| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.4 LAccepted-AOC 24 25 MANGAL ARCADE TELCO ROAD OPP HOTEL DOUBLE TREE MOHAN NAGAR CHINCHWAD PUNE 411019 | PUNE | MAHARASHTRA | 411019 | L1 | Accepted-AOC REASONABLE | |
| 2 | L2₹24.9 L+₹3,616 (0.15%)Rejected-Finance 171 NARAYAN PETH PUNE PUNE MAHARASHTRA 411030 | PUNE | MAHARASHTRA | 411030 | L2 | Rejected-Finance HIGH RATE | |
| 3 | L3₹25.3 L+₹49,959 (2.01%)Rejected-Finance | L3 | Rejected-Finance HIGH RATE | |
| 4 | L4₹25.5 L+₹61,976.20 (2.50%)Rejected-Finance | L4 | Rejected-Finance HIGH RATE | |
| 5 | L5₹25.9 L+₹1.0 L (4.17%)Rejected-Finance 00 BHADAR TIKARMAFI BAZAR SULTANPUR UTTAR PRADESH 227413 | AMETHI | UTTAR PRADESH | 227413 | L5 | Rejected-Finance HIGH RATE |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
15 Jun 2022, 6:00 pmClosed
Shri Prveen Kumar, IDSE
GE NDA Khadakwasla
REPAIR/ MAINT OF FOCUS / FLOOD LIGHTS, HIGH MAST AND ALLIED WORKS AT NDA KHADAKWASLA
2022_MES_526724_1
8610/E8
Open Tender
Civil Works
Item Rate
180 days
GE NDA Khadakwasla
As per tender document
9 documents required · 9 mandatory
₹500
Yes
GE NDA Khadakwasla
₹60,000
Yes
5 Sept 2022
27 May 2022
17 Jun 2022
28 May 2022
15 Jun 2022
7 Jun 2022
29 May 2022 - 6 Jun 2022
Amount
Taking down the existing light fittings on multi mounting brackets from 16/21 mtrs highmast pole by taking on ground repairs/ replacing the defective parts like electronic drivers connection wires and refixing the same to its original position all as directed. Note: (i) Cost of spares , electronic drivers,connection wires replaced against above mentioned item will be measured & paid for separately under respective items of Sch 'A' here-in-below. (ii) The defects / repair of the floodlight making them functional after handing over defective floodlights of highmast (iii) Maintaining proper record of repair / maint in a well bound register duly bringing out the details of spares replaced on each and every flood light and getting it authenticated. (iv) Safety of his men engaged for executing the work along with safety equipment and clothes for the men shall be maintained.
Supply only following flood light spares of branded make as mentioned in the list of make enclosed with Particular specifications for replacement :- MCB TPN 230 volts C curve 63 amps Make L&T,Havells/Legrand)
Supply only MCB TPN 230 volts C curve 40 amps Make L&T/Havells/Legrand)
Supply only digital time switch, DIN type daily / weekly with 2 change over (CO), 16 amps 230 volts Make L&T/Legrand/Havells
Supply only Power contactor 16/18 amps 3 pole a.c. With 230 volts coil
Supply only Power contactor 40 amps 3 pole a.c. With 230 volts coil.
Supply only PVC insulated copper conductor FRLS grade two core cable 2.5 sqmm, ISI marked
Supply only PVC insulated aluminium conductor FRLS grade two core cable 2.5 sqmm, ISI marked
Supply only MCCB 63 Amps 4 pole 415 V Make L&T, /Legrand/Havells.
Supply only MCB DP 230 volts B curve 6-32 amps Make L&T/Havells/Legrand)
Supply only electronic driver for 200 watts flood lights Make should be as per the Existing manufacturer
Supply only electronic driver for 150 watts flood lights Make should be as per the Existing manufacturer
Supply only electronic driver for 100 watts flood lights Make should be as per the Existing manufacturer
Supply only electronic driver for 50 watts flood lights Make should be as per the Existing manufacturer
Surge protection device(SPD) of capacity 10/20 KV compatible with industrail & outdooor LED fixtures Make should be as per the Existing manufacturer
Supply only self adhesive PVC electrical insulation tape 7 mtr long with superior quality complete all as specified and directed.
Dismantling/ taking down the pole upto 16/21 metre height of high mast light by engaging suitable crane and repairing by replacing the unserviceable top pully of pole and other part such as winch motor, steel wire, power cable and servicing ,toping of oil and greasing the gear wheel assembly and hoisting, refixing and connecting up complete all as directed by Engr in charge. Note : a) The repair of light fittings and light fitting spares are measured and paid separately. b) Spares such as steel wire, motor, power cable etc will be measured and paid separately. c) The entire work shall be carried out with well experienced professionals who undertake the high mast poles dismantling /repair works. d) Minor spares such as screws, bolt/nuts, grease etc shall provided by the contractor without any extra cost over and above the quoted rate. )
S&F stainless steel rope twisted of size10mm/6 mm dia with necessary connections proper binding on both sides from bottom drum mast top connecting hook including taking down old unsv one complete all as specified and directed.
M & L for gear box oil of grade EP 90/140 in standard packed/sealed container including drain out old gear box and filling up new gear box oil complete all as specified and directed Make : HP/Servo/valvoline
Disconnecting electric connection and taking down carefully Fractional motor from highmast housing of any type and capacity as described below: -removing the burnt winding of motor rewinding with super enameled copper winding wire of suitable gauge or of matching size to the exisiting wires including all insulating material such as insulation paper sleeve, tape, varnishing etc and reassembling, testing, transporting back to site and refixing to original position all as directed
S&F 3 phase induction motor of 1HP heavy duty 415 V AC 50 Hz 1500 RPM Suitable for lifting of highmast as per existing make winch all as specified and directed
Supply & Laying, jointing & testing of UG LT cables XLPE insulated, aluminium conductor multi stranded armoured heavy duty 1100 Volt grade cross sectional area 16 sqmm 4 core laid in trenches/ ducts/ along poles/through pipe under road etc with new aluminium lugs of cable size all as specified and directed
Ditto all as per item No 22 above but size 10 sqmm 4 core
Ditto all as per item No 22 above but size 4 sqmm 3 core
Taking out existing defective worn out UG LT cable of any size 1100 volts grade from trenches of any size from different locations incl brick bats etc complete, all as specified and directed. (Note: Excavation & earth wk shall be measured and paid for separately),
Excavation in trenches in hard/dense soil n.exc 1.5 M wide and not exceeding 1.5 mts in depth in wide for laying of cables and n exc 1.5 mtr in depth and getting out incl dressing/trimming sides and levelling/grading and ramming of bottom of excavation complete all as specified and directed.
Excavation in trenches in soft/dis integrated rock n exc 1.5m wide and n.exc 1.5m in depth and getting out complete all as specified and directed.
Returning, filiing in incl spreading, leveling watering and well ramming excavated soil in layers not exceeding 25 cm thick each, filling back in trenches after cables have been laid and tested as specified
Removing excavated surplus soil obtained from excavation to a distance not exceeding 1.5 m above the starting point, complete all as specified.
M&L for laying of reinforced concrete pipe, dia of 150 mm 2 nos half round for bottom and top and before laying excaved area shall be levelling all as specified and directed. Note: One half round Top and One half round bottom together will be considered as one running meter.
S&F in replace of sintex box thermo plast (weather proof) IP 66, on flood light poles made out of thermoplastic of size 140mm x 140 mm x 95 mm size with connector for connecting incomming and outgoing of cable including 01 No of MCB SP 6 Amps to control the pole light circuit and MS brackets made out of 32 x 4 mm flats for fixing the box on post complete with nuts, bolts and wahers and suitable size of double compression cable glands for incomming, outgoing of cable Complete all as specified and directed Make Sintex Cat pat No GSJB-1414 or equivalent in any other approved makes.
S&F distribution box 2 Module 230V, 5 HZ, IP-65 & IK-09 Class-II, weatherproof cabinets, door and cabinet fully reversible, removable chassis and faceplates, including weatherproof glands, rails qty-1 Nos, coppper fork type 100 A busbars as short link including end caps, complete all as specified and directed Make: Legrand/L&T/Schinder
S&F in replace MCB DB 02 way SPN (single door) sheet metal enclosure factory made suitable for MCB DB's 240 volts with 200 amp rated busbar, neutral & earthing link bar, surface mounting complete including MCB SPN 06 Amp 230V, 50 HZ, complete all as specified and directed Make: L&T/Legrand/Havells
M&L for cutting hard standing by providing suitable T&P to make suitable size bore for & including fixing 32 mm dia GI pipe in road/cutting hard etc. including the cost of making good the disturbed surface and matching with existing (Chequered tiles/Road/PCC) complete all as specified and directed Note : Quoated rate includes 32 mm dia GI Pipe light grade also.
S & F of 100 watts flood light white in colour, LM6 aluminium or higher grade powder coated and water proof pressure die cast aluminium enclosure, with inbuilt electronic drivers and IP 66 protection complete ,Single phase, suitable for highlighting architectural facade and general purpose lighting etc fixing in MS chanel by drilling hole of suitable , size, using nut, bolts and washers of suitable size including suitable mounting structure as reqd at the site complete all as specified and directed. Make:Havells Catpart No.JETAALBAFLOODLIGHT100W/Cromopton/Philips
S & F of 150 watts flood light white in colour, LM6 aluminium or higher grade powder coated and water proof pressure die cast aluminium enclosure, with inbuilt electronic drivers and IP 66 protection complete ,Single phase suitable for highlighting architectural facade and general purpose lighting, etc fixing in MS chanel by drilling hole of suitable size, using nut, bolts and washers of suitable size including suitable mounting structure as reqd at the site complete all as specified and directed. Make:Havells Catpart No.JETAAIRISFL150WLED757ARNBLTG/Cromopton/Philips
S&F in replacement of 200 watt LED flood light luminaire with separate driver assemble box with secondary optics made in pressure die cast housing and heat sink in aluminium extrusion and IP 66, with suitable Mounting structure as per site requirement complete all as specified and directed Make Havells- Cat No JETAVALOURFL200WLED757MODNBLTG/Crompton/Luker or any other approved makes
S&F in replace of 300 watt LED flood light luminaire with separate driver assemble box with secondary optics made in pressure die cast housing and heat sink in aluminium extrusion and IP 66, with suitable Mounting structure as per site requirement complete all as specified and directed Make Havells- Cat No JETAVALOURFL300WLED757MODNBLTG/Crompton/Luker or any other approved makes
S&F in replacement of 400 watt LED flood light luminaire with separate driver assemble box with secondary optics made in pressure die cast housing and heat sink in aluminium extrusion and IP 66, with suitable Mounting structure as per site requirement complete all as specified and directed Make Havells- Cat No JETAVALOURFL400WLED757MODNBLTG/Crompton/Luker or any other approved makes
M&L for straight through joint (epoxy) for PVC insulated and sheathed aluminium conductor under ground cable incl freud , thimbles, nut & bolts, washers etc and testing afterjointing complete, all as specified and directed 16 sqmm to 35 sqmm 3.5 core cable Make: M-seal/Raychem/Cabseal/ Denson
S & F PVC insulated multistranded copper conductor 3 core 10 sqmm for connection of floodlight on rooftop and fixing with suitable size clamp and connecting with suitable size copper lugs complete all as specified and directed. Make Polycab/Havells/Finolex
S & F PVC insulated multistranded copper conductor 4 core 10 sqmm for connection from panel to high mast fitting, and connecting with suitable copper lugs complete all as specified and directed. Make Polycab/Havells/Finolex
S&F in replacement of automatic timer switch distribution board, factory assembled in powder coated sheet steel enclosure, comprising of 40 Amps 3 Pole MCB, power contactor and 230V digital time switch for controlling LED/SV etc street lights , including earth work for fixing Timer switch distribution Board and shall be provided 4 Nos 35x35x4mm thick angle iron supports of not less than each 0.6 mt height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement all as specified and directed Make Indoasina Cat Pat No.TL040DB0/L&T/Legrand
S & F in replacement Busbar panel weather proof outdoor type single door, fabricated out of 3.15 mm thick CRCA sheet with epoxy powder coating of RAL-7035 ( Siemens Gray) shade with matt finish with seven tank pre treatment process.The panel shall be provided with aluminium bus bars, 300mmX40mmX5mm(thickness) electrolytic grade of adequate rating. The bus bars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with 4. RYB & black colour coding and fix horizontally. The panel shall be provided with 04 Nos 25mmx25mmx3mm thick angle iron supports of not less than each .3 mtr height duly painted with anti corrosive black paint and grouted on wall (at Sudan Dome)and suitable fixing arranement as per site requirement. The overall size of the Busbar panel shall be 350mmx200mmx400mm (LxBxH).including PCC (1:3:6) complete all as directed and specified.
M & L for PVC insulated aluminium conductor FRLS grade two core cable 2.5 sqmm ISI marked including PVC conduit pipes of dia not less than 19 mm complete all as specified and directed.
M&L for earthing complete with galvanised steel earth plate electrode 600x600x6.3mm thick, burried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron strip 32 X 6 mm of 15m length by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 in SSR PART-I connected to earthing test point all as specified or indicated including provision of earthing lead protection pipe, PCC earth pit with cover, excavation & earth work, testing on completion etc all as specified and directed.
S&F in replacement integral LED aviation light comprising housing with polycarbonate enclosure, aviation light is to be fixed on highmast light frame complete all as specified and directed. make Bajaj Catpart No: BGAV302LED or equivalent in Havells/Wipro/Luker/ Havells
S&F 1x18 watt WW (3000K) LED bollard outdoor gate light with polycarbonate diffuser and IP 65 protection incl demolition of existing PCC and make suitable PCC for new bollard as per site requirement and fixing arrangements all as directed Make Luker Catpart No: LGLRBGE-27 or equivalent in havells or philips
S&F 1x10 watt WW (3000K) LED outdoor gate light with polycarbonate diffuser and IP 65 protection incl demolition of existing PCC and make suitable PCC for new bollard as per site requirement and fixing arrangements all as directed. Make Luker Catpart No: LGLSMD or equivalent in havells or philips
S&F GI tubing light grade 40 mm dia isi marked appx 1 mtr to 1.5 mtr long with Flat Iron Base for mounting of Flood light with all fittings incl nut,bolt,washers suitable size and also make the hole for pole for entry of the 2.5 sqmm PVC conductor all as specified and directed at site.
Supply,install, commission and testing cubical type LT panel board,outdoor type, manufactured by a CPRI approved factory, floor mounted, dust & vermin proof,front and rear operated door with necessary locking arrangement made of 50 x 6mm MS angle iron frame work and CRCA sheet of 3.15mm thick duly painted with two coats of powder coated paint of approved shade after seven tank treatment process both internally and externally. The panel shall be suitable for 415 Volts, 50 HZ, 3 Phase 4 wire system and shall be complete with suitable capacity aluminium bus bar (1.5 times the incoming switch gear current rating) with suitable size of PVC insulated copper conductor, thimbles glands complete all as specified and directed with the following accessories : (a) MCCB 63 A 4 Pole 415 V 25 KA - 01 No (Incoming) (b) MCB 40 A SP Pole 10 KA L&T - 04 Nos (c) Street light timer Digital Switch - 1 No (d) Power contracts 32 MNX 3 pole - 1 No (e) Aluminium bus bar 4 strip (f) Internal wiring for panel incl insulators, sleeves etc (g) Painting and treatment as per CPRI
S&F in replacement of LED rope light out door 12 W 24V IP 68 with warm white incl 2 Pin power supply connector,Connector pin, and End cap as per site requirement fixing at roof of the bldg with suitable PVC saddles for every one mtr on rope. Make : Luker Cat part No LSO68 or equivalent in Wipro/ Polycab
S & F Connector suitable for LED Strip outdoor 12 W 24 V IP 68 fittings
S&F Connector pin suitable for LED Strip outdoor 12 W 24 V IP 68 fittings
S&F in replacement integral 25 Watt LED post top lantern black/ copper dust painted cast aluminium spigot, spun aluminium canopy with clear acrylic cover and accessorieson on existing GI Pipe of diameter complete all as specified and directed.Make Havells catpart No.CORALPT25WLED757PSYMTOPC/ luker/ Crompton
S&F 1x18 watt WW (3000K) LED bollard Integral decorative LED bollard with polycarbonate diffuser and IP 65 protection incl demolition of existing PCC and make suitable PCC for new bollard as per site requirement and fixing arrangements all as directed Make Luker Catpart No: LOBRD60 or equivalent in havells or philips (Quoated rate includes PCC work also)
S&F of decorative outdoor(IP-54) bollard with castor antique finish including E-27 base 14 watt WW LED bulb/lamp with necessary accessories complete all as specified. Make Luker Catpart No: LBF012E27AG or equivalent in havells or philips. Note: Quoted rate shall be deemed include the 14 watt bulb
S&F in replacement of 60 W LED Out door post top light ,Correlated colour temperature 5700 K, post top with diecast aluminium body confirm to IP-66 , incl suitable arrangements for pole 3.5 mtr decorative pole complete directed Make - Bajaj/HPL/Luker
M&L for PCC (1:2:4) type B-1 (Using 20 mm graded stone aggregate) as in coping of pole sand including forme work and demolition of existing coping complete all as specifed and directed.
S&F in replacement of cylindrical panel locks of suitable size or as per sample including drilling,cutting and welding etc in panel sheets without disturbing to other existing fitments and directed.
Supply only fixing in repair of cylindrical panel locks as per sample including drilling,cutting and welding etc in panel sheets without distrubing to other existing fitments complete all as specified and directed.
S&F in repalcement of old broken cold rolled mild steel hinges of existing busbar etc of suitable size or as per sample including welding and painting to match with existing colour of panel sheet etc all as specified and directed.
M&L for preparation of existing surface of busbar and supporting surface angle iron of busbar by scraping down, peeled off old paint,cleaning etc and applying one coat of smoke grey paint to busbar incluidng clenaing of busbars from inside by blowing compressed air etc complete all as specified and directed.
Labour for disconnecting exisitng incoming and outgoing cables from existing busbar after taking proper shutdown and excercising all safety precautions, human safety, removing the old busbar panel complete with its accessories and setting a side at safe place and after changing CRCA sheet of thickness 2mm thick busbars angle iron supports etc including all cables re-terminated according to existing system with busbar panel all as specified and directed.
S&F against item No 64 above in replacement busbar panel of 2mm thick CRCA sheet with epoxy powder coating of RAL 7032(Smoke grey). Note: Size and design of item shall be executed as per site requirement and also approved
KESARI AND SONS
Sneha Aircool
Sparkh Electricals & Works
M/S DEV ENTERPRISES
SONU ENTERPRISES
M/s Harshal Traders
CHAITANYA WINDWELL
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .