Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.6 LAccepted-Finance | ₹14.6 L | L1 | Accepted-Finance Lowest bidder |
| 2 | L2₹15.6 LRejected-Finance | ₹15.6 L | L2 | Rejected-Finance High rate offered |
| 3 | L3₹17.5 LRejected-Finance 3 C DR JAGABANDHU LANE KOLKATA 700012 | KOLKATA | KOLKATA | WEST BENGAL | 700012 | ₹17.5 L | L3 | Rejected-Finance High rate offered |
Tender Value
Refer Docs
EMD Value
₹41,280
Closing Date
5 Jan 2026, 12:00 pmClosed
EE II CKHED
P12 CIT Road 1st floor Kol 14
Second source Power line arrangement for BMT SNCU Baby Nursery PICU 1 Dialysis Peritonial Dialysis in NRSMC and H Kolkata
2025_WBPWD_968377_1
WBPWD/EE-II/CKHED/ eNIT-79/25-26
Open Tender
ELECTRICAL WORKS ORG
60 days
NRS MCH
as per NIT
4 documents required · 4 mandatory
₹41,280
central kolkata health electrical division
9 Jan 2026
5 Dec 2025
7 Jan 2026
5 Dec 2025
5 Jan 2026
11 Dec 2025
10 Dec 2025
Amount
SITC of LT Cubicle type fully compartmentalized floor / wall mounted panel board of size with multi-tier arrangement, having rigid & self supporting structure fabricated with sufficient no. of channels (50x15x15mm) and covered by 14 SWG CRCA sheet with base structure by 75x40x4mm channel. All incoming, outgoing are to be housed in respective compartments with hinged & gasketted doors at the front. All the doors should have panel lock arrangements in such a fashion that it can not be unlocked unless the respective feeder remains OFF. The rear of panel should have gasketted wire net guard for ventilation and arrangement shall be made for easy access to each compartment by providing rear doors with locking system. The panel is to be properly gasketted to prevent the dust & vermin. All vertical & horizontal bus-bar chambers are to be properly arranged & all electrical switches, bus-bars are to be fixed by MS nut-bolts on suitable hylam board / non-hygroscopic insulators of adequate size & dimension. The outgoing feeder connections from respective switches are to be made at the rear side of the panel by means of bus-bar / multicore copper cables, to be terminated on bolted type terminals for cable connections or bush insulators for bus connection, as directed by EIC.
INCOMER : S &F Incoming 415V 320A, (DN3B-400D) FP 36kA MCCB with thermal magnetic release ( L&T Cat No.-CM98403OOQOOG ) with extended spreaded terminals (LT-Kit ST98066OOOO- 8Pcs) Rotary Handle with Extended ROM (L&T cat no.--CM99861OOOO)-- 1 No.-- 1 No. with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection and necessary interconnection with tinned copper bars & colour sleeve to BBC - 1 Nos. ( Make : L&T/Siemens equivalent cat no/ABB equivalent cat no.)
BUS BAR CHAMBER: 415V,400A 4 bars BBC of suitable dimension made out of 14 SWG powder coated CRCA sheet with front covers fixed with 4 nos fixing bolts in each with 99.99% electrolytic tinned copper bars a) for main vertical BB: 4 X 50 X 5 mm annealed Cu bar insulated with good quality heat sink on bakelite insulator & front transparent fibre glass guard. b) For horizontal BB: 4 x 20 x 5 mm annealed Cu bar insulated with good quality heat sink on bakelite insulator & front transparent fibre glass guard.
OUTGOING : (i) S & F of 415V 160A DN 2-250D FP 36kA MCCB with micro processor release ( L&T Cat No.-CM92108OOL1OG ) with two nos extended spreaded terminals (LT-Kit CM92007OOOO- 8Pcs) Rotary Handle with Extended ROM (L&T cat no.--CM98041OOOO)-- 1 No. - 3 set [Make :LT/Siemens/Legrand/ABB]
(ii) S & F of 415V 100A, DN0-100C FP 25kA MCCB with micro processor release ( L&T Cat No.-CM91712OOKOOG ) with two nos extended spreaded terminals (LT-Kit CM92007OOOO- 8Pcs) Rotary Handle with Extended ROM (L&T cat no.--CM98041OOOO) [Make :LT/Siemens/Legrand/ABB] -3 Set
iii) S & F 400/5Amp ratio C.T (Kappa/AE) - 3 nos.
iv) S & F 125/5Amp ratio C.T (Kappa/AE) - 12 nos.
iv) S & F of 240V, 0.5-0.6VA burden at 5A, Resolution range (0.001A-1A depending upon CT primary) digital ammeter( Make: L&T/ AE).-6 nos
v) S & F 240V, digital voltmeter (Make:L&T/ AE).-1 no
vi) S & F Phase indication LED indicator light (R,Y,B)p - (SIEMENS/L&T) - 3 nos
vii) S & F 2/6 Amp SPMCB(Make-SIEMENS/LT/Legrand)---3 nos.
viii) Interconnection with 1.5 sq. mm flexible FR Cu wire with proper dressing
ix) S & F EI Danger Board(150mm x100mm)
Incoming 415V, 200A open execution type manual change over in sheet steei enclosure(CO21250OOSO) incl S &F Rotary Handle with Extended ROM (L&T cat no.--CM99861OOOO)-- 1 No.
Dismantle the existing TPN SFU, Connection etc from the existing panel and making temporary arrangement to feeed the existing fed locations.
Supply and Delivery of 1.1 KV grade following sizes Al. armoured PVC/XLPE cable (Make-RR cable/Havells/polycab/KEI/glostar) as mentioned below as per choise of EIC.
4 Core 240 sqmm
4 Core 70 sqmm
4 Core 50 sqmm
Laying of 1.1 KV grade following sizes Al. armoured PVC/XLPE cable (Make-RR cable/Havells/polycab/KEI/glostar) as mentioned below as per choise of EIC.
4 Core 240 sqmm (Through masonry trench)(F-3/4c)
4 Core 240 sqmm (Through under ground trench)(F-2/1c)
4 Core 240 sqmm (on wall with S & F 25mm x 25mm x 6mm MS angle iron frame of size 12" length and 3" breadth - frames are to be placed 1 mtr interval)
4 Core 240 sqmm (on wall with S & F MS clamps as required))
4 Core 70 sqmm(on wall with S & F MS clamps as required)) (F1/2d)
4 Core 50 sqmm(on wall with S & F MS clamps as required)) (F1/2d)
4 Core 300 sqmm (on wall with S & F MS clamps as required))
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below[ F-4,7 ]
4 Core 240 sqmm [ F-4,7(c) ]
4 Core 70 sqmm [ F-4,7(c) ]
4 Core 50 sqmm [ F-4,7(c) ]
4 Core 300 sqmm
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. [ F-5,9 ]
4 Core 240 sqmm
4 Core 70 sqmm
4 Core 50 sqmm
4 Core 300 sqmm
Supply and Fixing 1.1 KV single core stranded 'FRLSH' PVC insulated & unsheathed single core stranded copper wire(RR Cable/Finolex/ /Polycab/KEI as approved by EIC) making necy. connection as required
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. [ F-5,9 ]
S & F of 415V, FP 63A FP MCB after withdrawing the SFUs of the SNCU & Baby Nursery Panel, First floor OPD Panel and making necessaryarrangement and required connection as required.
Dismantle the existing 2 nos 3.5 core 240 sqmm and one number 3.5 core 300 sqmm Al armoured cable from the existing panel and removing the MS gland box, six nos old empty main switch cover, ms box, loop box, withdrawing different size of cables which are not in used and in damaged condition and relaying the 6 nos different type cables on wall approx 4 mtr each by ms saddle and as required. .
Supplying and fixing of 415V,400A open execution type change over switch with S & F sheet steel enclosure (Cat no: CO44000OSOO) having extended handle with S & F flip-able handle (i.e. assembly of handle, shaft, center bush, bush clip) (cat no: CX40001OOOO) fitted on wall with suitable size of fastner. .
S & F 50mm metal flxible pipe with necessary couplings as required having outer edge of PVC made.
S & F 415V AC, LED Digital Ammeter with necessary inter connection including S & F connecting wires, sockets etc (Make L&T, cat no: WL131010OOOO)
S & F 240V AC, CT having ratio 400/5 with necessary inter connection including S & F connecting wires, sockets etc (Make AE) after removing the existing busbar and reinstalled the busbar after fixing the CTs.
S & F 415V AC, LED Digital voltmeter with necessary inter connection including S & F connecting wires, sockets etc (Make L&T, cat no: WL132010OOOO)
Painting the Main switch cover, grill, Busbar chamber etc after cleaning rust by sand paper.
Covering the holes by brick and sand in the wall(approx 1 sqmtr) and plastering the wall both in outside and inside where the holes are exsist.
S & F of 230V LED panel indication lamp after disconnecting the faulty one ( Make: L&T/Other similar make).
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required. [G-2,4b]
Earthing with 50 mm dia GI pipe(By TATA-Medium GI pipe) 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below:
Supplying & fixing earth strip of galvanized (Hot Dip) MS flat 50 mm x 6 mm
S & F of 40mmx 6mm T type MS angle of length 300mm length duly painted as required and fitted by required size of fastner.
Rate is inclusive all taxes and cess
Defect Libility Period 1 year
STAAR CONSTRUCTION (BID ID -7811859)
S. A. ENTERPRISE (BID ID -7797759)
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid