EE SDW IX
RITHALA STP SEC-11 ROHINI DELHI 110085
Renovation of internal lighting system of civil office, booster pumping station and new booster pumping house at Staff qtr Rithala Re-invite
2022_DJB_232267_1
NIT No. 13 (2022-23)
Open Tender
Miscellaneous Works
Works
30 days
RITHALA STP SEC-11 ROHINI DELHI
Please refer Tender documents.
4 documents required · 4 mandatory
₹500
As per NIT
₹11,200
2 Dec 2022
16 Nov 2022
25 Nov 2022
16 Nov 2022
25 Nov 2022
16 Nov 2022
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano types switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm FRLS PVC insulted copper conductor single core cable etc as required.
Supply and fixing metal box of 150mm X 75mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 3 pin 5/6 A socket outlet and 5/6 A piano type switch, connections/ painting etc. as required.
Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 & 15/16 A socket outlet and 15/16A piano type switch, connections painting etc as required.
Wiring for circuit /Submain wiring along with earth wire with the following sizes of FRLS PVC insulted copper conductor, single core cable in surface/recessed medium class PVC conduit as required 2x2.5sq.mm+ 1x2.5sq.mm earth wire.
2x4sq.mm+ 1x4sq.mm earth wire.
2x6sq.mm+ 1x6 sq.mm earth wire
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.
Installation, testing and commissioning of pre wired, fluorescent fitting/ compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling / wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor single core cable and earthing etc. as required.
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required, Single pole,
Supplying and fixing 6 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DP complete with connections, testing and commissioning etc. as required, double pole,
Supplying and fixing 63 A rating, 240V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required, double pole,
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (4 + 12), Double door.
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note: Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8 way (4 + 24), Double door.
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required upto 450 mm sweep
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7-meter-long etc. with charcoal/ coke and salt as required.
Supply of 35 sq mm 3.5 core LT aluminium power cable. Make:- Havells /Gloster/Universal/Grandlay/ICC/ICU/any other DJB approved make of DJB
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. Upto 35 sq mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
Supply 20 watt LED (Tube Light) decorative ultra slim square profile LED lighting fixture with extruded polycarbonate, environmental friendly, energy efficient ready to use pack.
Supply 70/72 watt LED Outdoor luminaries’ new generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high efficient LED as lighting source and PC cover having TOP opening separate driver compartment with IP66 protection and impact resistance of IK07.
Supply of exhaust fan heavy duty 1440 RPM size 450 mm.
Supply of Air circulator wall fan 450 mm.
RISHABH ENGINEERS
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .