Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.2 CrAdmitted-Finance CHENNAI | CHENNAI | TAMIL NADU | 600001 | ₹1.2 Cr | L1 | Admitted-Finance |
| 2 | L2₹1.3 Cr+₹12.5 L (10.3%)Admitted-Finance | ₹1.3 Cr+₹12.5 L (10.3%) | L2 | Admitted-Finance |
| 3 | Not Admitted-Finance PLOT NO 13 SHAKTI KHAND II INDRAPURAM GHAZIABAD 201014 | GHAZIABAD | UTTAR PRADESH | 201014 | - | - | Not Admitted-Finance Others-During Technical evaluation erroneously uploaded as accepted instead of rejected, since submitted all documents with rubber stamp signature, hence legally not valid. |
| 4 | Rejected-Technical 39A FIRST MAIN ROAD BARATHI NAGAR AMBATTUR CHENNAI TAMIL NADU 600053 | THIRUVALLUR | TAMIL NADU | 600053 | - | - | Rejected-Technical Price quoted in Techno commercial bid |
| 5 | Rejected-Technical | - | - | Rejected-Technical Price quoted in Techno commercial bid |
| Sl No | Description | Qty | Unit | V.K.sam Engineering L1 | JYOTI ELECTRO SYSTEMS PVT LTD L2 |
|---|---|---|---|---|---|
| 1.00 | Design and Supply of 11 KV / 433V, 500 KVA, Package Outdoor Sub-Station (CSS) comprising of: HV Compartment comprising of 11 KV, 630A, 500 KVA, 21 KA, 3 Phase 50 HZ, SF6 encapsulated Vacuum circuit breaker 1 No. as outgoing and Isolator 2 Nos as incomer with standard accessories, Transformer compartment:
11 KV/433V, 500 KVA, DYnII, Cast Resin Dry Type Transformer with standard accessories. LV compartment comprising
1 No 415V, 1000A, 4 pole, 50 KA, ACB and
1 No. APFC unit with standard accessories
as per Technical specification of Schedule ‘A’. | 1 | Set | 40,95,645 ₹40,95,645 Lowest | 45,76,272 ₹45,76,272 |
| 2.00 | Installation, testing and commissioning of 11 KV / 433V, 500 KVA, Package Outdoor Sub-Station (CSS) with standard accessories as per Technical specification of Schedule ‘A’. | 1 | Set | 50,000 ₹50,000 Lowest | 84,746 ₹84,746 |
| 3.00 | Supply of 11 KV, 630A, 25KA, 3 Phase 50 HZ Vacuum circuit breaker with dry type P.T, C.T. ratio - 300/1/1 of Incomer Feeder and all other accessories as per Technical specification schedule ‘A’ | 1 | No. | 5,77,650 ₹5,77,650 | 4,02,543 ₹4,02,543 Lowest |
| 4.00 | Installation of 11 KV, 630A, 25KA, 3 Phase 50 HZ Vacuum circuit breaker of Incomer Feeder as per Technical specification schedule ‘A’. | 1 | No. | 7,500 ₹7,500 Lowest | 16,950 ₹16,950 |
| 5.00 | Supply of 11 KV, 630A, 25KA, 3 Phase 50 HZ Vacuum circuit breaker with C.T. ratio - 150/1/1 of Outgoing Feeder and all other accessories as per Technical specification schedule ‘A’ | 3 | No. | 17,32,950 ₹17,32,950 | 12,07,629 ₹12,07,629 Lowest |
| 6.00 | Installation of 11 KV, 630A, 25KA, 3 Phase 50 HZ Vacuum circuit breaker of Outgoing Feeder as per Technical specification schedule ‘A’. | 3 | No. | 9,000 ₹9,000 Lowest | 50,850 ₹50,850 |
| 7.00 | Design and Supply of floor mounted L.T. distribution panel shall be comprising of ACB for Incoming feeder: 1 No. - 1000 A, 4P, 50 KA & MCCB for Outgoing feeders 3 Nos.- 400 A, 4P, 50 KA, 3 Nos.- 250 A, 4P, 50 KA, 2 Nos.- 100 A, 4P, 25 KA as per Technical specification schedule ‘A’. | 1 | Set | 8,55,000 ₹8,55,000 | 8,05,085 ₹8,05,085 Lowest |
| 8.00 | Installation of floor mounted L.T. distribution panel shall be comprising of ACB as per Technical specification schedule ‘A’. | 1 | Set. | 15,000 ₹15,000 Lowest | 42,373 ₹42,373 |
| 9.00 | Supply of H.T. 11KV, 3 C X185 Sq.mm. XLPE U.G. Alu. cable as per Technical specification of schedule ‘A’. | 1,650 | Mtr. | 17,82,000 ₹17,82,000 Lowest | 22,37,400 ₹22,37,400 |
| 10.00 | Laying of H.T. 11KV, 3 C X185 Sq.mm. XLPE U.G. Alu. cable Through cable Trench as per Technical specification of schedule ‘A’. | 1,400 | Mtr. | 1,26,000 ₹1,26,000 Lowest | 3,55,600 ₹3,55,600 |
Tender Value
₹1.5 Cr
EMD Value
₹3.0 L
Closing Date
27 Feb 2024, 2:30 pmClosed
Chief Mechanical Engineer
7th Floor, Centenary Building. No.1 Rajaji Salai
e TENDER FOR DESIGN, SUPPLY, INSTALLATION, TESTING AND COMISSIONING OF 500 KVA PACKAGE OUTDOOR SUB-STATION (CSS) NEAR GATE NO.2 IN CHENNAI PORT AUTHORITY UNDER TWO COVER SYSTEM
2024_ChPT_788940_1
MEE / 69 / 2023 / Dy.CME(ES)
Open Tender
Electrical Works
Works
150 days
Chennai Port Authority
As per Tender
5 documents required · 5 mandatory
₹0
₹3.0 L
Yes
Dy.CME s Chamber
23 Jul 2024
5 Jan 2024
28 Feb 2024
5 Jan 2024
27 Feb 2024
15 Jan 2024
5 Jan 2024 - 30 Jan 2024
12 Jan 2024
Design and Supply of 11 KV / 433V, 500 KVA, Package Outdoor Sub-Station (CSS) comprising of: HV Compartment comprising of 11 KV, 630A, 500 KVA, 21 KA, 3 Phase 50 HZ, SF6 encapsulated Vacuum circuit breaker 1 No. as outgoing and Isolator 2 Nos as incomer with standard accessories, Transformer compartment: 11 KV/433V, 500 KVA, DYnII, Cast Resin Dry Type Transformer with standard accessories. LV compartment comprising 1 No 415V, 1000A, 4 pole, 50 KA, ACB and 1 No. APFC unit with standard accessories as per Technical specification of Schedule ‘A’.
Installation, testing and commissioning of 11 KV / 433V, 500 KVA, Package Outdoor Sub-Station (CSS) with standard accessories as per Technical specification of Schedule ‘A’.
Supply of 11 KV, 630A, 25KA, 3 Phase 50 HZ Vacuum circuit breaker with dry type P.T, C.T. ratio - 300/1/1 of Incomer Feeder and all other accessories as per Technical specification schedule ‘A’
Installation of 11 KV, 630A, 25KA, 3 Phase 50 HZ Vacuum circuit breaker of Incomer Feeder as per Technical specification schedule ‘A’.
Supply of 11 KV, 630A, 25KA, 3 Phase 50 HZ Vacuum circuit breaker with C.T. ratio - 150/1/1 of Outgoing Feeder and all other accessories as per Technical specification schedule ‘A’
Installation of 11 KV, 630A, 25KA, 3 Phase 50 HZ Vacuum circuit breaker of Outgoing Feeder as per Technical specification schedule ‘A’.
Design and Supply of floor mounted L.T. distribution panel shall be comprising of ACB for Incoming feeder: 1 No. - 1000 A, 4P, 50 KA & MCCB for Outgoing feeders 3 Nos.- 400 A, 4P, 50 KA, 3 Nos.- 250 A, 4P, 50 KA, 2 Nos.- 100 A, 4P, 25 KA as per Technical specification schedule ‘A’.
Installation of floor mounted L.T. distribution panel shall be comprising of ACB as per Technical specification schedule ‘A’.
Supply of H.T. 11KV, 3 C X185 Sq.mm. XLPE U.G. Alu. cable as per Technical specification of schedule ‘A’.
Laying of H.T. 11KV, 3 C X185 Sq.mm. XLPE U.G. Alu. cable Through cable Trench as per Technical specification of schedule ‘A’.
Laying of H.T. 11KV, 3 C X185 Sq.mm. XLPE U.G. Alu. cable Through Earth with RCC Troughs as per Technical specification of schedule ‘A’.
Laying of H.T. 11KV, 3 C X185 Sq.mm. XLPE U.G. Alu. cable Through cement concrete / Tar Road / Railway line with G.I. pipes as per Technical specification of schedule ‘A’.
