Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance UDHAMPUR | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹13,100
Closing Date
8 Nov 2024, 3:00 pmClosed
Executive Engineer
Electric Division Udhampur JPDCL
Creation of 63 kVA Substation alongwith erection of 11KV line on 9 mtr. PCC Poles, 30mm Sq. ACSR Weasel conductor, LT Line on 8mtr. PCC Poles at Village Rakh Sansoo For research Station of SKUAST (J) Udhampur
2024_PDD_261064_1
ED/UDH/21 of 2024-25 dt. 17-10-2024
Open Tender
Electrical Works
Turn-key
90 days
Village Rakh Sansoo
Please refer Tender documents.
2 documents required · 2 mandatory
₹600
Executive Engineer Electric Division UdhampurJPDCL
₹13,100
13 Nov 2024
18 Oct 2024
9 Nov 2024
18 Oct 2024
8 Nov 2024
18 Oct 2024
18 Oct 2024 - 23 Oct 2024
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 11 KV line on 9 mtr. Long PCC poles, 30mm² ACSR Squirrel Conductor at village Rakh Sansoo for Research Station of SKAUST (J) Udhampur
9 mtr. Long PCC poles (PCC-WL-300 Kg)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30mm² ACSR conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KV Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT 3-phase 4 wire on 8 mtr. Long PCC Poles, 30mm ACSR Weasel conductor at village Rakh Sansoo for Research Station of SKAUST (J) Udhampur.
8 mtr. Long PCC poles (PCC-WL-300 Kg)
GI u Clamps for shackle insulator
30mm² ACSR Cond.
Shackle insualtor
Galvinized Nuts and Bolts.
Danger Plates with Clamps
Anti climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 63 KVA Sub station at village Rakh Sansoo for Research Station of SKAUST (J) Udhampur.
11/0.433 KV, 3-phase distribution Transformer 63 KVA with Bimetallic Terminal Connectors Energy Level-2 Aluminium Wound, & with LV Cable box having detachable Aluminium Gland plate
Gapless surge Arestor, 9 kv, 10 KA , LA with polymer housing stn. Type
11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical
11 KV Horn gap fuse set 3 phase 200 A
120mm² 1.1 KV Grade, PVC insulated standed conductor FRLS Type
9 mtr. long pole (ST-410 SP33)
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45KN, lightening impulse 75KV Positive and 80 KV Negative, creepage distance 320mm with fitting.
GI Channel /Angle/flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of sub stn. Excavation of earth pit of dia 650mm & depth 3000mm installation of earthing pipe of 40mm Nominal bore & 4mm wall thickness & length 2.5 mtr. Long as per IS 1239. G.I Strip for neutral earthing of size 25mmx3mm for connection of transforemr body, GO Set & lightening arrestor as per IS 2629/85, GI Nuts & bolts refilled with earth enhancement materials and earth chamber with RCC Slab cover
11 KV Poloymer composite pin insualtor, 12 KV, 5KN Lightening impulse 75 KV Positve and 80 KV Negative, creepage distance 320mm
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Danger Plates with Clamps
GI Barbed wire for Anticlimbing
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Painting of ST poles 9 mtr. of sub stn. with 1 coat of Red oxide
Painting of ST poles 9 mtr. of sub stn. with 2 coat of Aluminium paint
VEENA CONSTRUCTION CO. (BID ID -2196623)
M/S VAISHNO TRADERS (BID ID -2221451)
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .