EE
Electrical Division No.II, HPPWD, U.S. Club, Shimla-01.
Providing special repair of MRI and USG chambers Dr. room corridor waiting areas and toilets in old causality block B at IGMC Shimla. Providing 20 KVA 20 KW online UPS therein.
2026_PWD_126447_2
ED.II.TA.TENDER.25.26.3183 dt. 21.01.2026
Open Tender
Electrical Works
Percentage
30 days
Shimla
Please refer to tender documents. Eligibility criteria is mentioned at page No. 9-10 of GCC. Documents mentioned in eligibility criteria must be uploaded to qualify the bid.
7 documents required · 7 mandatory
₹350
₹15,600
24 Feb 2026
24 Jan 2026
2 Feb 2026
24 Jan 2026
31 Jan 2026
24 Jan 2026
Supply Installation Testing & Commissioning of 20KVA/20 KW Online UPS : Three Phase Input & Three Phase Output- Autosensing, True Online UPS with Full Digital Signal Processing (DSP )Technologies with Touch Screen (LCD /LED ) display Panel & Pure Sine Wave O/P . UPS unit shall operate in double conversion mode, it shall be a VFI-type UPS (as per stanard IEC 62040-3).UPS along with same rating Inbuilt K rated Galvanic ISOLATION Transformer of same OEM make only. UPS should be with Latest IGBT Based Rectifier & Inverter Technology. UPS should have minimum 30 minutes backup on SMF Batteries Bank with Minimum VAH = 18000 VAH,along with following features/specifications The job includes the cost of Supply, installation, commissioning and testing charges including rack, connecting and other petty material required to complete the job.
The UPS should have following specification.
INPUT FEATURE :
Input Voltage window 320 VAC - 480 VAC 3 Phase
Input Frequency window 45-55 Hz .
Nominal Frequency 50 Hz
Total Harmonic Current Distortion (THDI ) should be less than 3 % at full rated load
Input power factor (PF) greater than or equal to 0.99
OUTPUT FEATURE :
Output Power Factor should be unity.
Output Power Capacity in watts (KW) 20KVA / 20KW
Output Voltage - 380 / 400 /415 Volts rms, adjustable via the user interface.
Total Harmonic Distortion : < 2% for linear load & < 5% for 100% non-linear load
Output Frequency range 50/60 HZ.
Other Features
UPS overall Efficiency : upto 94% ( AC to AC i.e Online Mode) and 98% ( Eco Mode ) without Isolation transformer losses
Overload Capacity: A) 10 minutes at a load representing 125% , B) 60 second at a load representing 150%
Parallel option : Parallel option upto 4 Units should be available
Bypass : UPS Should Be built in Manual and Maintenance Bypass feature
Operating Temperature : 40 degree C
Noise Level :Less than 65 dBA
Emergency Power Off (EPO) Should be available as standard
Protection requried :TVSS inbuilt ,over volatage,short circuit ,overload at UPS O/p and Under Voltage at battery terminal,input phase sequence protection feature,with dust filters and inbuilt TVSS device for surge protection.
UPS should has feature of common battery bank up to at least 2 units.
Isolation :UPS Should be with same OEM make inbuilt Isolation Transformer at Input side.
Communications & Management :-
Interface ports : USB/ RS 232 & optional SNMP .
Touch Screen LCD Display and LED indicators
Alarms : Audible Alarm required for Mains failure, Low Battery, Inverter Trip, Over Temperature, Over Load
Safty Standard & Certifications and Test reports
ISO 9001 & 14001,45001 certified OEM ,Safety Standard: IEC62040-1, EMC: IEC62040-2, Performance IEC62040-3 , along with CE/UE certification. Product should be ROHS / PEP & REACH certified And IP20 Protection ,Quoted model should be tested by SAMEER/ERTL/NTH or any Govt. approved NABL Accredited Lab. Bidder to submit the type test report from any Govt. LAB /NABL accredited LAB in supporting to above technical parameters.
Warranty Terms : Five Years on UPS & Three Years on Batteries onsite service Support
Approved Make : APC- Schneider / Vertiv -Emerson/Legrand-Numeric Only for UPS & Exide, Quanta & Panasonic for SMF Batteries. .
SERVICE & Support : OEM should have 3-4 own /ASP based registerted service centers in the state for better & timely service support, need to share at least 2 engineers contact details with service center address details in the region of installation and OEM Turnover should not be less than 500 Crores/year in last 3 financial years with profitability. 10 years presence of OEM in Govt. project segment And Quoted product should be available on OEM Website with as per asked technical specifications
Battery Bank : UPS unit shall be equipped with its independent battery bank of the following:
VRLA type, mounted on a rack with a design life of 3 yrs as per OEM , Sealed Maintenance Free - Lead Acid Battery with suspended Electrolyte (Leak Proof)The battery shall be sized to ensure continuity in the supply to the inverter for 30 minutes for a power rating of 20KVA at full rated load & 1.7 ECV.
Battery Type : DC Voltage Bus with Flexibility of at least 4-6 no. of Batteries , Min. 30 Mins Backup , 12V Batteries will be provided by firm Minimum required VAH per UPS =18000 VAH.(12V,75Ah 20 no. batteries)
DC Battery Breaker : For safe maintenance on the battery of UPS unit, the system shall include a circuit breaker to isolate the battery from the corresponding rectifier /charger and inverter. When the battery is isolated from the system, the UPS shall continue to supply the load without interrup-tion or disturbance, except in the event of a normal AC source outage.
Battery Rack & Links - Racks Suitable for Mounting the All Batteries each Sheet Metal Type along with interconnection cables and 5/7 meter wire from UPS to battery bank.
Approved Make:APC-Schneider, Vertiv- Emerson, Numeric- Legrand only for UPS & Exide / Quanta/Panasonic for Batteries or as approved by Engineer-in-charge
Providing & Laying of one number aluminium conductor, PVC insulated and PVC sheathed armoured/ XLPE power cable, 1.1 KV grade of following sizes on wall surface as required
Armoured cable 25 sq. mm (3.5 core)
Supplying and fixing following rating, followings poles 10ka 240/415v 'C' curves miniature circuit braker suitable for inductive load of following poles in the exsisting MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing TP&N copper bus-bar chamber suitable for 415 volts capacity with 4 No. copper strip bus-bars each of length and x-section suitable for following current carrying capacities, enclosure made of sheet steel having thickness of 1.6mm, dust protected, duly powder painted with detachable gland plate and other accessories including drilling holes on the board, making connections, earthing etc. as required
63 A Copper Busbar Chambers 15" (SS Enclosure)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.75 MB
GCC.pdf
Tender Documents • 5.43 MB
BOQ_186461.xls
BOQ • 0.37 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .