| Sl No | Description | Qty | Unit | M/s Bhat Engineering Works L4 | Global Engineers L1 | FAVOURITE ELECTRICALS L5 | Yatha Consultants and Engineers L2 | M/S STAR NEOTECH ENGINEERS L3 | M/S HI TECH ENGINEERING SERVICES L6 |
|---|---|---|---|---|---|---|---|---|---|
| 0.00HVAC INSULATED HOT / CHILLED WATER PIPING (insulation type-I) Supplying, laying/ fixing, testing and commissioning of following nominal sizes of Hot / chilled water piping plumbing inside the building etc. Rest of specification as per technical annexure annexed of item No. 11. Note : The Pipes of sizes 150mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. | |||||||||
| 1.00 | 150mm dia. (50mm insulation) | 30 | RMT | 2,600 ₹78,000 Lowest | 2,670 ₹80,100 | 3,392 ₹1,01,760 | 2,916 ₹87,480 | 2,850 ₹85,500 | 3,800 ₹1,14,000 |
| 1.10 | 100mm dia. (50mm insulation) | 25 | RMT | 1,850 ₹46,250 Lowest | 2,040 ₹51,000 | 2,406 ₹60,150 | 2,268 ₹56,700 | 2,150 ₹53,750 | 2,800 ₹70,000 |
| 1.20 | 80mm dia. (50mm insulation) | 100 | RMT | 1,400 ₹1,40,000 Lowest | 2,030 ₹2,03,000 | 1,819 ₹1,81,900 | 2,075 ₹2,07,500 | 1,700 ₹1,70,000 | 2,100 ₹2,10,000 |
| 1.30 | 65mm dia. (50mm insulation) | 80 | RMT | 1,300 ₹1,04,000 Lowest | 1,600 ₹1,28,000 | 1,587 ₹1,26,960 | 2,020 ₹1,61,600 | 1,400 ₹1,12,000 | 2,000 ₹1,60,000 |
| 1.40 | 50mm dia. (50mm insulation) | 50 | RMT | 875 ₹43,750 Lowest | 1,370 ₹68,500 | 1,318 ₹65,900 | 1,336 ₹66,800 | 900 ₹45,000 | 1,800 ₹90,000 |
| 1.50 | 40mm dia. (25mm insulation) | 60 | RMT | 670 ₹40,200 Lowest | 897 ₹53,820 | 780 ₹46,800 | 1,245 ₹74,700 | 700 ₹42,000 | 1,200 ₹72,000 |
| 1.60 | 32mm dia. (25mm insulation) | 30 | RMT | 570 ₹17,100 Lowest | 860 ₹25,800 | 668 ₹20,040 | 1,215 ₹36,450 | 630 ₹18,900 | 1,100 ₹33,000 |
| 1.70 | 25mm dia. (25mm insulation) | 70 | RMT | 490 ₹34,300 Lowest | 666 ₹46,620 | 563 ₹39,410 | 1,100 ₹77,000 | 500 ₹35,000 | 750 ₹52,500 |
| 1.80 | 20mm dia. (25mm insulation) | 50 | RMT | 370 ₹18,500 Lowest | 560 ₹28,000 | 448 ₹22,400 | 1,053 ₹52,650 | 400 ₹20,000 | 590 ₹29,500 |
Tender Value
Refer Docs
EMD Value
₹1.7 L
Closing Date
24 Nov 2020, 4:00 pmClosed
Executive Engineer Mechanical SKIMS
Office of Executive Engineer Mechanical SKIMS
Supply installation testing and commissioning of Independent Heat Pump based HVAC system to newly constructed Engineering Block at SKIMS Soura.
2020_SKIMS_108462_1
NIT NO. 52 OF 2020-21 Dated. 02.11.2020
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
90 days
SKIMS Soura
as per nit
7 documents required · 7 mandatory
₹4,500
Director Finance SKIMS Soura
₹1.7 L
Yes
Office of Executive Engineer Mechanical SKIMS
27 Apr 2021
5 Nov 2020
26 Nov 2020
5 Nov 2020
24 Nov 2020
5 Nov 2020
5 Nov 2020 - 11 Nov 2020
11 Nov 2020
Amount
HVAC INSULATED HOT / CHILLED WATER PIPING (insulation type-I) Supplying, laying/ fixing, testing and commissioning of following nominal sizes of Hot / chilled water piping plumbing inside the building etc. Rest of specification as per technical annexure annexed of item No. 11. Note : The Pipes of sizes 150mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
150mm dia. (50mm insulation)
100mm dia. (50mm insulation)
80mm dia. (50mm insulation)
65mm dia. (50mm insulation)
50mm dia. (50mm insulation)
40mm dia. (25mm insulation)
32mm dia. (25mm insulation)
25mm dia. (25mm insulation)
20mm dia. (25mm insulation)
15mm dia. (25mm insulation)
INUSLATED VALVE Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. Rest of specification as per technical annexure annexed of item No. 11. BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot water circulation as specified.
150mm dia.
100mm dia.
80mm dia.
65mm dia.
50mm dia.
40mm dia.
BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified. Rest of specification as per technical annexure annexed of item No. 11.
80mm dia.
65mm dia.
50mm dia.
NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including insulation as specified.Rest of specification as per technical annexure annexed of item No. 11.
80mm dia.
Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified.Rest of specification as per technical annexure annexed of item No. 11.
80mm dia.
50mm dia.
Providing and fixing in position the industrial type pressure gauge complete as required. Rest of specification as per technical annexure annexed of item No. 11.
Providing & fixing in position the mercury in glass industrial type thermometer complete as required. Rest of specification as per technical annexure annexed of item No. 11.
AIR DISTRIBUTION DUCT (FOR VENTILATION) Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/ round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. Rest of specification as per technical annexure annexed of item No. 8.
0.63 MM (24 gauge) Galvanized Sheet Steel Ducting
0.80 MM (22 gauge) Galvanized Sheet Steel Ducting
Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, Rest of specification as per technical annexure annexed of item No. 8.
Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core. Rest of specification as per technical annexure annexed of item No. 8.
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required. Rest of specification as per technical annexure annexed of item No. 8.
FIRE DAMPERS Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required etc. Rest of specification as per technical annexure annexed of item No. 8.
Fire damper
Actuator
Supplying, fixing acoustic lining of supply air duct and plenum with 25 mm thick resin bonded glass wool having density of 32 Kg/M3, with 25 mm x 25 mm GI section of 1.25 mm thick at 600mm centre to centre covering with reinforced plastic tissue paper and 0.5 mm thick perforated aluminum sheet fixed to inside surface of ducts with cadmium plated nuts, bolts, stick pins, CPRX compound complete. Rest of specification as per technical annexure annexed of item No. 8 &9.
AIR COOLED REVERSIBLE TYPE HEAT PUMP Supply, installation, testing and commissioning of Screw / Scroll type Heat Pump unit of 100 KW actual capacity at the parameters indicated below. complete with Screw / scroll compressor, etc. Rest of specification as per technical annexure annexed of item No. 2. Heat Pump shall be complete as per specifications and shall have operating parameters as given below: Parameters for the heat pumps are as under:- Hot water in : 112º F Hot water out : 122º F Hot water flow rate: 100 USGPM Note:- The job also includes lifting of heat pump units up to the terrace level of fourth floor, positioning of heat pumps at appropriate location and bringing of truss work into its original décor after any temporary change requisite to accommodate the positioning of heat pumps.
PUMPS Supply, installation, testing and commissioning of End Suction Back pull out centrifugal pumps complete with motor, base frame, vibration isolators, drain valves and other accessories etc.Rest of specification as per technical annexure annexed of item No. 3. Pumps shall be complete as per specifications and shall have operating parameters as given below: Chilled/Hot water pumps with VFD Water flow rate : 100 USGPM Head : 100ft Motor HP : 7.5 HP
AIR HANDLING UNITS Supply, installation, testing and commissioning of double skin modular construction, draw through Ceiling Suspended (CS) Air Handling Units etc. Rest of specification as per technical annexure annexed of item No. 5.
Basement area, 8000CFM (CS) AHU, 70.0 KW heating capacity, 4 row deep heating coil, 40 mm Static Pressure with 7.5 HP/ 3 Phase motor.
FAN COILS UNITS (HI-WALL MOUNTED TYPE) Supply, Installation, testing &Commissioning of hi-wall mounted fan coil unit of specified heating capacity and air flow as per the specification complete with drain pan, 3 speed motor, thermostat temperature control system, cordless remote, washable pre-filter, electrical terminal box & high temperature resistance flexible piping of required length at site on the supply & return side of FCU. The unit shall be complete with all allied accessories. Rest of specification as per technical annexure annexed of item No. 6.
400 CFM (1.0 TR)
600 CFM (1.5 TR)
FAN COIL UNIT CONTROLS Supply, installation, testing and commissioning of controls for fan coil units consisting of 3-way motorized spring return valves, wiring etc. Rest of specification as per technical annexure annexed of item No. 7.
Water Flow Rate 2.4 USGPM
Water Flow Rate 3.6 USGPM
EXPANSION TANK Supplying, installing, testing and commissioning of pressurized cold water expansion tank with air separator with S.S braided pipe flexible connector suitable for total volume of water in cold water circuits along with necessary accessories such as centrifugal air separator, pumps etc. in order to keep cold water system under (+) pressure and to prevent entrapment of pressure and to prevent entrapment of air in the system. The tank shall be precharged steel expansion tank with replaceable heavy duty butyl rubber bladder. The tank shall have 50 MM system connection and 20 mm drain and charging valve connection to facilitate the on site charging of the tank to meet system requirement. The tank shall be fitted with lifting rings and a floor mounting skirt for vertical installation. The tank and air separator must be constructed in accordance with section VIII of the ASME Boiler and pressure vessel (Unfired) code and stamped 125 PSI working pressure. The complete system shall be sourced from single manufacturer and supplied and installed with all accessories and safety fixtures and safety fixtures required for proper functioning of the complete hydronic system.
The capacity of each tank shall be 500 Liters approx (for chilled water system). Contractor need to quote as per actual requirement with calculation backup duly approved from EIC.
Water Softener Plant:- Supply, installation, testing and commissioning of softener plant having metallic body and having a maximum capacity of delivering 2000 liters/hr. and pressure range between 1.5 to 5 Kg/cm² etc. Rest of specification as per technical annexure annexed of item No. 4.
VFD for Air Handling units Supply, installation, testing & commissioning of VFDs. VFD designed for HVAC applications with built-in PID controller, control panel (keypad & display) , IP-65 enclosure (for outdoor applications) & IP-55 enclosure (for indoor applications) for use on fans. The display should be in alpha- numeric characters and programming facility should be in user- friendly HVAC terminology. VFD’s shall have built-in harmonic filters with THDI less than 5%. Each VFD panel to be provided with digital display showing electrical parameters like voltage, current and power consumption. Each VFD shall be installed in a dedicated external enclosure and the inter connecting wires between driver and MCC shall be included. Necessary transformer, power adapters, sensors, relay etc as required for satisfactory operation shall be in the scope of VFD supplier. It should be BMS Compatible.
Providing and fixing in position the following Ball Valves with Strainer duly insulated as per specifications and drawings.
15mm dia.
Providing and fixing in position the following Ball Valves without strainer duly insulated as per specifications and drawings.
15mm dia.
Providing and fixing in position the following Flexible coupling (with control rods) for the Hot water pumps.
80mm dia.
Supply, installation, testing and commissioning of cooling thermostats for Air Handling Units as per specifications including all accessories , mountings, wiring between thermostat & unit, terminations etc. Rest of specification as per technical annexure annexed of item No. 7.
Proportional thermostats for Air Handling Units
80mm dia.
Providing and fixing in position the following water flow switch as per specifications: Rest of specification as per technical annexure annexed of item No. 7.
Providing and fixing in position Auto air vents of following size etc. Rest of specification as per technical annexure annexed of item No. 11.
20 mm dia.
Providing and fixing in position the following Drain Valves (For Drain) duly insulated as per specifications and drawings
25mm dia.
15mm dia.
DRIAN PIPE:- Providing and fixing in position the following GI medium class cut to required length and installed with screw joints including the necessary fittings (bends, tees, unions, sockets etc) duly insulated with 25 mm thick TF quality thermocole pipe section as per specifications.
25mm dia.
15mm dia.
INSULATION Supply, Installation, Testing & Commissioning of external thermal insulation with closed cell cross-linked polythelene foam with self adhesive and density for insulation of ducts as per specifications & drawings. Rest of specification as per technical annexure annexed of item No. 12.
19 mm thick for conditioned space
Supply, installation and balancing of extruded aluminium powder coated air louvers complete with aluminium wire mesh birdscreen & volume conrtol dampers as per specifications. Rest of specification as per technical annexure annexed of item No. 8.
Fresh air louvers
Providing, fixing Termination of PVC insulated armored sheathed XLPE aluminum conductor cables from main panel boards to heat pump equipments through walls/ceiling with appropriate clamps and fixing arrangements etc. Rest of specification as per technical annexure annexed of item No. 21.
Providing and fixing of electric power cabling from main control panel to all electric mechanical components suitable for 420v, 3 phase, 50 Hz and from main control panel to individual indoor fan coil units for single phase supply. The control wiring shall be PVC insulated and PVC sheathed, multicore, stranded copper cable with required no. of cores. Rest of specification as per technical annexure annexed of item No. 21.
G.I. earthing continuity conductors between panel boards and equipments as required and as per I.E. Rules 1956. Rest of specification as per technical annexure annexed of item No. 21.
G.I. Stripe 25x5mm
Main Earth Ring (Chemical Earthing)
Fabricating and Installation of following size of Hot Dip Galvanized Perforated cable Trays including horizontal & vertical bends, reducers, tees, cross members, and other accessories as required and duly suspended from the ceiling with MS suspenders. Rest of specification as per technical annexure annexed of item No. 21.
100 mm width x 40 mm depth x 1.6 mm thickness
150 mm width x 40 mm depth x 1.6 mm thickness
450 mm width x 50 mm depth x 2.0 mm thickness
Supply, installation, testing and commissioning of electrical control panel as per technical specifications s annexure "B" item No.20.
Providing and fixing of false ceiling of powder coated of aluminium composite panel of 4 mm thick sheets by way of suspending 25mm wide rectangular Al. /G.I. channel of appropriate thickness from the true ceiling to form grid of 2’ x 2’ size (False ceiling void of 3 feet or as per site requirement) followed by connecting of grid network by means of Al. /G.I. channels to act as a frame in which ACP sheets can be fitted & also should accommodate air diffusers, lighting fixtures as per the site requirement. The leveling of grid has to be accurate throughout including fixtures, hooks, fasteners & attachment rods with slab is also included in the job.
Yatha Consultants and Engineers
M/S STAR NEOTECH ENGINEERS
M/s Bhat Engineering Works
FAVOURITE ELECTRICALS
M/S HI TECH ENGINEERING SERVICES
stage.html
html • 0.03 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .