Centralized Air-Conditioning for Auditorium at Saharanpur Campus, IIT Roorkee
2026_IITR_921697_1
IWD/IE/26-27/RT/E-31
Open Tender
Electrical Works
Percentage
150 days
Saharanpur Campus, IIT Roorkee
As per tender documents
7 documents required · 7 mandatory
₹1,180
Registrar
₹1.9 L
11 Aug 2026
11 Aug 2026
2 Sept 2026
11 Aug 2026
1 Sept 2026
25 Aug 2026
11 Aug 2026 - 18 Aug 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1PART A (Supply Installation Testing and Commissioning) | |||||
| 2Supply, Installation, Testing & Commissioning of Modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling/heating having 100% hermetically sealed inverter type twin Rotary/Scroll Compressor(s), minimum two compressors (with individual seperate PCB) for above 14HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R-410-A Refrigerant or equivalent, vibration Isolators with suitable foundation etc. complete as required. To have better efficiency condensor fan shall be capable to operate at different speed with respect to load. The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and CPWD Specifications and work even at 50°C ambient temperature without tripping. | |||||
| 3The system shall be able to deliver 100% of the rated capacity upto 39 Degree Celcius. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply and BMS compatible. The unit shall be filled with first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion, and reduce the risk of degradation, thereby improving overall performance and durability. The Indian Seasonal Energy Efficiency Ratio (ISEER) of the unit shall be as per Energy Conservation and Sustainable Building Code (ECSBC) 2024 as below and complete as per CPWD specification, connections, inter connections etc. as required. (For capacity <40 kWr ISEER 6.4, Capacity > 40 and <70 ISEER 6.5, Capacity > 70 ISEER 6.6 for ECSBC Building) For Cooling and Heating (Both) | |||||
| 4 | 16 HP | 96 | Per HP | 20,385 | ₹19,56,960 |
| 5 | Supply, installation, testing and commissioning of Controller/Manager with touch screen display accessible through remote views to include the indoor plan layout view, icon view and list view and menus for system configurations. This will allow the users to put limitations on the maximum and minimum temperatures and ensures an appropriate room temperature. This system shall be compatible with connecting Minimum 256 nos. indoor units and remote access to a PC/ BMS through LAN/Wi-fi network. The controller enables monitoring of the VRF system's operation, including temperature, fan speed, and other parameters. | 1 | Nos | 3,82,313 | ₹3,82,313 |
| 6Supply, Installation, Testing and Commissioning of Y/T/Multi Joints. Joints shall be of same Original Equipment Manufacturer (OEM) make as of ODUs and IDUs | |||||
| 7 | Indoor Units | 4 | Each | 4,535 | ₹18,140 |
| 8 | Outdoor Multi Joints | 4 | Each | 8,098 | ₹32,392 |
| 9Floor Standing outdoor Type DX AHU | |||||
| 10AHU Construction: - Supply, installation, testing and commissioning of factory built floor mounted double skin type DX Air Handling Units made of 48+/-2 mm thick panels (Density:40+/-2 KG/Cu.m.) consisting of G.I. Casing of thickness 0.8 mm pre-coated outside layer and 0.8 mm thick GI sheet inside layer with polyurethene foam (PUF) insulation factory injected between them by injection moulding machine, complete with plug fan suitable for static pressure as detailed below, cooling coil section with machanically bonded aluminium finned copper tubes (tube thickness not less than 0.3 mm) cooling coil, filter section with filter having filteration efficiency and particle size matching TEFC drive motor suitable for 415+10% volts, 50 + 3% Hz, 3 phase, A.C. supply, minimum IP 55, drain connections, with stainless steel drain pan duly insulated , and necessary vibration isolation arrangement etc. complete as per specifications and drawings of following capacities. | |||||
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.37 MB
T31.pdf
Tender Documents • 1.99 MB
BOQ_968568.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].