Supply of Heat Shrinkable Straight through joint kit for H.T. 11KV, 3C X X185 sq.mm XLPE UG Aluminum Cable as per Technical specification of schedule ‘A’.
Installation of above straight through joint including all other accessories as per Technical specification of schedule ‘A’
Supply of Indoor type heat shrinkable End termination kit for H.T. 11KV, 3X185 Sq mm XLPE UG Aluminum Cables. as per Technical specification of schedule ‘A’.
Installation of Indoor type heat shrinkable End termination kit for H.T. 11KV, 3X185 Sq mm XLPE UG Aluminum Cables. as per Technical specification of schedule ‘A’.
Supply of 3 ½ core 185 Sq.mm. LT Aluminum XLPE cable from proposed Compact substation to feeder pillar as per Technical specification of schedule ‘A’
Laying of 3 ½ core 185 Sq.mm. LT Aluminum XLPE cable from proposed Compact substation to feeder pillar and end terminations of the cable Through cable Trench Make it separate both ends as per Technical specification of schedule ‘A’.
Laying of 3 ½ core 185 Sq.mm. LT Aluminum XLPE cable from proposed Compact substation to feeder pillar and end terminations of the cable Through Earth with RCC Troughs as per Technical specification of schedule ‘A’.
Laying of 3 ½ core 185 Sq.mm. LT Aluminum XLPE cable from proposed Compact substation to feeder pillar and end terminations of the cable Through cement concrete / Tar Road / Railway line with G.I. as per Technical specification of schedule ‘A’.
Supply of Heat Shrinkable Straight through joint kit for L.T. 1.1KV, 3 1/2 X 185 sq.mm XLPE UG Aluminum Cable as per Technical specification of schedule ‘A’.
Installation of Heat Shrinkable Straight through joint kit for L.T. 1.1KV, 3 1/2 X 185 sq.mm XLPE UG Aluminum Cable as per Technical specification of schedule ‘A’.
Supply of Battery and Battery charger unit including 2 Nos.12V, 185 Ah. Maintenance free Battery as per Technical specification of schedule ‘A’.
Installation of Battery and Battery charger unit including 2 Nos.12V, 185 Ah. Maintenance free Battery as per Technical specification of schedule ‘A’.
Supply of G.I. plate earthing electrode size is not less than 60 Cm. X 60 Cm. X 10 mm. in accordance with BIS 3043 / BS 7430 or latest for neutral earth as per Technical specification of schedule ‘A’.
Installation of G.I. plate earthing electrode size is not less than 60 Cm. X 60 Cm. X 10 mm. in accordance with BIS 3043 / BS 7430 or latest for neutral earth as per Technical specification of schedule ‘A’
Supply of providing of maintenance free earth in accordance with BIS 3043 / BS 7430 or latest for CSS body earth and L.T. panel as per Technical specification of schedule ‘A’.
Installation of providing of maintenance free earth in accordance with BIS 3043 / BS 7430 or latest for CSS body earth and L.T. panel as per Technical specification of schedule ‘A’
Supply of 40 mm x 6 mm G.I. flat for 500 KVA, CSS body earth and L.T. panel as per Technical specification of schedule ‘A’.
Laying of 40 mm x 6 mm G.I. flat for 500 KVA, CSS body earth and L.T. panel as per Technical specification of schedule ‘A’.
Supply of 25 mm x 3 mm copper flat for 500 KVA, CSS neutral earth as per Technical specification of schedule ‘A’.
Laying of 25 mm x 3 mm copper flat for 500 KVA, CSS neutral earth as per Technical specification of schedule ‘A’.
Supply and installation of 11 KV grade rubber hand gloves as per IER as per Technical specification of schedule ‘A’.
Supply and installation of First aid box as per IER as per Technical specification of schedule ‘A’.
Supply and installation of First aid and Shock treatment chart and safety rules with suspension clamp and front clear plastic sheet lamination as per Technical specification of schedule ‘A’.
Supply and installation of Fire extinguisher- 1 No. and Fire bucket 4 Nos. with pedestal stand as per IER as per Technical specification of schedule ‘A’.
Supply and installation of Flexible rubber mat 1M width X 2.5 mm thick, 11 KV as per IER as per Technical specification of schedule ‘A’.
Testing and commissioning entire system and produce test report.
JYOTI ELECTRO SYSTEMS PVT LTD
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.03 MB
BOQ_829263.xls
BOQ • 0.29 MB
69TENDER2023.pdf
Tender Documents • 0.77 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .