Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.7 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹26.9 L+₹24,260 (0.91%)Rejected-Finance | L2 | Rejected-Finance Being L2 | |
| 3 | L3₹30.6 L+₹4.0 L (14.9%)Rejected-Finance | L3 | Rejected-Finance Being L3 | |
| 4 | L4₹30.7 L+₹4.0 L (15.1%)Rejected-Finance | L4 | Rejected-Finance Being L4 | |
| 5 | L5₹31.3 L+₹4.6 L (17.2%)Rejected-Finance NO 26 GURU AMARDAS COLONY BHAINSA NAKA SAGAR MADHYA PRADESH 470001 | SAGAR | MADHYA PRADESH | 470001 | L5 | Rejected-Finance Being L5 |
Tender Value
₹36 L
EMD Value
₹72,000
Closing Date
31 Aug 2020, 6:00 pmClosed
Maj Punit Kumar GE
GE (I) (P) Fy Jabalpur PO-Khamaria PIN-482005
SPECIAL REPAIR AND REPLACEMENT OF DG SET PUMPING SET AND SUMMER APPLIANCES AGAINST BER ITEMS AT TECH AREA TAKU CPE ITARSI UNDER GE (I) (P) FY JABALPUR
2020_MES_364909_1
8330/ITA/E8
Open Tender
Civil Works
Item Rate
365 days
Itarsi
As per eNIT
7 documents required · 7 mandatory
₹500
Yes
GE (I) (P) Fy Jabalpur
₹72,000
Yes
22 Dec 2020
29 Jul 2020
5 Sept 2020
29 Jul 2020
31 Aug 2020
24 Aug 2020
Amount
Supply, installation, commisioning and testing of Diesel Engine driven generating set 62.5 KVA, 50 KW, 415 Volts, 3 phase 4 wire, engine complete with integral acoustic enclosures as per latest Indian Standards of central pollution control board and as alternator with relay panel for automatic starting on mains failure, control panel, sound proof canopy with AMF pannel and PCC foundation of required size for DG set as per manufacturer's instructions with GI tin shed for protection of panel and DG set from rain water complete including the following :-
A. ENGINE :-
(i) 4 cylinder, In-line 4 stroke, radiator cooled engine.
(II) Optimised turbocharger for increased altitude capabilities fuel economy with In line fuel pump with electric governer.
(iii) Stainless steel exhaust flexible coupling and exhaust pipe
(iv) Radiator
(v) Coolant inhabitor
(vi) Plate type lubricant oil cooler
(vii) Spin-on fileters coolant, fuel & lubricant oil.
(viii) Dry type heavy duty replaceable paper element air cleaner with restriction indicator.
(ix) Fly wheel housing and fly wheel suit single bearing alternator.
(x) Electrical starter motor
(xi) Battery charging alternator.
(xii) 12 volts 180AH ESE battery with multi standared copper cable for connecting wire and terminal complete
(xiii) First fill lub oil.
B. ALTERNATOR :-
(i) Self exited, self regulated.
(ii) Voltage regulation plus/minus/percent.
(iii) Class 'H' insulation
(iv) Silent pole revolving field.
(v) Digital automatic voltage regulator.
(vi) Noise level 75 dBA@ /meter
(vii) Telephone interference factor .50
(viii) Total harmonic factor better than 2%
(ix) Supplying power to variable electrical load for unlimited hours. Prime power (PRP) is in accordance with ISO 8523. 10% overload capacity for 1 hours every 12 hours of operation and will be suitable tropical conditions.
C. FUEL TANK :-
(i) Fuel tank suitable capacity for 12 Hrs on full load with provision for supply and return lines, level indicator, drain valve, cleaning cover, vent pipe & locking devices shall be provided.
(ii) Fuel pipe line from fuel tank to FIP of suitable size.
(iii) The fuel tank has to be mounted / located in side the cubicle.
D. ACOUSTIC ENCLOSURE :-
(i) Designed to meet stringent MoEF/CPCB-II norms 75 dBA @ 1 meter.
(ii) Air inlet louvers to be designed to operate at rated load even at 50 degree centigrade air inlet temp. Four point lifting for easy handling.
(iii) Cubical to be powder coated for long lasting service life and super finish with UV resistent powder coating, it has to with stand extreme environment. Has to be use stain steel hardware.
(iv) Insulation material conforming to IS 8183 speces for better sound.
(v) Genset control unit with integrated E-governor helps in reading all genset inputs and controls the genset GCU help in monitoring of following parameters, Controls the engine speed, supports auto mains failure (AMF) functions for 3 ph genset, low fuel level, support manual control (MCP) functions for 3 phase genset, Measres Genset, Measures Genset Voltages and currents, Measures electrical parameters like frequency, Power factor, Generato, KVA, KW, KVAr, Monitor critical engine safety parameters, Starts/Stops the genset, Have counters for genset start/stop, run hours, KWH, power factor
E. INBUILT AMF CONTROL PANEL FOR DG SET :-
(I) MCCB 63 Amps, 4 pole, 415 volts, 10 KA, 50 Hz - 02 Nos
(ii) Power contactors of suitable sizes, Air break type - 02 Nos
(iv) Current transformer (CT) of rating 100/5, tape wound, rated burden 5 VA - 03 Nos
(v) Micro processor based relay of suitable size/ratings-01 Nos
(vi) Battery charger auto/manual switch - 01 Nos
(vii) Suitable communication with features of following protections :- Over current, overvoltage, under voltage, under frequency, Low pressure oil.
(viii) Genset shall be fully automatic ie auto on when mains fail and auto off when mains on complete
F. MAINTENANCE AND OPERATIONAL MANUAL OF PLANTS - 01 SET SHALL BE SUBMITTED BY CONTRACTOR ALONGWITH THE FOLLOWING :-
(I) Test certificate of Alternator.
(ii) Test certificate of Diesel Engine.
(iii) Test certificate of Gen Set (by OEM).
(iv) Test certificate of Acoustic enclouser.
(v) Rubber mat.
Note : (a) Provision of PCC plateform as per manufacturer guidelines/specifications and shall be of required size. The cost of the same shall be deemed to be included in the unit quoted rates. Nothing shall be admissible on this account
(b) Testing of the DG set shall be carried out by the rep of the accepting office/IEM
(c ) The contractor shall submit the drawing for approval of the GE before procurement of the DG set
(d) Resistive load whether water load or strip heaters of suitable capacity and POL/DHPP for testing of DG set to be made available during test by the contractor. The cost of the same shall be deemed to be included in the unit quoted rates.
(e) The DG set shall be procured from authorized OEM and of same group. The accoustic panel shall also be manufactured by the same OEM
(f) Anyother details not mentioned above but is required for efficient functioning of DG set is deemed to be included in the unit quoted rate
Supply, installation, commisioning and testing of Diesel Engine driven generating set 30 KVA, 50 KW, 415 Volts, 3 phase 4 wire, engine complete with integral acoustic enclosures as per latest Indian Standards of central pollution control board and as alternator with relay panel for automatic starting on mains failure, control panel, sound proof canopy with AMF pannel and PCC foundation of required size for DG set as per manufacturer's instructions with GI tin shed for protection of panel and DG set from rain water complete including the following :-
A. ENGINE :-
(i) 3 cylinder, In-line 3 stroke, radiator cooled engine.
(II) Optimised turbocharger for increased altitude capabilities fuel economy with In line fuel pump with electric governer.
(iii) Stainless steel exhaust flexible coupling and exhaust pipe
(iv) Radiator
(v) Coolant inhabitor
(vi) Plate type lubricant oil cooler
(vii) Spin-on fileters coolant, fuel & lubricant oil.
(viii) Dry type heavy duty replaceable paper element air cleaner with restriction indicator.
(ix) Fly wheel housing and fly wheel suit single bearing alternator.
(x) Electrical starter motor
(xi) Battery charging alternator.
(xii) 12 volts 90AH ESE battery with multi standared copper cable for connecting wire and terminal complete
(xiii) First fill lub oil.
B. ALTERNATOR :-
(i) Self exited, self regulated.
(ii) Voltage regulation plus/minus/percent.
(iii) Class 'H' insulation
(iv) Silent pole revolving field.
(v) Digital automatic voltage regulator.
(vi) Noise level 75 dBA@ /meter
(vii) Telephone interference factor .50
(viii) Total harmonic factor better than 2%
(ix) Supplying power to variable electrical load for unlimited hours. Prime power (PRP) is in accordance with ISO 8523. 10% overload capacity for 1 hours every 12 hours of operation and will be suitable tropical conditions.
C. FUEL TANK :-
(i) Fuel tank suitable capacity for 12 Hrs on full load with provision for supply and return lines, level indicator, drain valve, cleaning cover, vent pipe & locking devices shall be provided.
(ii) Fuel pipe line from fuel tank to FIP of suitable size.
(iii) The fuel tank has to be mounted / located in side the cubicle.
D. ACOUSTIC ENCLOSURE :-
(i) Designed to meet stringent MoEF/CPCB-II norms 75 dBA @ 1 meter.
(ii) Air inlet louvers to be designed to operate at rated load even at 50 degree centigrade air inlet temp. Four point lifting for easy handling.
(iii) Cubical to be powder coated for long lasting service life and super finish with UV resistent powder coating, it has to with stand extreme environment. Has to be use stain steel hardware.
(iv) Insulation material conforming to IS 8183 speces for better sound.
(v) Genset control unit with integrated E-governor helps in reading all genset inputs and controls the genset GCU help in monitoring of following parameters, Controls the engine speed, supports auto mains failure (AMF) functions for 3 ph genset, low fuel level, support manual control (MCP) functions for 3 phase genset, Measres Genset, Measures Genset Voltages and currents, Measures electrical parameters like frequency, Power factor, Generato, KVA, KW, KVAr, Monitor critical engine safety parameters, Starts/Stops the genset, Have counters for genset start/stop, run hours, KWH, power factor
E. INBUILT AMF CONTROL PANEL FOR DG SET :-
(I) MCCB 63 Amps, 4 pole, 415 volts, 10 KA, 50 Hz - 02 Nos
(ii) Power contactors of suitable sizes, Air break type - 02 Nos
(iv) Current transformer (CT) of rating 100/5, tape wound, rated burden 5 VA - 03 Nos
(v) Micro processor based relay of suitable size/ratings-01 Nos
(vi) Battery charger auto/manual switch - 01 Nos
(vii) Suitable communication with features of following protections :- Over current, overvoltage, under voltage, under frequency, Low pressure oil.
(viii) Genset shall be fully automatic ie auto on when mains fail and auto off when mains on complete
F. MAINTENANCE AND OPERATIONAL MANUAL OF PLANTS - 01 SET SHALL BE SUBMITTED BY CONTRACTOR ALONGWITH THE FOLLOWING :-
(I) Test certificate of Alternator.
(ii) Test certificate of Diesel Engine.
(iii) Test certificate of Gen Set (by OEM).
(iv) Test certificate of Acoustic enclouser.
(v) Rubber mat.
Note : (a) Provision of PCC plateform as per manufacturer guidelines/specifications and shall be of required size. The cost of the same shall be deemed to be included in the unit quoted rates. Nothing shall be admissible on this account
(b) Testing of the DG set shall be carried out by the rep of the accepting office/IEM
(c ) The contractor shall submit the drawing for approval of the GE before procurement of the DG set
(d) Resistive load whether water load or strip heaters of suitable capacity and POL/DHPP for testing of DG set to be made available during test by the contractor. The cost of the same shall be deemed to be included in the unit quoted rates.
(e) The DG set shall be procured from authorized OEM and of same group. The accoustic panel shall also be manufactured by the same OEM
(f) Anyother details not mentioned above but is required for efficient functioning of DG set is deemed to be included in the unit quoted rate
Supply and install water cooler stainless steel electric driven (single phase) having approx storage capacity of 80 Litres and nominal cooling capacity of 40 Litres per hours with minimum 3 star rating. Make- LG/Samsung/Blue Star / Voltas / Usha Sriram
Supply and installed of refrigerator electric driven (single phase) capacity 310 Ltrs complete with minimum 3 star rating all as specified and directed. Make- LG/Samsung/ Godrej / Whirpool
Supply and installed hi wall split units indoor / outdoor complete with cordless remote controll unit and and inbuilt air ioniser and plasma filter for better indoor air quality with minimum 3 star rating and EER 3.2 of capacity 1.5 TR with necessary wall brackets complete all as specified and directed.Make- LG/Samsung / Daikin/ Godrej/ Voltas/ Blue Star/ Carrier
Supply , install, testing and commissioning factory made cubical type, CPRI approved indoor type LT panel board totally enclosed, weather and vermin proofIP 55 class protection, 1100 volts grade, 50 Hz AC Supply made out of 2.00 mm thick CRCA sheet steel for load bearing and 2mm thick for non-laod bearing conforming to IS 2417--1962 insulated Aluminium busbar of 200 Amps ratings installed on fiber insulators housed in seperate bus chambers covered with heat shrinkable sleeve with necessary bus bar taping, copper controlled wiring of required size with 40x40x6mm angle iron frame , hinged doors, front opening and locking arrangement and powder coated on out side and inside including provision of PCC platform 100mm thick with PCC 1:4:8, type D2 and brick work etc using 40mm graded stone aggregate one meter arround the panel board, cable gland and lugs for incomming and out going cable etc. and to be accomodated with following accessories.
(a) 4 Nos bus bar rating 200 Amps and fixed on heavy duty rubberised / porcelain support - 01 No
(b) MCCB 125 Amps, 4 Pole, 415 volts, 36 KA, Ics=100% Icu - 01 Nos
(c) MCCB 63 Amps,4 pole, 415 Volts, 18KA, Ics=100% Icu - 04 Nos
(d) Ofload changeover switch panel mounted type of cap 125 Amps, 4 pole, 415 volts - 01 No
(e) Meter combination to rated voltage 0-500 volts and currents 0-125 Amps in three phase system Digital type - 01 Nos
(f) Capacitor bank 3 phase 415 Volts, 50 hz AC 5 KVAR - 01 No
(g) Indication lamp for RYB - 1 set
(h) Terminal block 125 Amps for incoming supply for RYBN - 01 No
(j) Terminal block 63Amps to out going supply for RYB - 05 No
(k) Fully automattic star delta starter suitable for 15HP monoblock pump set with single phase preventer - 03 Nos
(l) Power factor meter digital type display - 01 No
(m) Copper wound CT coil 100/5 - 03 Nos
Material and labour for earthing complete with galvanised steel plate earth electrode 600 x 600 x 6mm thick buried directly in ground ( earth pit not less than 2.25 mtr below normal top edge of the plate not less than 1.5 mtr below normal ground level connected with GI earth strip of size 32 x 6 mm thick at two points by means of bolts and nuts, check nuts and washers including charcoal dust, common salt, necessary exacavation in soft / loose soil, returning filling in and removal of surplus soil to a distance up to 50m, PCC pit in 1:3:6 type CI, using 20mm grade stone aggregate and MS angle iron frame 40 x 40 x 6mm, RCC 1:2:4 type B-1 using 20mm grade stone aggregate, 40mm thick pit cover, reinforced with 6mm dia TMT bars 75mm centre to centre both ways, MS handle 12mm dia, PGI funnel, wire mesh and GI pipe of 20mm bore (light grade) and earth lead protection pipe 50mm bore (medium grade) 5m long as shown in electrical plate No.5 of SSR Part-I including testing complete all as per directed.
Supply , installed test and comissioning of multistage submersible pump motor set electrically driven, 415 volts, 3 phase AC ssupply,, 50 Hz, discharge of water units , 330LPM at 120 meter head including connecting the same to column pipe of 50mm bore and lowering the same into borewell alongwith necessary submersible cable complete all as directed.
Note : (i) Lowering pipe and cable will be measured and paid saperately.
(ii). Contractor shall carry out the yeild test and cost of yeild test shall be deemed to be included in the rate quoted.
(iii) Prior approval of the accepting officerwill be obtained if there is any change in specification of pump set.
(iv) Discharge of pump will be decided according to yield of bore well by accepting officer.
Supply and fix PVC insulated and PVC sheathed multi stranded copper conductor flat weather proof cable for submersible pump set of size 3 core 6 Sqmm 1100 volts grade including necessary water Proof connection to submersible pump of cable lead complete all as specified and directed.
Material and labour for GI colomn pipes for submersible pump , 3 meter standered length as per IS heavy duty grade 50mm dia ISI marked with long GI socket complete. for holding and fasting the colomn pipe including jointing complete all as specified and directed.
Supply and fix star delta starter suitable for submersible pump of over load current rating 17-25 amps with phase falilure, phase imbalance, phase reversal short circuit protection including voltmeter, ammeter with ON- OFF trip indication and dry run preventor complete all as directed.
Supply and fixing of Centrifugal pump and motor set eleectric driven, 415 volts, 3 phasse AC supply, 50 Hz suitable of discharging capacity 4000 to 4500 LPM, having head 30 mtr inclusive of fully automatic star delta starter of suitable capacity, with PCC foundation 1:4:8 type D2 using 40mm stone aggregate all as directed by Engr-in-Charge.
Supply and fixing of monoblock pump set, electric driven 415 V, 3 phase system having capacity 15 HP having head of 41 mtr and discharge of 1200 LPM inclusive of and PCC poundation 1:4:8, type D2 using 40mm stone aggregate all as per specified and directed by Engr-in-charge.
Dashmesh Enterprises
M/s SHIVRATAN CONSTRUCTION
BRITE INDUSTRIES
Veer Brothers
Goodluck Enterprises
TANUJ CONST. CO.
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .