot water circulation including Insulation thickness of valves should be equal to the Insulation of PUF and GI Cladding of Pipe Section as sepcified.
80 mm dia NRV
Automatic Air Purge Valves for hot water circulation header as specified and required by Engineer In Charge.
Automtic Air Purge Valve 20 mm dia
Air Separator (PN16)
SITC of water pressure gauge (100 mm Ø) bourdon type with brass ball valve of 3/8" Ø and SS tubing, socket. Range (0-50) / (0-100) as required by Engineer In Charge.
SITC of Mercury in glass industrial thermometer in SS-304 casing with 0.5 C least count, range 0-100 C. Brass oil filled thermowell of 1/2" size as required by Engineer In Charge.
Supply, installation, commissioning and testing of factory made, CPRI approved LT CHS Plant, indoor type made out of CRCA sheet 2 mm thick, frame factory fabricated with front and back openable double door with locking arrangement, with MS angle section 50x50x6 mm support, duly powder coated painting having thickness not less than 100 microns provided suitable gasket to make it dust and vermin proof, suitable for 3 Phase 4 wire, 415 Volts, 50 Hz, AC supply system, floor mounted and grounting the legs of panel in PCC foundation 1:4:8 complete as all directed suitable for and including the following :-
INCOMERS (a) Bus Bar TPN Copper extensible type main bus bars of minimum of 3000 A capacity (As per capacity of corresponding incoming / Bus couplers) , and auxilliary bus bars of suitable capacity with heat shrunk coloured sleeves and i/c SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 50kA . (b) ACB 2000 Amps, 415 Volt, 50 KA, 4 Pole, thermal magnetic release - 01 No for incoming (Extended Rotary Operating Handle, Phase Spreader links and Phase barriers) Make: Legrand/Schenider/Simens
OUTGOINGS (c) 3 Nos- 800A 10 KA TP ACB with Microprocessor release (3# Hot Water Generator) (d) MCB -16 Amp, 10KA, TP - 02 Nos Pressurization PUMPs/Diesel Pump/ Boiler Pump (e) MCCB 63 Amp, 10KA, TP - 03 Nos for Pumps (f) MCB 5/6 Amp, 10KA, SP,- 80 No for Bldg load/FCU. Makes of MCBs: Legrand/Schenider/Simens (g) LED Phase indication lamps (01 Set) with 2Amp back up MCB, Breaker 'ON/OFF' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required. - 2 Set (h) Digital Ammeter with in built ASS, metering C.T.s "CAST RESIN" type, 15VA, and accuracy class-1of 2000/5A for measuring current in each phase - 01 Set. (j) All accessories prewired with appropriate size copper strip or wire and thimbles etc. all as required including foundations as per Manufacturers recommendations all as directed by Engnr-in-Charge. Note : Contractor will submit the drawing of panel to GE before execution for approval.
Supply & Laying/ fixing of following size XLPE insulated and PVC sheathed Copper conductor armoured cable/unarmoured as required of 1.1 KV grade complete as required. (ISI Marked) (in ground/in pipe/in duct/on surface/on cable tray)
3.5 Core x 240 sq.mm. (Electric Hot Water Generator)
4 Core x 10 sq.mm. (Pump)
4 Core x 6 sq.mm (Pressurization Unit)
2 Single core x 2.5 sq.mm. (FCU)
4 Core x 4 sq.mm (Boiler Pump)
Earthing complete with GI earth plate electrode of size 60cm X 60cm X 6mm buried directly in ground vertically at a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides by 15 cm thick and packed layer of charcoal dust and common salt filling in alternate layers etc and connected to and including GI strip of size 32x6 mm up to 7.5 mtr by means of bolts, nuts, check nuts and washers made of brass and protected by light grade 40mm dia upto 7.5 mtr long GI pipe connected to main control board and GI pipe light grade 20mm bore for watering and including funnel, wire mesh, RCC pit cover 50mm thick and PCC chamber pit with PCC 1:2:4 type C2 (including excavation and earth work disposal of surplus soil to a distance not exceeding 50 metre) and testing making test point and testing after completion all as specified and shown on plate No 3 of SSR Part-I 2009 complete all as specified & directed by Engr-in-charge.
Supply and fixing rubber matting conforming to IS-15652-2006 complete as required. of size 2m * 1m * 25 mm complete all as specified & directed by Engr-in-charge.
Supply, Installation, Testing Balancing & Commissioning of G.S.S rectangular/round ducting including plenum as required as per IS 655 - 2006 complete with gaskets, elbows, splitters, vanes, supports adjustable dampers, etc. as per approved drawings.(Factory Fabricated)The price shall include necessary scaffolding required for working at required height.
Hot dipped Galvanised with 120GSM Zinc coating
Thickness: 22 GAUGE Sheet
Supply and fixing of acoustic lining of supply air duct and plenum with 15 mm thick Supply and Application of Acoustic Insulation with Engineered Nitrile Rubber open cell foam with Density 140 - 180 Kg/m3 passing Class 1 Fire Performance test as per BS 476 Part 7, Air Erosion test for 10,000 fpm air velocity as per ASTM C 1071-05 and with built-in antimicrobial protection. The material should pass Fungi Resistance Test as per DIN EN ISO 846 Method A and Bacterial Resistance Test as per DIN EN ISO 846 Method C; to be applied using manufacturer's recommended Rubber based Adhesive in a blend of solvents.
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications complete all as specified & directed by Engr-in-charge.
Supplying & fixing of Jet Nozzel as per specifications and installtion should be done as per drawing complete all as specified & directed by Engr-in-charge.
Supply and fixing of Flexible connection Duct of FCU complete all as specified & directed by Engr-in-charge.
GLYCOL CIRCULATING PUMP: Supply, Erection, Testing and Commissioning of Transfer pumps for the capacity of 5 LPM 5 meter head for Glycol Fluid transfer with base frame foundation, bolts coupling coupling guard,TEFC, (OEM design HP for the required Flow and Head ) and other accessories for proper function of the pump.
GENERAL NOTES:
The rate for each item of work included in the Schedule of Quantities shall, unless expressly stated otherwise, include cost of : (a) All materials, fixing materials, accessories, appliances tools, plants, equipment, transport, labour and incidentals required in preparation for and in the full and entire execution, testing, balancing, commissioning and completion of work called for in the item and as per Specifications and Drawings. (b) Wastage on materials and labour. (c) Loading, transporting, unloading, handling/double handling, hoisting to all levels, setting, fitting and fixing in position, protecting, disposal of debris and all other labour necessary in and for the full and entire execution and for the job in accordance with the contract (d) documents, good practice and recognize principles. Liabilities, obligations and risks arising out of Conditions of Contract. (e) The unit rate for all equipment or materials in Indian Rupees shall include cost of equipment and materials including all taxes and duties and also including forwarding, freight, insurance and transport into Contractor’s store at site, storage, installation, testing, balancing, commissioning and other works required.
The contractor shall perform Nitrogen test and vacuum test on refrigerant piping. Start and stop timing & pressure maintained shall be checked and the readings recorded shall be counter signed by Engineer-in-Charge.
Cable glands shall be compression type, heavy-duty chromium plated.
All cable termination to have lugs/ thimbles.
INSTRUCTION / MAINTENANCE MANUAL
The Contractor shall prepare and produce instruction, operation and maintenance manuals in English for the use, operation and the maintenance of the supplied equipment and installations and submit to the Client / Consultant in (3) copies at the time of handing over. The manual shall generally consist of the following: (i) Description of the project. (ii) Operating instructions. (iii) Maintenance instructions including procedures for preventive maintenance. (Iv) Manufacturers catalogues. (v) Trouble shooting charts. (vi) Schematic & control wiring diagrams. (vii) Commissioning Certificate. (viii) Training,Opeartion, Installation manual and Trouble shooting manual and Training should be imparted to the field person. (ix) Traning shall be of 02 week for 10 persons at site.
For Make List If any make stated below does not comply with the technical specifications and or IS Standards then such a make shall not be used in the work.
MAINTENANCE OF PLANT AND TRAINING OF PERSONNEL The Cont ractor shall arrange to provide, at no extra cost, necessary personnel and material to carry out all routine maintenance of the CHS equipment as required regularly.
Supply and fixing water storage tank 5000 Ltrs capacity complete all as specified and directed.
Cutting existing pipe and tee (Refer item 4 above)
M&L for PCC platform (Refer item 4 above)
DES RAJ AND SONS BUILDERS PVT LTD (BID ID -3371330)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid