| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹31.5 LAccepted-AOC KOTHI NO 766 PHASE III MODEL TOWN BATHINDA PB | L-1 | Accepted-AOC Being lowest bidder | |
| 2 | L-2₹44.7 L+₹13.2 L (41.8%)Rejected-Finance | L-2 | Rejected-Finance Not being lowest bidder | |
| 3 | L-3₹47.0 L+₹15.5 L (49.0%)Rejected-Finance | L-3 | Rejected-Finance Not being lowest bidder | |
| 4 | L-4₹47.2 L+₹15.6 L (49.6%)Rejected-Finance 19192 STREET NO 8 BIBI WALA ROAD OPPOSITE DAV COLLEGE BATHINDA PUNJAB PIN 151001 | BATHINDA | BATHINDA | PUNJAB | 151001 | L-4 | Rejected-Finance Not being lowest bidder | |
| 5 | L-5₹49.0 L+₹17.5 L (55.5%)Rejected-Finance | L-5 | Rejected-Finance Not being lowest bidder |
Tender Value
₹57.2 L
EMD Value
₹1.1 L
Closing Date
3 Feb 2024, 6:00 pmClosed
CWE Bathinda
HQ CWE Bathinda Bathinda Mil Stn
ADDITION/ALTERATION INCLUDING REPAIRS TO INTERNAL ELECTRIFICATION AT BLDG OF KENDRIYA VIDYALAYA SCHOOL NO.1 UNDER GE(S) BATHINDA AT BATHINDA MIL STN
2023_MES_634445_1
CWE BTD/TOKEN-53/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Bathinda Mil Stn
As per NIT
7 documents required · 7 mandatory
₹1,000
GE (South) Bathinda
₹1.1 L
HQ CWE Bathinda
4 Apr 2024
27 Dec 2023
5 Feb 2024
27 Dec 2023
3 Feb 2024
19 Jan 2024
4 Jan 2024
Amount
Taking down carefully existing unserviceable copper / aluminum point wiring (light, fan, socket) complete including removal of unserviceable fittings such as switches,bell pushs , ceiling roses,Pendent,regulators, sockets, light fittings, call bells etc. removing the material to KV School store for keeping in safe custody or for taking credit all as specified and as directed by Engineer-in- charge. Note: weight of Aluminium / Copper scrap shall be ascertained by Board of officers as ordered by GE.The copy of BOO duly countersinged by GE shall be enclosed with final Bill.
Material and Labour for point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits), with 2.5 Sqmm nominal cross sectional area single core PVC insulated, unsheathed 'multi stranded' FRLSH copper cable, 1100 volts grade, with multi stranded copper conductor drawn through and including non-metallic, rigid non mettalic PVC conduit (medium grade) 20mm bore surface on wall / ceiling with and including 2.5 sqmm single core PVC insulated, multistranded, unsheathed, FRLSH copper conductor cable as continuous earth continuity conductor (green in colour) including modular metal flush box concealied with front & modular cover plate with frame suitable matching colour of required module for mounting or housing switches, socket outlets, fan regulators, etc. including blanking plates & all other fixing accessories for one light/fan/call bell/exhaust fan point controlled by one 5/6 Amps switch or bell push or one 5/6 Amp switch and fan regulator and including cutting chases (as required) and making good surfaces to match with adjoining surface complete all as specified and as directed by Engineer-in-charge. NOTE:- The quoted unit rate is deemed to be inclusive of cost of metal flush boxes, modular white cover plates, modular frame plates and flush fixed with cement mortar 1:4 etc.However modular switches,sockets and regulators shall be measured and paid seperately under respective items of Schedule'A' BoQ.
All as per serial item No 2 here in before but for one additional light point on the same switch circuit complete all as specified and as directed by Engineer-in-charge.
All as per serial item No 2 here in before but for one socket outlet 3 pin 5/6 Amps 250 volts on same board complete all as specified and as directed by Engineer-in-charge.
All as per serial item No 2 here in before but for one socket outlet 3 pin 5/6 Amps 250 volts on Independent board complete all as specified and as directed by Engineer-in-charge.
All as per serial item No 2 here in before but for socket outlet one 6 pin, 6/16 Amps, 2 in 1 with cable 2.5 Sqmm multistranded copper conductor FRLSH cable on the independent board including provision of 2.5 Sqmm PVC insulated copper conductor FRLSH cable continuos as earth wire connected to earth dolly, conductor etc complete all as specified and as directed by Engineer-in-charge.
Material and labour for concealed Point wiring for one light point controlled by 02 x two way switches (using red, black and green colour wires as colour coding) complete with 1.5 Sqmm (nominal cross section area) single core FRLSH PVC insulated unsheathed and multi strand copper conductor cable 1100 volt (ISI marked) drawn through and including PVC conduit 20mm dia (medium duty, ISI marked) with all fittings and all accessories i.e. pipe bend, pipe hook, elbow, junction box, 2mm thick galvanised steel pressed sunken terminal boxes of suitable size (Min 60mm deep, suitable length) concealed in wall, 3mm thick bakelite plastic laminated sheet top cover for sunken boxes flush to surface for mounting of switches / socket / regulator etc, including provn of 1.5 Sqmm single core FRLSH PVC insulated multi strand copper conductor wire continues as earth wire connected to earth dolly etc. including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3) complete all as specified and as directed by Engineer-in-charge.. (switches, regulator shall be measured and paid separately under appropriate item of BOQ).
Supply and fixing Modular Switch 1 way 6A,1 Module complete all as specified and directed by Engineer-in-charge.
Supply and fixing Modular Switch Two way 6A,1 Module complete all as specified and directed by Engineer-in-charge.
Supply and Fixing Modular Bell push 6A 1 module complete all as specified and as directed by Engineer-in-charge.
Supply and fixing Modular Switch one way 16 Amp 240 Volt, AC ,1 Module complete all as specified and directed by Engineer-in-charge.
Supply and fixing Modular Socket Outlet , Multipurpose,3 Pin, 6 Amp , 2 Module complete all as specified and directed by Engineer-in-charge.
Supply and fixing Modular Socket outlet , multipurpose, 3 Pin, 6/ 16 Amp 2 Module complete all as specified and directed by Engineer-in-charge.
Supply and Fixing Modular type Five step High speed Fan regulator, Electronic Type , 2 module complete all as specified and as directed by Engineer-in-charge.
Supply and Fixing ceiling rose surface type polycarbonate, isolated body three teriminal, tpline series 20 x 50mm, 6 Amps, three terminal complete all as specified and as directed by Engineer-in-charge.
Supply and Fixing Call Bell Ding dong , AC, 230 volts, single pole ISI mark complete all as specified and as directed by Engineer-in-charge.
Supply and Fixing wall mounted extruded Aluminium/polycarbonate integrated LED batten fixture with tube 1.2 m, 20watt, 1.2 m 6500K, efficacy not less than 90 lumen/watt, extruded Aluminium/polycarbonate, PC diffusor and integrated inbuilt driver ,complete with and including connection with copper cable of suitable size from ceiling rose to fitting complete all as manufacturer's instructions ,as specified and as directed by Engineer-in-charge.
Supply and Fixing wall mounted LED batten fitting 10 (±10%) watt, 6500K, 0.6m, efficacy not less than 90 lumen/watt , extruded Aluminium/polycarbonate, PC diffusor and inbuilt driver complete with and including connection with copper cable of suitable size from ceiling rose to fitting complete all as manufacturer's instructions ,as specified and as directed by Engineer-in-charge.
Supply and Fixing pendent type LED batten fixture T8(G13 holder) 1.2 m, extruded Aluminium/polycarbonate, including 2x LED retrofit tube 20(±10%) watt, 1.2 m T8 6500K,efficacy not less than 90 lumen/watt, extruded Aluminium/polycarbonate, PC diffusor and inbuilt driver complete with and including connection with copper cable of suitable size from ceiling rose to fitting complete all as manufacturer's instructions ,as specified and as directed by Engineer-in-charge.
Supply and Fixing LED panel light fitting, surface mounted, square shaped of size (600mm x 600mm x 70) mm, 34(±10%)watts efficacy not less than 120 lumen/watt, extruded Aluminium/polycarbonate, PC diffusor, module and inbuilt driver complete with and including connection with copper cable of suitable size from ceiling rose to fitting complete all as manufacturer's instructions ,as specified and as directed by Engineer-in-charge.
Supply and Fixing LED street light fitting 35 Watt 230V AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp bracket with impact and corrossion resistant complete with IP 65/66 protection including fixing with GI/MS bracket made out of suitable size of light grade tube upto 1.2 mtr length bent to shape with 02 sets of MS clamps made out of minimum 3 mm MS flat iron with suitable bolt and nuts complete with and including connection with copper cable of suitable size from ceiling rose to fitting complete all as manufacturer's instructions ,as specified and as directed by Engineer-in-charge.
Supply and Fixing LED flood light fitting sqaure shape 100 Watt 230V AC having efficiency not less than 130 Lm / Watt outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp, with impact and corrossion resistant complete with IP 65/66 protection size fixing at any height upto 15m complete with and including connection with copper cable of suitable size from ceiling rose to fitting complete all as manufacturer's instructions ,as specified and as directed by Engineer-in-charge.
Supply and Fixing Post top lantern LED type 20 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistance complete with driver and lamp connection with and including copper cable of suitable size from ceiling rose to fitting complete all as manufacturer's instructions ,as specified and as directed by Engineer-in-charge.
Material and Labour in replacement for Sub main wiring concealed PVC conduit with two single core of size 4 Sqmm FRLSH PVC insulated unsheathed with multistranded copper conductor cable 1100 volts grade drawn in and including non metallic rigid PVC conduit & conduit fittings medium quality of size 20 mm dia conforming to 3537 Part-I ISI marked including one single core of size 4 Sqmm FRLSH PVC insulated unsheathed with multistranded copper conductor cable 1100 volts grade as in contineous earth conductor cable connected to earth dolly complete all as specified and as directed by Engineer-in-charge.. (Colour code phase-Red, Neutral-black and Earth as Green) complete all as specified & directed.Notes:-(a) Cost of PVC conduit , conduit accessories and earth wire included in sub main wiring. (b) Three single core 4 Sqmm FRLSH PVC insulated unsheathed with multistranded copper conductor cable 1100 volts grade including non metallic rigid PVC conduit of size 20 mm dia shall be measured as one length.
Material and Labour in replacement for Sub main wiring concealed PVC conduit with two single core of size 6 Sqmm FRLSH PVC insulated unsheathed with multistranded copper conductor cable 1100 volts grade drawn in and including non metallic rigid PVC conduit & conduit fittings medium quality of size 25 mm dia conforming to 3537 Part-I ISI marked including one single core of size 6 Sqmm FRLSH PVC insulated unsheathed with multistranded copper conductor cable 1100 volts grade as in contineous earth conductor cable connected to earth dolly complete all as specified and as directed by Engineer-in-charge.. (Colour code phase-Red, Neutral-black and Earth as Green) complete all as specified & directed.Notes:-(a) Cost of PVC conduit , conduit accessories and earth wire included in sub main wiring. (b) Three single core 6 Sqmm FRLSH PVC insulated unsheathed with multistranded copper conductor cable 1100 volts grade including non metallic rigid PVC conduit of size 25 mm dia shall be measured as one length.
Material and Labour in replacement for Sub main wiring concealed PVC conduit with two single core of size 10 Sqmm FRLSH PVC insulated unsheathed with multistranded copper conductor cable 1100 volts grade drawn in and including non metallic rigid PVC conduit & conduit fittings medium quality of size 32 mm dia conforming to 3537 Part-I ISI marked including one single core of size 10 Sqmm FRLSH PVC insulated unsheathed with multistranded copper conductor cable 1100 volts grade as in contineous earth conductor cable connected to earth dolly complete all as specified and as directed by Engineer-in-charge.. (Colour code phase-Red, Neutral-black and Earth as Green) complete all as specified & directed.Notes:-(a) Cost of PVC conduit , conduit accessories and earth wire included in sub main wiring. (b) Three single core 10 Sqmm FRLSH PVC insulated unsheathed with multistranded copper conductor cable 1100 volts grade including non metallic rigid PVC conduit of size 32 mm dia shall be measured as one length.
Material and Labour in replacement for Sub main wiring concealed PVC conduit with Four single core of size 25 Sqmm FRLSH PVC insulated unsheathed with multistranded copper conductor cable 1100 volts grade drawn in and including non metallic rigid PVC conduit & conduit fittings medium quality of size 40 mm dia conforming to 3537 Part-I ISI marked including Two single core of size 25 Sqmm FRLSH PVC insulated unsheathed with multistranded copper conductor cable 1100 volts grade as in contineous earth conductor cable connected to earth dolly complete all as specified and as directed by Engineer-in-charge.. (Colour code phase-Red, Neutral-black and Earth as Green) complete all as specified & directed.Notes:-(a) Cost of PVC conduit , conduit accessories and earth wire included in sub main wiring. (b) Six single core 25 Sqmm FRLSH PVC insulated unsheathed with multistranded copper conductor cable 1100 volts grade including non metallic rigid PVC conduit of size 40 mm dia shall be measured as one length.
Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 10 Sqmm 2 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately)
Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 16 Sqmm 2 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately)
Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 70 Sqmm 4 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately)
Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 120 Sqmm 4 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately)
Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 185 Sqmm 4 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately)
Material and Labour Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 4 core XLPE armoured aluminium conductor cable of size 16 sqmm to 35 sqmm complete all as manufacturer's instructions ,as specified and as directed by Engineer-in-charge.
Material and Labour Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 4 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as manufacturer's instructions ,as specified and as directed by Engineer-in-charge.
Material and Labour Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 4 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm complete all as manufacturer's instructions ,as specified and as directed by Engineer-in-charge.
Excavation in trenches, not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for pipe line, cable trenches or for manholes etc not exceeding 10 sqm area on plan and not exceeding 1.5 metre in depth and getting out in soft/loose soil complete all as specified.
Returning filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm thick complete all as specified.
Removing excavated soil to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified.
Material and Labour sand cushioning, with dry and clean fine river sand for underground cable 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of cable complete all as specified. (Note:- Punned thickness shall be considered for payment purpose)
Supply and laying un-reinforced precast concrete cable cover, Class LV, Type 1, Flat size 250mm x 150mm x 40mm ISI Marked for protection of under ground cable complete all as specified and directed.
Material and Labour for PCC (1:4:8) type D2 using 40mm graded crushed stone aggregate as in foundation of poles etc, filling and mass concrete including necessary form work complete all as specified.
Material and Labour for PCC (1:3:6) type C2 using 40mm graded crushed stone aggregate as in coping of poles etc,e including necessary form work complete all as specified.
Supply and fixing GI tubing, light grade 40 mm bore complete with all fittings for cable protection, fixed along poles or laid under floor , under road and hardstanding etc. and making good after laying of cable complete all as specified and as directed by Engr - in- Charge.
Supply and fixing GI tubing, light grade 50 mm bore complete with all fittings for cable protection, fixed along poles or laid under floor , under road and hardstanding etc. and making good after laying of cable complete all as specified and as directed by Engr - in- Charge.
Material & Labour cast iron Cable route indicator oval shaped of size 200mm x 150mm x 6 mm thick with and including letter embossed as "LT UG CABLE" and fixed on 25mm x 25mm x 6 mm MS angle iron 450 mm long embedded in PCC block 20cm x 20cm x 20cm in PCC 1:3:6 type C1 using 20 mm stone aggregates with and including two coats of synthetic enamel paint over a coat of red oxide zinc chromate primer on exposed steel surfaces complete all as specified and as directed by Engineer-in-charge.
Material and Labour Steel tubular swaged pole type 410 SP-31 (9.00mtr long) complete with cast iron base plate, finial, taper plug, bolts nuts & screws complete all as specified including internal surface of steel tubular pole through out and external surface up to planting depth shall be painted with bituminous paint and remaining external surface shall be treated with two coats of aluminium paint over a coat of red oxide zinc chromate primer complete and painting upto 1.5 mtr with alternate layer of yellow & black including marking Sr No of the poles all as specified. Note:- Necessary earthwork and cement concrete work shall be measured and paid seperately in respective items of respective schedules. (Note:- Excavation, earthwork and PCC shall be measured and paid separately under respective item of Sch.)
Supply and fixing junction box ,size not less than 200mm x 160mm x 98mm, insulated type , made out with Polycarbonate with glass fiber reinforced. Note :-1.Manufacturer should submit routine test certificate for CJB/PJB 2.The Polycarbonate Junction Box shall be environment friendly, recyclabe, UV resistant, halogen & silicon free, anti acid & anti corrosive. 3. The Junction Box shall be rated for Degree of ingress Protection IP 66 in accordance with IEC 60529. 4.The gasket material of junction box shall be Polyurethane and the gasket shall be internally embedded. 5.The Junction Box shall be complies with requirements of the standards IEC 60998 - 1, IEC 60988 - 2 - 1, IEC 60670 - 22 & IEC 60670 - 2 - 5. 6. The Junction Box color according to RAL 9011. 7.The manufacturer of Junction Box / Enclosure shall submit a copy of IEC Certificate . For better safety the Polycarbonate enclosure and shall be fire retardant & self - extinguishing in accordance with IEC 60695 - 2 - 11, DIN VDE 0304 Part - 3, UL Subject 94 for Flammability V-2. It should be tested at Glow Wire test for 960 degree Centigrade. The impact strength of Polycarbonate enclosure / boards i.e. the Degree of protection against mechnical load shall be in accordance with EN 50298 - 98 for IK 08.
Material and Labour Bracket made with GI pipe 40mm dia medium grade at 120 degree angle,1.2 mtr long ,including fixing with help of 02 Nos. MS clamps made out with flat iron 40mm x 5mm, nuts, bolts and washers etc.including duly painted with two coats of aluminium paint paint over a coat of red oxide zinc chromate primer complete all as specified and directed by Engineer in charge.
Supply , installation, commissioning and testing Wall Mounting indoor type LT Panel board made of Polycarbonate ASTA CPRI approved OEM made main LT Panel embedded with PU gasket with conical top with thimble and cable entry boxes with cable glands. The panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES including MCCBs and indicator lamps which shall be UV resistance in accordance with IEC 61439-1, clause 10.2.4: The panel shall be IP 65, IK 08, anti-acid & anti corrosive. Panel should covered from all sides with front and back lockable door and hinges complete with copper bus bar with heat shrinkable PVC sleeve, DMC insulators, TPN, three phase, 04 wire (In separate chamber), Internal Power & control wiring with suitable size PVC insulated FRLS single core multistranded copper wire cableand including panel painting The manufacturer of panel shall submit a copy of ASTA CPRI TEST REPORT IN POLYCARBONATE only also share panel assembled by OEM only. TYPE TEST & ROUTINE TEST REPORT to be submitted. The ASTA CPRI report shall have mention of following tests performed and passed out satisfactorily - Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak & short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits. The panel shall pass glow wire test 960 degrees Centigrade in accordance with 60695-2-11 [flame retardant and self-extinguishing] with and including pedestal/ frame grouted in PCC (1:2:4) type B-1 20mm graded stone aggregated, thimble and cable entry boxes with cable glands comprising of following accessories complete all as specified and directed by Engineer-in-charge :- INCOMER: (i) MCCB 250 Amp, 4 pole 25 KA 415V Fixed Thermal & Magnetic Released - 01 No. (ii) Onload Manual Change over Switch 200A 4Pole - 01 No. (iii) Set of LED RYB type indicating lamps - set of three (iv) Copper Bus Bar 400Amp TPN OUTGOINGS: (i) MCB 63/100 Amp, FP 10KA 415V C-Curve - 04 Nos. (ii) MCB 63/100 Amp DP 10KA 230V C-Curve - 10 Nos. (iii) MCB 10-32 Amp DP 10KA 230V C-Curve - 06 Nos.
Supply , installation, commissioning and testing Wall Mounting indoor type LT Panel board made of Polycarbonate ASTA CPRI approved OEM made main LT Panel embedded with PU gasket with conical top with thimble and cable entry boxes with cable glands. The panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES including MCCBs and indicator lamps which shall be UV resistance in accordance with IEC 61439-1, clause 10.2.4: The panel shall be IP 65, IK 08, anti-acid & anti corrosive. Panel should covered from all sides with front and back lockable door and hinges complete with copper bus bar with heat shrinkable PVC sleeve, DMC insulators, TPN, three phase, 04 wire (In separate chamber), Internal Power & control wiring with suitable size PVC insulated FRLS single core multistranded copper wire cableand including panel painting The manufacturer of panel shall submit a copy of ASTA CPRI TEST REPORT IN POLYCARBONATE only also share panel assembled by OEM only. TYPE TEST & ROUTINE TEST REPORT to be submitted. The ASTA CPRI report shall have mention of following tests performed and passed out satisfactorily - Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak & short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits. The panel shall pass glow wire test 960 degrees Centigrade in accordance with 60695-2-11 [flame retardant and self-extinguishing] with and including pedestal/ frame grouted in PCC (1:2:4) type B-1 20mm graded stone aggregated, thimble and cable entry boxes with cable glands comprising of following accessories complete all as specified and directed by Engineer-in-charge :- INCOMER: (i) MCCB 160 Amp, 4 pole MCCB, 25 KA 415V Fixed Thermal & Magnetic Released - 01 No. (ii) Onload Manual Change over Switch 160A 4Pole - 01 No. (iii) Set of LED RYB type indicating lamps - Set of three (iv) Copper Bus Bar 300Amp TPN OUTGOINGS: (i) MCB FP 63/100 Amp 10KA 415 V, C-Curve - 04 Nos. (ii) MCB 63/100 Amp DP 10KA 230V C-Curve - 06 Nos. (iii) MCB 10-32 Amp DP 10KA 230V C-Curve - 06 Nos.
Material and Labour in replacement of for earthing with galvanized steel plate electrode 600mm x 600 mm x 6 mm size directly burried in ground vertically to earth pit not less than 2.25 meter deep below normal ground level with top edge of the earth plate not less than 1.5 m below normal ground level surrounded with coal dust and common salt filling in alternative layers of 15 cm thick each connected to and including GI earth wire 4 mm dia by means of nuts, bolts, check nuts & washers etc connecting to earthing test point, main switch board and including 15 mm dia GI pipe light grade for protection of earth lead from earth plate to distribution board and 20 mm dia GI pipe medium grade connected with funnel having wire mesh for watering purpose including necessary excavation and earth work, PCC (1:2:4) type B-1 (using 40mm graded stone aggregates) for earthing pit, 10mm thick cast iron cover with angle iron frame of size 40mm x 40mm x 6mm all as specified and shown in electrical plate No 3 of SSR Part-I and testing on completion complate all as specified Note:- PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner.
Material and Labour for Earthing with galvanized steel plate electrode 600mm x 600 mm x 6 mm size directly burried in ground vertically to earth pit not less than 2.25 meter deep below normal ground level with top edge of the earth plate not less than 1.5 m below normal ground level surrounded with coal dust and common salt filling in alternative layers of 15 cm thick each connected to and including GI earth strip 25mm x 4 mm length upto 7.5m by means of nuts, bolts, check nuts & washers etc connecting to earthing test point, main switch board and including 40 mm dia GI pipe light grade for protection of earth lead from earth plate to distribution board/LT Panel and 20 mm dia GI pipe medium grade connected with funnel having wire mesh for watering purpose including necessary excavation and earth work, PCC (1:2:4) type B-1 (using stone aggregates) for earthing pit, 10mm thick cast iron cover with angle iron frame all as specified and shown in electrical plate No 3 of SSR Part-I and testing on completion complete all as specified Note:- PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner.
Supply and Fixing galvanised iron strip 25mm x 4mm buried in ground / fixed to wall & floor for ground conductor all as directed.complete all as specified and as directed by Engineer-in-charge.
Supply and fixing in replacement (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 4 Way 240V, suitable for mounting MCB/Isolator etc, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCB/Isolator etc shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing in replacement (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 8 Way 240V, suitable for mounting MCB/Isolator etc, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCB/Isolator etc shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing in replacement (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 12 Way 240V, suitable for mounting MCB/Isolator etc, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCB/Isolator etc shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing in replacement (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 250 Amp rated bus bar) VTPN, 4 Way 415V, suitable for mounting MCCB/MCB, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCCB/MCB shall be measured and paid separately under appropriate item of BOQ.
Supply and Fixing in replacement sheet metal enclosure with two pin & earth plug and socket (industrial type DB) with and including one MCB SPN ,B curve type capacity 25 Amps ,10 KA complete all as specified and as directed by Engineer-in-charge..
Supply and fixing MCB ‘C’ curve suitable for 240 volts AC supply, 06 to 32 Amps, SP with over load and short circuit protection and rupturing capacity not less than 10 KA, complete all as specified and as directed by Engineer-in-charge complete all as specified and as directed by Engineer-in-charge.
Supply and fixing MCB ‘C’ curve suitable for 240 volts AC supply, 20 to 32 Amps, SPN with over load and short circuit protection and rupturing capacity not less than 10 KA, complete all as specified and as directed by Engineer-in-charge complete all as specified and as directed by Engineer-in-charge.
Supply and fixing MCB ‘C’ curve suitable for 240 volts AC supply, 40 to 63 Amps, SPN with over load and short circuit protection and rupturing capacity not less than 10 KA, complete all as specified and as directed by Engineer-in-charge complete all as specified and as directed by Engineer-in-charge.
Supply and fixing MCCB of capacity 125 Amp, 4 Pole, 415 volt, short circuit breaking capacity 16KA , fixed thermal magnetic trip, setting 80-100%, Icu-100% Ics confirming to IEC-947, IS-13947, including thimbles, nuts, bolts, washers etc, including making incoming, outgoing connections complete all as specified and as directed by Engineer-in-charge .
Supply and Fixing Rigid non-metallic PVC conduit of external dia 25mm including junction boxs, tees, bends,elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. complete all as specified and directed by Engr-in- Charge.
Supply and Fixing Rigid non-metallic PVC conduit of external dia 32 mm including junction boxs, tees, bends,elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. complete all as specified and directed by Engr-in- Charge.
Supply and Fixing Rigid non-metallic PVC conduit of external dia 40 mm including junction boxs, tees, bends,elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. complete all as specified and directed by Engr-in- Charge.
Taking down Ceiling fan & Exhaust fan, sealing cable end , dismantling blades and removing and deposting the same in E/M store yard of K.V. No.1 Bathinda and refixing the same on existing location complete all as specified and directed by Engr-in- Charge.
Hanging only ceiling fan and connecting up with and including suitable size of copper cable from ceiling rose or connector to ceiling fan retrived from serial item no. 66 here -in before complete all as specified and directed by Engr-in- Charge.
Fixing only Exhaust fan and connecting up including suitable size of copper cable from ceiling rose or connector to Exhaust fan retrived from serial item no. 66 here -in before complete all as specified and directed by Engr-in- Charge.
Supply and Fixing Heavy duty wall mounted fan, AC, 400mm, 230 volt, minimum 1350RPM speed, complete with fan motor, set of blades, mounting accessories kit, Base Stand, Guard set, Guard ring, Guarantee Card , Instruction manual, Pull cord control for speed and oscillation, Minimum air Delivery: 70 CMM, Elegantly designed fan base, ribs guard. oscillation degree 60˚,Pull cord control for speed and oscillation on-off, balanced blades, Thermal overload protector (TOP) helps in protecting the motor in case of any high voltage fluctuation, Max noise level: 65 dB, max power consumption: 50 W, 50 Hz complet all as per manufacturer's instructions and complete all as specified and directed by Engr-in- Charge.
Supply and Fixing Heavy duty Exhaust fan steel body AC, 300mm sweep ,230 volt, BEE, 5 star rated minimum 1500RPM, copper winding, complete with louvers and shutter and mounted in suitable opening arrangement in wall/window and connecting up including 3 core PVC insulated PVC sheathed copper conductor flexible cable(manufacturer provided) from ceiling rose to fan complete including grouting with bolts, nuts etc complete all as specified and directed by Engr-in- Charge.
Material and Labour for Cutting holes, exceeding 150sq.cm but not exceeding 400 sq cm area, not exceeding 30 cm depth in brick walls built in cement mortar and making good in cement mortar 1:3 or cement concrete 1:2:4 type B-1 using 20mm graded stone aggregates as required, and making good the distubed surfaces of wall, matching the surfaces with existing colour with white washing / colour wahing / colour painting complete all as specified and directed by Engr-in- Charge.
Supply and Fixing Lamp holder PVC/polycarbonate type with back plate suitable for batten fitting with LED bulb 5W complete all as specified and as directed by Engineer-in-charge.
Supply and laying or fixing and testing wiring with FRLSH PVC insulated and unsheathed multi-stranded copper conductor, single core, cable of size 2.5 sqmm, connected to existing terminal/socket point/ MCBs etc for invertor/School bell complete all specfied and directed
Supply and Fixing Gong Bell 12 inches ISI marked for loud long range sound, power capacity not more than 15W complete all as specified and as directed by Engineer-in-Charge.
Supply and Fixing Electronic timer designed to control ringer / sirens in Schools/Colleges/Offices having separate programming for Weekdays and Weekends for all 3 different modes, 25 Bells per day, can be programmed as needed including making connections and programming complete all as specified and as directed by Engineer-in charge.
Supply and Fixing electronic energy meter, single phase, temper proof LCD display with PC cover, 230V, 10-60 Amp, accuracy Class-I, conforming to IS 16444 compatible with existing infrasturcture , IP 54, 6-digit bright back lit display counter records most accurate error free forward energy recording irrespective of current direction. High surge resistant, hackproof, low power consumption, high insulation resistance & dielectric strength, anti-temper features (phase-neutral or main & load wire interchanged, neutral missing, DC immunity, abnormal voltage, earth load tamper indication etc.) with performance parameters to show data, time, current reading, load, volatge, kWH etc. complete all as specified and as directed by Engineer-in charge.
Dismantling safely Interlocking tiles already laid on ground surfaces up to 0.70 mtr wide and deposit in store yard of KV No.1 Bathinda and Taking out old unservicable under ground LT XLPE of any size from trenches / wall / roof / road / pipe / pole / DB including taking out of bricks / un-reinforced precast concrete cable cover layer for cable protection and Re- laying the interlocking tiles carefully after recollecting from KV No.1 Bathinda as per existing pattern on ground surfaces as directed by Engineer-in-charge . Note:(i)The rate of dismantled Interlocking tiles up to 0.70mtr and deposting in stored of KV No.1 Bathinda and recollect the same from store of KV School Bathinda for Re- laying carefully as per existing pattern on ground surfaces as directed by Engineer -in-charge is included in this item and nothing shall be paid extrta on this account. Old unservicable cable and bricks/ bats /un-reinforced precast concrete cable cover shall be considered in schedule of credit under respective items of Schedule of credit.(ii) Excavation and earth work shall be measured and paid seperately under respective items of Schedule'A' BoQ..
Note:- (i) The contract sum shall be calculated by deducting the amount shown in Credit Schedule attached to this tender from total amount of Schedule 'A'/BOQ.
M/s NIRMAN BUILDERS
M/s VISHAL ELECTRIC STORE
M/S MANI GARG CONTRACTOR
Aman Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .