ED IT
ITD, CHQ AAI, Safdarjung Airport, New Delhi
Establishment of Non-IT Infrastructure for Disaster Recovery (DR) Site at Hyderabad
2018_AAI_19568_1
AAI/CHQ/ITD/DR/2018
Open Tender
Information Technology
150 days
Hydrabad
Please refer Tender documents.
13 documents required · 13 mandatory
₹2,950
Yes
Airports Authority of India
₹40.2 L
Yes
CHQ AAI, New Delhi
24 Feb 2022
18 Dec 2018
30 Jan 2019
18 Dec 2018
29 Jan 2019
21 Jan 2019
18 Dec 2018 - 3 Jan 2019
8 Jan 2019
Amount
Flooring
SITC of Vitrified Tiles flooring: Providing and laying Vitrified tiles in different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS: 15622, of approved brand & manufacturer, in all colours and shade, in skirting, riser of steps, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS: 15477, in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately .Size of Tile 600x600 mm. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing complete as per direction of Engineer-in-charge.Size of Tile 600x600 mm. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Carpet Flooring: Providing and laying of Carpet Tile over NOC area, Cabins reception area. The floor which receives the carpet to be thourougly cleaned as per manufacturer's specification. The carpet is to be laid over a bed of manufacturer's approved adhesive spread evenly over the entire floor. The rate shall include cutting, trimming, fixing and clearing away of residual material to a location as directed. Refer to Annexure VII for Detailed specification.
SITC of Raise Flooring: Providing and fixing Access Floor panel of 600x600x32 mm medium grade Filled Steel anti static high pressure Lamination of 800H grade (FS800H). Access Floor panel shall be steel welded construction with an enclosed bottom pan with uniform pattern of 64 hemispherical cones. The top and bottom plates of Steel Gauges: top 0.6 mm and bottom 0.7 mm fused spot welded together (minimum 64 welds in each dome and 20 welds along each flange). The panel should be corrosion resistant epoxy coated for lifetime rust protection and cavity formed by the top and bottom plate is filled with Pyrogrip non-combustible Portland cementitious core mixed with lightweight foaming compound. The access floor shall be factory finished with Anti-static High Pressure laminate with Non Warp technology upto 1mm thickness for superior adhesion and Surface flatness within 0.75mm.The panel is to withstand a Concentrated Load of 363 kgs applied on area 25mm x 25mm without collapse in the centre of the panel which is placed on four steel blocks. The panel will withstand and Uniformly Distributed Load (UDL) minimum 1250 kg/sqm and, an impact load of 50kg all complete as per the approved manufacturers specification and as per the direction of Engineer-in-charge. All specification must be printed on the side of the panel to ensure the quality of the product. 300 mm Finished Floor Height (FFH). For detailed specifications, refer to Annexure VII and corrigendums..
PARTITIONS
SITC of GYPSUM PARTITIONS: 100mm GYPSUM board partition with two layerf of 12.5 mm thick Gypsum Board on each side of the frame- screw fixed with drywall screws of 25mm & 35mm at 300mm centres to either side of 48mm. Stud (0.5mm thick having one flange of 34mm and another flange of 36mm made of GI Steel) placed at 610mm c/c in 50mm floor and ceiling channel (0.5mm thick have equal flanges of 32mm made of GI steel) anchored to the floor & true ceiling using suitable anchor fasteners or metal screws with Pvc plugs. The boards are to be fixed to the framework with joints staggered to avoid leakage through joints . Rate to include making provisions in panels, grooves and finishing the same to fix soft board (0.45x1.8m) and whiteboard (1.2mx3.2m) fixed flush on the partition. Note soft board and whiteboards will be paid for separately. Rate also to include making openings for glass panels, ducts, services and doors by providing concealed frames on all sides, framework above false ceiling and any other provisions reqd. to facilitate the same, all hardware etc. all complete. 75 mm overall thickness partition with 12.5 mm thick double skin fire rated board conforming to IS: 2095: part I. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Fire Rated Glass partitions: Providing and fixing non load bearing fixed frame for fire resistant glazed Partition of 120 min Fire Rating, made out to a profile of dimension 60mm x 70 mm of 1.6 mm thick galvanised steel sheet as per test evidence suitable for fixing fire rated glass for 120 min of both integrity & radiation control (EW120) & minimum 15 min of insulation (EI15).The profile has to be fixed to the supporting construction by means of anchor fasteners of size M10 x 80, every 150 mm from the edges and every 500 mm (approx) c/c. Linear meaurement of frame shall be measured for payment. The frame shall be filled with mineral wool insulation of density min 96kg/ m³. and finished with a approved fire resistant primer or Powder coating of not less than 30 micron in desired shade as per the directions of Engineer - in- charge. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Glazing : Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc., with G.I. beading made out of 1.6 mm thick G.I. sheet (zinc coating not less than 120 gm/m²) of size 20 x 33 mm screwed with M4 x 38 mm SS screws at distance 75 mm from the edges and 150 mm c/c , including applying a coat of approved fire resistant primer/powder coating of not less than 30 micron on G.I. beading, & special ceramic tape of 5 x 20 mm size etc complete in all respect as per direction of Engineer-in-charge. The glass shall be clear, toughened, interlayered, non-wired fire resistant having 11 mm thickness of approved brand with 120 minutes of fire resistance both integrity & radiation control (EW120) and minimum 15 min of insulation (EI15) and having a sound reduction of 37dB and LT of 86%. Glass shall be compliant to class 2(B)2 category of Impact Resistance as per EN 12600. The glass should be manufactured in UL & TUV audited Facility and including UL-EU Certification.The maximum glazing size cannot be more than 1100 mm x 2200 mm (w x h) or 2.42 sq mts in total area. The test report for the complete system (Glazed Door or Partition) will be considered valid only if it contains the stamp and signature of the authorized signatory from the glass manufacturer. (Actual glass size is to be measured at site for payments). For detailed specifications, refer to Annexure VII and corrigendums.
SITC of TOUGHENED GLASS PARTITION : Providing and fixing 12mm frameless self standing toughened glass of required height and length with mirror polished edges, fixed as per specified layout with patch fittings fixed as and where requried, specially or4dered stainless steel patch fittings as legs, tees, junctions, angles, glass to glass connectors, wall to glass connectors, L angle connectors, 2 way glass connectors with SS patti with double sided bolt including all Stainless steel bolts with nuts etc. used as and where required as per layout plan, glass to be of required length with proper support with all gap filled with silicon sealantglass to have holes/ cut outs to accommodate patch fittings, all complete as per entire satisfaction of Engineer-in-charge. For detailed specifications, refer to Annexure VII and corrigendums.
FALSE CEILING
Modular False Ceiling: Providing and fixing mineral fibre false ceiling tiles at all heights of size 595X595mm of approved texture, design and pattern. The tiles should have Humidity Resistance (RH) of 99%, Light Reflectance ?85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS 476 pt – 6 &7)in true horizontal level suspended on interlocking T-Grid of hot dipped all round galvanized iron section of 0.33 mm thick (galvanized @120 gsm ) comprising of main T runners of 15x32 mm of length 3000 mm, cross T of size 15x32mm of length 1200 mm and secondary intermediate cross T of size 15x32 mm of length 600 mm to form grid module of size 600x600 mm suspended from ceiling using galvanized mild steel item (galvanised@80gsm) 50 mm long 8mm outer diameter M-6 dash fasteners, 6 mm diameter fully threaded hanger rod up to 1000 mm length and L-shape level adjuster of size 85x25x2 mm, spaced at 1200 mm centre to centre along main ‘T’. The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size24x24X3000 mm made of 0.40 mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be pre-painted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the engineer-in-charge. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Gypsum Ceiling: Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with : 12.5 mm thick tapered edge gypsum fire resistant board conforming to IS: 2095- Part I. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of FIRE RATED DOORS :Providing and fixing single or double steel door shutters with 45mm thk flush design shutter comprising of two outer sheets of 18 gauge steel sheets rigidly connected and reinforced inside with continuous vertical 20 gauge stiffeners, spot welded in position at not more than 150mm on centres including void filled with mineral wool (density as per specification), all fittings, mortice lock with handle on both sides, tower bolt, stopper, aldrop, shop and final painting etc all complete. Each door to have 300mm x 200mm vision panel fitted with wired fire rated glass. Refer to Annexure VII for Detailed specification. For detailed specifications, refer to Annexure VII and corrigendums.
(1200mm + 300 mm) x 2400 mm unequal double Leaf door
900 mm x 2400 mm single Leaf door with panic bar
SITC of Glazing in Fire Resistant Door: Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc., with G.I. beading made out of 1.6 mm thick G.I. sheet (zinc coating not less than 120 gm/m²) of size 20 x 33 mm screwed with M4 x 38 mm SS screws at distance 75 mm from the edges and 150 mm c/c , including applying a coat of approved fire resistant primer/powder coating of not less than 30 micron on G.I. beading, & special ceramic tape of 5 x 20 mm size etc complete in all respect as per direction of Engineer-in-charge. The glass shall be clear, toughened, interlayered, non-wired fire resistant having 11 mm thickness of approved brand with 120 minutes of fire resistance both integrity & radiation control (EW120) and minimum 15 min of insulation (EI15) and having a sound reduction of 37dB and LT of 86%. Glass shall be compliant to class 2(B)2 category of Impact Resistance as per EN 12600. The glass should be manufactured in UL & TUV audited Facility and including UL-EU ertification.The maximum glazing size cannot be more than 1100 mm x 2200 mm (w x h) or 2.42 sq mts in total area. The test report for the complete system (Glazed Door or Partition) will be considered valid only if it contains the stamp and signature of the authorized signatory from the glass manufacturer. (Actual glass size is to be measured at site for payments). For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Panic Bar: Providing and fixing panic bar / latch (Double point) fitted with a single body, Trim Latch & Lock on back side of the Panic Latch of reputed brand and manufacture to be approved by the Engineer- in- charge, all complete. For detailed specifications, refer to Annexure VII and corrigendums.
Glass Door. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Toughened Glass Door: Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-incharge. For detailed specifications, refer to Annexure VII and corrigendums.
PAINTING and POP.
SITC of POP:Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Painting: Wall painting with acrylic emulsion paint, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required, to achieve even shade and colour. Two coats. For detailed specifications, refer to Annexure VII and corrigendums..
SITC of Fire Retardant Paint:Providing and applying two coats of fire retardant paint on cleaned wood / ply surface @ 3.5 sqm per litre per coat including preparation of base surface as per recommendations of manufacturer to make the surface fire retardant. For detailed specifications, refer to Annexure VII and corrigendums..
BLINDS
SITC of Motor in Blind:Provision of Motor in blind of following specifications: Motors DIA 34.75 mm, Torque(NM) - 6 NM , Speed (rpm) - 28 RPM (Radio motors), Voltage - 220 V, Power consumption (W) - 155 W, Frequency - 50 HZ, Lifting capacity 15 KG, Average running noise(dbA) - less than 35 db .These motors can only operate on remote. For detailed specifications, refer to Annexure VII and corrigendums..
FURNITURE
SITC of Technical Workstation Furniture: Technical Workstations for NOC Area of Pyrotech - INFI , Godrej, Durian, Cosmos or equivalent as per the approval from AAI Site Incharge.
SITC of Steel Cabinet: Providing and fixing of 750mm high Powder coated steel cabinets with shelves, locks, handles etc. of Godrej, Durian, Cosmos - vertical filing cabinets or equivalent as per the approval from AAI Site Incharge.
SITC of Upholstered Chairs : P/F of Fully upholstered chairs . Synchro tilt mechanism. Pneumatic height adjustable gas lift mechanism. Twin wheeled nylon 5 prong castors. Height adjustable arms with 360 degree rotation. Adjustable tilt tension with four stage back-lock. Adjustable backrest height. Sliding seat pan. Medium back / High Back. Forward tilt. Soft arm caps. Foam density - 50 Kg/cu-m with hardness of 20Kg +/- 2 Kg at 25% compression. Fabric upholstered with fire retardant coating for fabric (Grade A - Fabric) of Herman miller - aeron or equivalent.
SITC of Sofa: Supply of three seater sofa with fabric outer layout of Godrej, Midas, Durian, Cosmos or equivalent as per the approval from AAI Site Incharge.
SITC of Working Table: Providing and placing in position laminated working table of required size: a) Working top to be made in 18mm thick commercial board having single boards pasted upon another board orf depth 150mm at all sides (except rear side) to make it thick upto 36mm. b) Vertical support shall be 18mm thick Commercial board for supporting working top. c) 1mm laminate shall be fixed on work top (top surface), vertical sides (both faces) d) 0.65mm balancing laminate on underside of table. e) Top to be fixed with 40x6mm teak margin on front, verticle side to have 20x6 teak margin on front cut out for cables etc. to be provided whenever required. The item shall be as per direction and satisfaction of Project-in-charge.
SITC of Centre Table: Supply of glass top Centre table mounted on teak wood polished frame of Godrej - PISA make Durian, Cosmos or equivalent as per the approval from AAI Site Incharge.
SITC of High Back Chair: High back chair with armrest and comfort cushion of Godrej - La Sede, Durian, Cosmos or equivalent as per the approval from AAI Site Incharge
SITC of Workstation Chair: Workstation chair of Godrej - EII 5002T, Durian, Cosmos or equivalent as per the approval from AAI Site Incharge
SITC of Visitor Chair: Visitor chair in Cabin as per specification - 3 seater set of Godrej Premium lounge or equivalent. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Reception Table: Reception table of Godrej - First impression or equivalent as per specification, For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Reception Chair: Reception chair of Godrej Marvel or equivalent as per specification. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of File Cabinet: File cabinet of 4 horizontal shelves of Godrej - vertical filing cabinets or equivalent for cabins. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Manager Table: Manager table of Godrej Enterprise or equivalent as per specification. For detailed specifications, refer to Annexure VII and corrigendums.
Miscellaneous items
Anti-termite Treatment: Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) :Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor: With Chlorpyriphos/Lindane E.C. 20% with 1% concentration
Supplying chemical emulsion in sealed containers including delivery as specified. Chlorpyriphos/ Lindane emulsifiable concentrate of 20%
SITC of Tile Puller and Others:Providing 2 nos. Tile puller with suction cup, wooden door ramp of required size and height, wooden steps of required dimensions as per direction of Project-in-charge (Unitile).
Thermal Insulation:Supply, Installation, Testing & Commissioning of Thermal Insulation: Supply & fixing of thermal insulation above ceiling with 19mm thick XLPE/Nitrile rubber.
SITC of MAIN LT PANEL : Design, fabrication, assembly, wiring, supplying, installation, testing and commissioning of front operated cubicle type compartmentalised front access free standing, dust and vermin proof (IP 20 ingress protection) switchboards suitable for use at 400 volts +/-10%, 3 phase 4 wire 50 Hertz system suitable for fault level of required value symmetrical at 400 volts +/-10%, fabricated from 2 mm thick CRCA MS sheets with hinged, gasketted (metal based neoprene) and lockable doors having structural reinforcement with suitable angle/channel/T/flat sections including 3 mm thick gland plates on top and bottom and including lifting hooks and GI earth strip of required size with 2 nos earthing terminals and powder coated paint finish of approved shade over metal surface cleaned and treated with seven tank process complete with interconnections etc as per specifications, as required and as below. MCCB and MCB operation at 415V AC, and the insulation need to be at 690V AC, all Panels shall be duly metal labled with schematic diagarm and Danger marks.Complete as required. All Panel/Switchboards shall have provision for entry of cables from the top and bottom as required. All live accessible parts shall be shrouded and all equipments shall be finger touch proof. The Busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports shall be used. All meters shall be digital type with LED display. Operations Logic to be decided and approved by AAI before GA drawing submission by bidder. LOC:-POWER ROOM Incomer: 2 No 800 Amps 4 Pole ACB (50KA) with trip setting at 40 to 100% and terminals suitable for cable connections on one side and bus bar connection on the other side,as per specifications and complete with inbuilt protections (UV,OV,EF,SC and OL) and as required at site of work. (with current setting plugs) . Metering, Indication & Protection: 2 Sets of R,Y,B Phase Indicating lamps with Neutral link with control MCB. (3x2A). ON-OFF-TRIP indication lamps with control MCB (3x2 A) Multi function Meter ( equivalent to EM 6400) with CT -800/5A, 15VA, CL-1.0. BUSBAR SECTION : 1000 amps 4 Strip (50KA) busbar chamber of suitable length and cross sectional area with AL busbars with colour coded and Shrouded. All busbars and interconnections shall be of suitable size( AL ) at 1.5Amps/Sqmm. Neutral bar shall be of the same size as phase bar. Metering, Indication & Protection: ON-OFF-TRIP and all phase with neutral indication lamps with control MCB (3x2 A) Tie Breaker: Providing Installation,Testing,Commissioning of 1 No 800 Amps 4 Pole ACB (50KA) with trip setting at 40 to 100% and terminals suitable for cable connections on one side and bus bar connection on the other side,as per specifications and complete with inbuilt protections (UV,OV,EF,SC and OL) and as required at site of work. (with current setting plugs) . OUTGOING: Two (2) Nos. 300A, 4Pole MCCB (25 KA) with ON-OFF-TRIP Indication Lamp with MCB Control Lamps, EM 6400, CT 300/5A, CL-1, 15VA Cts. Complete as required Two (2) Nos. 200A, 4Pole MCCB (25 KA) with ON-OFF-TRIP Indication Lamp with MCB Control Lamps, EM 6400, CT 200/5A, CL-1, 15VA Cts. Complete as required Two (2) Nos. 160A, 4Pole MCCB (15 KA) with ON-OFF-TRIP Indication Lamp with MCB Control Lamps, EM 6400, CT 160/5A, CL-1, 15VA Cts. Complete as required Three (3) Nos. 63A, 4Pole MCCB (25 KA) with ON-OFF-TRIP Indication Lamp with MCB Control Lamps, EM 6400, CT 63/5A, CL-1, 15VA Cts. Complete as required. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of UTILITY PANEL: Incomer One (1) No. 250 A, 4P MCCB (25 KA) with ON-OFF-TRIP Indication Lamp with MCB Control Lamps, EM 6400, 250/5A, CL-1, 15VA CTs . Complete as required Busbar AL 300A Metering, Indication & Protection: 1 Set of R,Y,B Phase Indicating lamps with Neutral link with control MCB. (3x2A) ON-OFF-TRIP indication lamps with control MCB (3x2 A) Multi function Meter ( equivalent to EM 6400) with CT -300/5A, 15VA, CL-1.0 OutGoing 6 nos 63A 4 pole MCB 4 nos 32A 2 pole MCB
SITC of Aluminium CABLE: Supply, storing, handling, laying, testing and commissioning of 1100 Volt grade XLPE insulated and sheathed aluminium conductor armoured cables, ISI marked , including providing required gap between adjacent cables (minimum one cable dia.) including providing identification tags in shaft/ cable trays etc. complete as per specifications, as required (Low v/d losses). For detailed specifications, refer to Annexure VII and corrigendums.
4 C x 300 Sq.mm cable
4 C x 95 Sq.mm cable
STIC of Copper CABLE: Supply, storing, handling, laying, termination, testing and commissioning of 1100 Volt grade XLPE insulated and sheathed copper conductor un-armoured cables ISI marked including providing required gap between adjacent cables (minimum one cable dia.) including providing identification tags in shaft and cable trays in ground etc. complete as per specifications, as required. For detailed specifications, refer to Annexure VII and corrigendums.
1C x 150 Sq.mm cable
1 X 95 Sq.mm cable
1C x 70 Sq.mm cable
4C x16 Sq.mm cable
4C x10 Sq.mm cable
4C x 6 Sq.mm cable
SITC of Aluminium Cable Termination : Supplying of all materials and making end terminations of 1.1 KV grade XLPE insulated aluminium multi core cables of the following sizes. The work includes cable cladding using brass plated double compression glands, sizing the core leads, removing insulation, fixing suitable crimping type heavy duty aluminium lugs/ thimbles by using hydraulic crimping tools with correct size of the dies, shaping the leads and neatly connecting the same to the equipment terminals. Complete as required. For detailed specifications, refer to Annexure VII and corrigendums.
4 C x 300 Sq.mm cable
4 C x 95 Sq.mm cable
SITC of Copper Cable Termination : Supplying of all materials and making terminations of 1100 Volt grade PVC insulated and sheathed copper conductor unarmoured cables including providing required gap between adjacent cables (minimum one cable dia.) and the cost of providing identification tags in shaft/ cable trays/ in ground etc. The work includes cable cladding using brass plated double compression glands, sizing the core leads, removing insulation, fixing suitable crimping type heavy duty copper lugs/ thimbles by using hydraulic crimping tools with correct size of the dies, shaping the leads and neatly connecting the same to the equipment terminals. Complete as required. For detailed specifications, refer to Annexure VII and corrigendums.
1C x 150 Sq.mm cable
1C x 95 Sq.mm cable
1C x 70 Sq.mm cable
4C x16 Sq.mm cable
4C x10 Sq.mm cable
4C x 6 Sq.mm cable
SITC of Cable Trays (Ladder Type):Supply, fabrication and installation of Hot dip galvanized(deposit of 75-80 microns) factory fabricated ladder type cable trays complete with fabricated bends, tees, nuts bolts , dash fasteners, elbows, reducers, offsets etc & required hardware. with rungs at every 250 mm spacing (c/c) of various width in two tier/three/five tier formation either on one side of the wall or on two sides of the wall or at other places and painted afterwards, if required. For detailed specifications, refer to Annexure VII and corrigendums.
50mm x 450mm x 2mm wide cable tray with rungs of 15mm x 30mm x 15mm
50mm x 375mm x 2mm wide cable tray with rungs of 15mm x 30mm x 15mm
50mm x 150mm x 1.6mm wide cable tray with rungs of 15mm x 30mm x 15mm
SITC of PERFORATED TYPE CABLE TRAYS(GI TRAYS)/ WIREWAYS: Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. For detailed specifications, refer to Annexure VII and corrigendums.
300 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 50 mm depth X 2.0 mm thickness
SITC of STEEL ITEMS:Supply,fabrication,erection & epoxy painting of steel items as required as per specification complete, Generally steel items include cable tray, cable tray supporting arrangements,MS Channels-(ISMC),Angles,Plates and any other steel items not covered in other items of schedule of quantities. The cable trays shall be of ladder made of angles and flats / sheet steel folded type . The rate shall also include painting with two coats of red oxide and primer and two coats of synthetic enamel paint of approved shade. For detailed specifications, refer to Annexure VII and corrigendums.
SUPPLY & INSTALLATION OF INDOOR LIGHTING FIXTURES: Supply, Erection, Testing & Commissioning of the following light fixtures complete with Energy Efficient Electronic Ballast, Control gear and all the other standard accessories. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Light Panel: Supply and installtion of 2'x2' recess mounted LED light panel in the entire area in such a manner that the lux level in the server farm area must be 500 lux measure at 1 mtr from from floor level at all places. For other area it must be 300 lux measured in a similar manner. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Round LED Lights: Supply and installation of 9" dia round recess mounted LED light panel in the entire area. For detailed specifications, refer to Annexure VII and corrigendums.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc
Earthing with GI place including accessories, and providing masonry enclosure withEarthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick cover plate having locking arrangement and watering pipe of 2.7 metre long etc
SITC of POINT WIRING: FOR LIGHT FIXTRURES: Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. (SWITCHES & SOCKETS SHALL BE OF MODULAR TYPE). For detailed specifications, refer to Annexure VII and corrigendums.
Single point controlled by 6 Amps switch (conduit / wires / switches)
2 - 3 point controlled by 6 Amps switch (combined rate for 2 / 3 points)
SITC of INDUSTRIAL TYPE SOCKETS AND PLUG TOPS: Supply, store, erection, testing and commissioning of factory made metal clad totally enclosed with cast aluminium housing with industrial socket/interlocked combined rotary switch and socket with scrapping earth connection and plug top. In case of interlocked socket, the interlocking should ensure that the plug cannot be inserted or withdrawn while the switch is in 'ON' position. (all switches & sockets shall be housed in painted MS boxes). The erection rate shall include supply of angle iron frame work and fixing accessories such as grip bolts/grouting/ welding to steel structures etc., All the MCBs shall be of 'D' Curve specifications. For detailed specifications, refer to Annexure VII and corrigendums.
32A, 415V, 3P+N+E, IP 44 Male top with socket, Plastic moulded industrial socket with suitable straight plug, Surface mounted / Raceway mounted type. The pricing shall include to make the required supports on the floor/Raceway along with required accessories.
32A, 230V, 2P+E, IP 44 Male top with socket, Plastic moulded industrial socket with suitable straight plug, Surface mounted / Raceway mounted type. The pricing shall include to make the required supports on the floor/Raceway along with required accessories.
SITC of MODULAR TYPE: Supply, erection, testing and commissioning of power points by providing following switches/sockets mounted on suitable size metal coated boxes fixed flush/surface on to the wall with all fixing and wiring accessories. For detailed specifications, refer to Annexure VII and corrigendums.
6/16 Amps, 5-pin (250 Volts) single phase universal socket with 16 Amps single pole switch with indicating lamp.The pin configuration shall be round type. Plug tops are excluded from the scope of supply.(Normal Power)
6/16 Amps, 5-pin (250 Volts) single phase universal socket with 16 Amps single pole switch with indicating lamp.The pin configuration shall be round type. Plug tops are excluded from the scope of supply.(Safety and Security systems UPS Power)
SITC of SUB-MAINS/CIRCUIT MAINS/POWER WIRING: Supply and running of 1100 V grade FRLS PVC insulated copper conductor wires in 2mm thick FRLS PVC/ MS conduits as per Technical specification. The rate shall include all wiring & conduit accessories as aplicable. For detailed specifications, refer to Annexure VII and corrigendums.
Supply and running of 2Rx2.5 Sqmm + 1Rx1.5 Sqmm FRLS PVC insulated multistrand copper conductor wire in 25mm dia FRLS PVC conduits for lighting circuits from DB to switch boards & emergency lighting circuits from MCB DBs to SBs and light fixtures
Supply and running of 2Rx2.5 Sqmm + 1Rx1.5 Sqmm FRLS PVC insulated multistrand copper conductor wire in 25mm dia FRLS PVC conduits for Raw power circuits (1x6/16A) from DB to Sockets and looping between the sockets
Supply and running of 2Rx4 Sqmm + 1Rx2.5 Sqmm FRLS PVC insulated multistrand copper conductor wire in 25mm dia FRLS PVC conduits for UPS power circuits (3x6/16A) and CAC units from DB to Sockets and looping between the sockets
Supply, running and termination of 1C x 10 Sqmm Flexible FRLS PVC insulated multistrand copper conductor wire in existing conduits/raceways.
Supply and fixing of the following charts / drawings duly Laminated
Single line diagram & Escalation Matrix
Rubber Mating 1M x 1M X 12mm
SITC of MCB distribution board: Supplying and fixing 4 way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. For detailed specifications, refer to Annexure VII and corrigendums.
DG Foundation: Creating DG bed foundation as per manufacturer specification at the designated site. For detailed specifications, refer to Annexure VII and corrigendums.
DG control cable from Panel AMF module to the DG control panel as per manufacturer specification. For detailed specifications, refer to Annexure VII and corrigendums.
Creating Cable Trench from Substation and DG yard to the main building. Bidder has to inspect the site and suggest how the cable can be taken such as either in trench or buried under the gound and/or on ladder tray. For detailed specifications, refer to Annexure VII and corrigendums.
40mm MS conduit
Flexible MS conduit
SITC of Fire Resistant Sealant System: Multi Cable and Pipe transit sealant system for the site with fire resistant material. The block to be factory manufactured as per the size and number of cable and pipe entry. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Automatic Transfer Switch: Automatic Transfer Switch with two inputs and one output with contactor arrangement, source indication lamps housed in MS box to be used for inrow coolign units. For detailed specifications, refer to Annexure VII and corrigendums.
DIESEL GENERATOR PACKAGE. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of DG Set: Supply of 500 KVA SILENT DG Set comprising of 500 KVA, 415 V alternator mounted on a common base frame, complete with (a) Batteries & Leads, (b) AVM Pads.(c) Residential Silencer.(d) First fill of lube oil.(e) Acoustic Enclosure.(f) Manual control panel (Isolator), (g) Adapter box with extended Bus Bar (h) residential silencers with cladding,(i) 990 ltr fuel tank with base, (j) MS Pipe with Bends, flanges packing as required (k) Fuel Pipe fittings like valves, tee, elbows etc. For detailed specifications, refer to Annexure VII and corrigendums.
PRECISION AIR-CONDITIONING. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of PAC: Supply, installation, testing and commissioning of Precision air conditioner with horizontal air flow pattern, can be placed in-between the racks or at the ends of rows, close to the heat source with 9 TR Net sensible Load at return air tempareture of 32-35 deg C & 43-45 deg C ambient ) - Inside of Cold Aisle should maintain 22+/-1 deg C, 50+/-5% RH . Unit should have Inverter/Digital Scroll Brushless compressor compatiable with R410a refrigerant. Each unit should deliver minimum 125 CFM per every kW of cooling and UL Listed. For detailed specifications, refer to Annexure VII and corrigendums.
Refrigerant piping, insulation as required, cable tray for pipes and cables, electrical cable for connecting indoor and outdoor, ODU stand, IDU stand, drain pipe, ball valve and all other low side items required for complete commissioning of the job. Piping and all low side work has to be done for 09 units including dummy units. For detailed specifications, refer to Annexure VII and corrigendums.
AISLE CONTAINMENT For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Sliding Door: Heavy gauge Aluminium Sliding Door with viewing panel and support arrangement. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Aisle Containment: Aisle containment made of Aluminium panels and Lexan sheet with supporting arrangement. For detailed specifications, refer to Annexure VII and corrigendums.
COMFORT AIR-CONDITIONING. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of 22 HP VRV: SITC of 22HP Variable Refrigerant Volume modular type air-conditioning Equipment complete with indoor and out door units with Central control system for areas other than Server Farm Area Centre. Outdoor Unit: Modular type outdoor units equipped with highly efficient scroll compressors, having Inverter technology, Corrosion resistant heat exchanger, low noise condenser fan etc of following independent circuits. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Indoor Units: Supply & Installation of following Indoor Units. The indoor unit shall have independent electronic control valve to control the refrigerant flow rate respond to variations of the air-conditioning load of the room. The fans shall be well balanced and noise free. The cooling coil shall be made of seamless copper tube. The tube shall be hydraulically or mechanically expanded and tested for 21 Kg/cm2. Indoor units shall have a wireless remote control. All the unit shall have required ceiling/floor mounting arrangement. All the indoor units shall have drain pump/facility to drain out the condensate water. Indoor room temp requirement 24± 1 deg C. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of accessories of VRV : SITC of accessories of VRV system including refrigerant , refrigerant piping with insulation , central controller ,control wiring between indoor to outdoor units , drain piping , MS stand and any other related accessories required to complete the work as per site requirement & technical specification mentioned in the tender. For detailed specifications, refer to Annexure VII and corrigendums.
UPS FOR CRITICAL LOAD. Refer to Annexure VII and corrigendum for Detailed specification
SITC of UPS: Supply, fixing and commissioning of 100KW Modular UPS Scalable to minimum 175KW with dual electrical distribution cables and panels to racks. UPS to have hot swappable power modules , hot swappable intelligence module and should be in minimum size of 25 KW - 30KW power module capacities. The system shall comprise of a user-replaceable continuous duty single bypass static switch module rated as per the Frame capacity. The power modules should be replaceable without transferring load on to bypass and without shutting down the load. Batteries : Supply, interconnection and commissioning of maintenance free lead acid (VRLA) type Hot Swappable Modular Batteries for back up time for approx 30 minutes on full load unity power factor on each UPS. It should possible to add or replace battery modules without switching the load to bypass source. The bank of batteries shall comprise of required Nos of batteries connected in series and there should be multiple banks connected in parallel to provide redundancy. Monitoring :The UPS should monitor and annunciate the status of individual battery modules and bank level and perform temperature compensated charging depending on environment temperature. Notification should be provided on the UPS integrated display for add or removal of Battery modules and Power Modules. For detailed specifications, refer to Annexure VII and corrigendums.
FLOOR MOUNTED PDU FOR UPS OUTPUT: Supply, installation, testing, commissioning of 175 kVA Floor mount Modular PDU which should include minimum 24 Nos. Hot swappable 32 A Single Pole MCBs along with moulded cables and industrial sockets which shall be connected to individual PDU within the Server rack without any additional need of output panel and cables should be supplied as per required length. Individual branch circuit monitoring shall be provided and should monitor the voltage & current of individual MCB and shall keep the record of that. It should be possible to add or replace circuit breaker modules without switching OFF the complete load bus. The PDU should have spare space for adding additional minimum 18 Nos. in future which shall be hot scaleable without any downtime. For detailed specifications, refer to Annexure VII and corrigendums.
UPS FOR NON-CRITICAL LOAD. Refer to Annexure VII and corrigendum for Detailed specification
SITC of UPS for Non-Critical Load : Supply, fixing and commissioning of 80KVA/72 KW Unitary (NON MODULAR) Online double conversion IGBT based floor mounted UPS system for uninterrupted operation of Lighting, IBMS and PAC loads. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Batteries : Supply, interconnection and commissioning of maintenance free lead acid (VRLA) type Batteries for back up time for approx 30 minutes on full load. For detailed specifications, refer to Annexure VII and corrigendums.
RACKS AND PDU. Refer to Annexure VII and corrigendum for Detailed specification
SITC of Server Racks: SITC of 42U Server Racks ( 600 mm x 1200 mm/1000mm ) UL approved; The Rack should be able to with stand a minimum Static load of 1300 Kgs and Rolling load of 1000 Kgs.The unit should have a minimum of IP 20 rating for protection against touch, ingress of foreign bodies, and ingress of water. Rack front door should have minimum 60 % of open perforation for efficient air flow. ROHS Compliant. For detailed specifications, refer to Annexure VII and corrigendums.
Cable Manager: Removal type cable manager rings in rear side of the racks
Blanking Panels in each rack -20 nos
SITC of Rack PDUs:SITC of Metered Rack PDUs with socket level monitoring include locking IEC receptacles, and ultra low profile circuit breakers, ZeroU, 32A, 230V, with minimum (18) C13 & (3) C19 outlets, each PDU should have Hydraulic Magnetic breakers and overall width of the PDU should not exceed 70 mm so as to ensure sufficient space at rear side inside the rack. PDU should be UL, EN 55032,EN 55024 , IEC 60950-1, CE/VDE Compliant, ROHS compliant. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Network Racks: SITC of 42U Network Racks ( 750 - 800 mm x 1200 mm ) UL approved; The Rack should be able to with stand a minimum Static load of 1300 Kgs and Rolling load of 1000 Kgs.The unit should have a minimum of IP 20 rating for protection against touch, ingress of foreign bodies, and ingress of water. Rack front door should have minimum 60 % of open perforation for efficient air flow. ROHS Compliant
Removal type cable manager rings in rear side of the racks
Blanking Panels in each rack -20 nos
Rack based Automatic Transfer switch 32A Single phase
SITC of Temperature & Humidity Sensor to be integrated with DCIM Solution, Sensor Humidity Range ±4% RH from 20% to 90% RH % , Sensor Temperature Range 0 degrees C to 40 degrees C with ±2 degrees C accuracy . For detailed specifications, refer to Annexure VII and corrigendums.
ADDRESABLE FIRE ALARM SYSTEM. Refer to Annexure VII and corrigendum for Detailed specification
SITC of Detector: Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required
SITC of Call Points: Supply, installation, testing & commissioning of Addressable Manual Call Points (Break Glass Type). The same shall be square in shape & made of ABS plastic material. Surface / Flush Mounting. It shall have a "Break glass" message embedded on the glass. The addressable module shall be enclosed along with the break glass in a junction box & with required accessories.
SITC of Sounder: Supply, installation, testing & commissioning of Conventional Sounder / Hooter. The sounder shall be made of ABS plastic material & have the Db level of minimum 85dBs and a multi tone facility, wall mounted with mounting base & required accessories.
SITC of Input Module : Supply, installation, testing & commissioning of Addressable Monitor Module (Input Module) with Surface / wall mounting box & required accessories.
SITC of Output Module : Supply, installation, testing & commissioning of Addressable Control Module (Output module) with surface/ wall mounting box & required accessories.
SITC of Isolator: Supply, installation, testing & commissioning of Addressable Fault / Loop isolator module with Surface mounting backbox & required accessories.
SITC of Indicator: Supply, installation, testing & commissioning of Response indicator for Above false ceiling Detectors with required acessories.
SITC of Power Pack: Supply, installation, testing & commissioning of 24V DC power pack with battery backup. (for Strobe cum Sounders.)
SITC of FRLS: Supply and laying of 2C x 1.5 Sq.mm Copper Armoured Multi stranded FRLS cable on wall / slab or structure with necessary spacer & saddles. scope shall also include required end termination using gland,lugs & required accessories. (Red in Colour)
SITC of Hand held Fire Extinguisher: Supply, Installation, Testing and commissioning of Hand held Fire Extinguisher - Clean Agent Type -4.0 Kg as required to support all areas
ASPIRATION SMOKE DETECTION SYSTEM. Refer to Annexure VII and corrigendum for Detailed specification
Supply, Installation, Testing & Commissioning, calculations of flow and hole sizes in pipe network. Sampling unit shall be of LED technology. Detected smoke density shall be able to be adjusted between high sensitivity to equal as ordinary smoke detector. Sampling system is connected to loop for ordinary fire alarm via address unit. Operation of sampling unit and status shall be able to display in fire alarm central unit.
Power Supply Unit
Capillary set with nozzel
Sampling Points
Aspiration Tubes with 25mm dia
Electronic Hooter with mounting arrangement
2 core x 1.0 sq.mm Armored cable
GAS BASED FIRE SUPPRESSION SYSTEM. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Cylinder: 120 Litre Seamless Cylinder CCOE Approved, complete with valve assembly and a pressure gauge with a safety burst disc and a safety cap. ( quantity is indicative) For detailed specifications, refer to Annexure VII and corrigendums.
Novec 1230 Gas (indicative only, Bidder need to calculate the gas quantity and quote as per requriement only).
Electric Cum Manual Actuator.
Pneumatic Actuator.
Discharge Nozzles are designed to provide the proper flow rate and distribution of Novec 1230 to total flood a hazard area : 180 deg. / 360 deg.
Master Cylinder Adapter Kit
Flexible discharge Hose
Manifold Check Valve installed at the discharge manifold to allow removal of any Novec 1230 cylinder from the manifold while still retaining a closed system.
Flexible Actuation Hose
M.S. Container strap
Manifold Discharge Pressure Switch
Manifold with Mounting and all accessories
Seamless pipes as per ASTM A 106 Gr. B. Sch. 40 for Cylinder
Signages
Hooter Cum Flasher
Abort Switch
Release switch
Gas Release Panel
Battery 12VDC 7.2Ah
ACCESS CONTROL SYSTEM. For detailed specifications, refer to Annexure VII and corrigendums.
SITC of Access Controller: Supply installation Testing & commissioning of 4 Reader Main Access Controller Miroprocessor based, tamper protected wall-mount case and communicating on Backnet/TCP/IP. ACCESS CONTROL SYSTEM which includes interface modules. For Server Room and Conference room. For detailed specifications, refer to Annexure VII and corrigendums.
12 Vdc and 6 amp power supply for Controller and electromagnetic lock
Supply installation Testing & commissioning of Biometric (Finger Print) card Readers
Supply installation Testing & commissioning of Smart Card Readers
Supply installation Testing & commissioning of Push to Exit Buttons
SITC of Manual Break Glass Unit
Supply installation Testing & commissioning of 600 Lbs Single Leaf Electro magnetic Lock
Supply installation Testing & commissioning of 1200 Lbs Double Leaf Electro magnetic Lock
SITC of Access Management Software license with seamless integretion BMS Software complete with Graphic User Interface. ACS software shall be loading BMS workstation
BMS PC
Contactless iClass Smart Cards
Supply and Laying of 8 Core x 0.75 Sq mm, multi strand, copper, sheilded,Screened cable between the access controller and Card reader
Supply and Laying of 4 Core x 0.75 Sq mm, multi strand, copper, sheilded cable between the access controller and EM Lock/ door sensor /Push Button
25 mm PVC Conduit
Cat6 Cable for Controllers to Network Rack
CCTV SYSTEM. For detailed specifications, refer to Annexure VII and corrigendums.
IP Indoor Dome Camera 2MP Onvif Compliant
16 CH NVR with VMS software
6 TB Surveillance HDD
24 port PoE L2 Fully Managed Switch
32" LED display
9U Rack
Cat6 cable
PVC Conduit 25mm dia
RODENT REPELLENT SYSTEM. For detailed specifications, refer to Annexure VII and corrigendums.
Master Console panel including support bracket
SITC of Transducer capable of Emitting Ultrasonic sound of frequencies 20 Khz and higher, with blinking LED Indication & shall capable to covering area of 150 Sq ft in floor & ceiling void and 300 Sq ft in Room void.
Rodent Cable
25" PVC conduit including all accessories.
WATER LEAK DETECTION SYSTEM. For detailed specifications, refer to Annexure VII and corrigendums.
4 zone Water Leak detection panel with Modbus Connectivity and battery
Water leak detection cable sensor
Electronic Hooter
DATA CENTER INFRASTRUCTURE MONITORING SYSTEM ( DCIM). For detailed specifications, refer to Annexure VII and corrigendums.
DCIM system should be modular and support perpetual licensing which provides us flexibility to purchase and expand enhanced modules according to AAI future need. Proposed DCIM should be created in separate installations to maintain sanctity of data as follows: a. Gateway/Convertor Devices: Required for connecting to third party BMS/ third party BMS controllers/field devices and building side device Integrator system. b. Monitoring layer: Responsible for polling SNMP and Modbus TCP based Infrastrucure devices inside the datacenter like Rack Mount PDU, EMS systems etc. c.Customized Report generator to integrate with Operations and Monitoring Layers. Refer to Annexure VII and corrigendum for Detailed specification
Central monitoring software along with required Server, Desktop for dash boards monitoring, configuration and report generation and other accessories and cabling as required. Refer to Annexure VII and corrigendum for Detailed specification
NETWORKING ( PASSIVE)
OM4, MPO to MPO, Pre-terminated Cable, MPO12, 12-Fiber, LSZH, aqua jacket,15 m
OM4, MPO to MPO, Pre-terminated Cable, MPO12, 12-Fiber, LSZH, aqua jacket, 20 m
OM4 MPO to MPO, Pre-terminated Cable, MPO12, 12-Fiber, LSZH, aqua jacket, 25 m
OM4 MPO to MPO, Pre-terminated Cable, MPO12, 12-Fiber, LSZH, aqua jacket, 30 m
OM4 MPO to MPO, Pre-terminated Cable, MPO12, 12-Fiber, LSZH, aqua jacket, 50 m
OS2, SM MPO to MPO, Pre-terminated Trunk Cable, MPO12, 12-Fiber, LSZH, yellow jacket, 10 m
OM4 MPO/12 to MPO/12, 12-Fiber, LSZH, aqua jacket, 3 m
OM4 MPO to MPO, Pre-terminated Cable, MPO12, 12-Fiber, LSZH, aqua jacket, 10 m
OM4 LC to LC, Fiber Patch Cord, 1.6 mm Duplex, LSZH, aqua jacket, 3 m
OS2, SM LC to LC, Fiber Patch Cord, 1.6 mm Duplex, LSZH, yellow jacket, 3 m
OM4 LC to Unconnectorized, Fiber Pigtail, 0.9 mm LSZH
OM4 LC to Unconnectorized, Fiber Pigtail, 0.9 mm LSZH
1U Panel, accepts four modules or coupler plates with fiber management trough
HD 1U sliding Panel, accepts (4) modules, providing up to 48 duplex LC ports, or up to 32 MPO ports
Adapter Plate, 8 x MPO
OM4, MPO-12 Module, 2x12F MPO to 24F LC Aqua, Method B
UD 2U sliding fiber panel, providing up to 144 duplex LC ports or up to 96 MPO ports
ETL Verified Category 6A U/UTP Cable, White jacket, 4 pair count, 1000 ft (305 m) length, LSZH
Category 6A U/UTP Patch Panel, 24 port
CAT 6A U/UTP, Solid Cordage Modular Patch Cord, Blue Jacket, 3ft, LSZH
OS2, MPO-12 Module, 2x12F MPO to 24F LC Blue, Method B, singlemode
24F, OS2, SM, Single Jacket/Single Armor, Gel-Free, Outdoor Stranded Loose Tube Cable
HD 1U Sliding Splicing fiber Panel, accepts (4) modules, providing up to 48 duplex LC ports, or up to 32 MPO port
48F Splice Tray
Coupler Adapter 24 LC OS2, Blue
2 port Square Faceplates
4 port Square faceplates
4 x 6 inches Fiber Pathway/Runner/Guide for laying fibre inside the runner with all bends, T joints, straight lengths, junctions and exit points and with all accessories.
100 x 300 mm Cable Basket for laying Copper inside the Pathway with all bends, T joints, straight lengths, junctions and exit points and with all accessories. Refer to Annexure VII and corrigendum for Detailed specification
VIDEO WALL PACKAGE. For detailed specifications, refer to Annexure VII and corrigendums.
vIDEO WALL : Max. 1.29mm pixel pitch or better (Lower pitch is regarded as better) LED wall to make a minimum image size of 4.2 m (W) and 1.6 m (H) )(±5%) or higher. Resolution of total wall should be minimum 3000X1200. Resolution of total wall: shall be minimum 3000X1200 or more. LED Configuration: RGB 3 in 1; Technology :Max. 1.29mm or better pixel pitch direct LED wall. Brightness on screen: Minimum 600 nits. Controller should be from the same manufacturer and single controller must be capable of giving UHD(4K, 30 Hz or better) output. Pixel Density: 620,000 pixels/m2 or higher. LED lifespan: ≥ 80,000 hours. Control IP based control to be provided. System should have redundant remote rack based /in built redundant dual power supply , should be kept away from the wall to reduce heat and noise around the LED wall. Refresh rate: ≥3000Hz,Operating Temperature: 0-40°C or better. Maintenance Access: Should be 100% front serviceable. Horizontal / Vertical Viewing Angle: 160° H, 140° V or better. Mounting On stands As per the design requirement surrounded with false partition for flush installation look and feel. All cables, accessories, Mounting Kits required to complete the installations and commissioning of the system must be included. The video wall must be suppled with wall management software. Refer to Annexure VII and corrigendum for Detailed specification
SAT, ISAT, Tier certification and health check Audit. For detailed specifications, refer to Annexure VII and corrigendums.
Individual system final aceptance test and Integrated system acceptance test with simulation by connecting dummy step load at 50%, 75% and 100%. All parameter possible at site must be shown and recorded and submitted to AAI before handover of the site. Refer to Annexure VII and corrigendum for Detailed specification
“Data Centre Facility to be constructed under this Contract shall be Uptime Institute Tier III / TIA Rated 3Certified. The Successful Bidder shall obtain: -Uptime Institute Tier Certification III / TIA Rated 3of Design Documents for the Complete Data Centre Facility Design. -Uptime Institute Tier Certification III / TIA Rated 3 of Constructed Facility for all areas of the Data Centre Facility to be constructed under this Contract. -The necessary Certifications will be obtained on behalf of the Client and passed to the Client on Award. -All Certifications shall be kept current for the Contract Period; The Successful Bidder shall be responsible for all costs associated with obtaining and maintaining these Certifications. Refer to Annexure VII and corrigendum for Detailed specification
Half yearly Health check audit for the datacenter by third party agency for power , Cooling and IBMS installations. The agency must have prior experience of minimum 5 years in conducting the audit. All the tools requried for the audit such as power quality analyser, thermal imager, Air hood ( for measuring CFM), Annemometer, Lux meter, temperature logger etc must be used to capture the operational parameters of the system. Refer to Annexure VII and corrigendum for Detailed specification
Multi skilled technician for operations and maintenance of the data center for five years from the date of handover of the site. Each shift must have 2 manpower and there will be 3 shifts along with a supervisor in general shift. Refer to Annexure VII and corrigendum for Detailed specification
Other Items
Bidder Name
Amount in Words
Labotek
Nikom InfraSolutions Pvt. Ltd.
Nikom InfraSolutions Pvt. Ltd.