Executive Engineer JPDCL ED Kathua
Office of the Executive Engineer JPDCL ED Kathua
Augumentation of Sub stations and reconductoring works at Mirpur Jagoo, Kalyanpur and Naroli in Nagri Block demanded in the Memorandum from Sh. Khazan Chand (BDC Chairperson) on Turnkey Basi
2022_PDD_188920_1
KED/25 of 2022-23 Dt.16.09.2022
Open Tender
Electrical Works
Turn-key
30 days
kathua
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,000
Executive Engineer JPDCL ED Kathua
₹60,000
25 Oct 2022
19 Sept 2022
7 Oct 2022
19 Sept 2022
6 Oct 2022
19 Sept 2022
19 Sept 2022 - 26 Sept 2022
Amount
Augmentation of Existing Transformer from 100-250 KVA At village kalyanpur
Augmentation of Existing Transformer from 100-250 KVA At village kalyanpur on Turnkey Basis by way of Supply, Erection/Installation, Testing, commissioning etc of the following material: (Dismantlled transformer and usefull allied material shall be returned to Divisional Stores at kathua)
11/0.433 KV 3 Phase Distribution Transformer 250 KVA with Bimetallic Terminal Connector Energy Level-2(Copper Wound) and with LV Cable box having detachable Aluminium Gland plate
185 mm² (2Ckt) Single Phase Cable,1.1K V Grade, PVC Insulated Stranded Conductor FRLS type
GI Channel/Angle/Flat of sizes including clamps
50mm2 ACSR Rabbit conductor
Gapless Surge Arrestor,9 kV ,10 KA ,LA with polymer housing, Stn. Type
9 Mtr PCC poles (WL 300 KG)
Pre febricated LT switch 2 Ckts
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Galvinized Nuts and Bolts.
Laying of HT line on 9 Mtrs.PCC poles with ACSR Weasel Conductor at kalyanpur on Turnkey Basis by way of Supply, Erection/Installation, Testing, commissioning etc of the following material: (Dismantlled transformer and usefull allied material shall be returned to Divisional Stores at kathua)
9 Mtr. Long Pole(WL-300 Kg )
GI V cross-arm with top Bracket including clamp
GI Channel x-arm including clamps and braces
50 mm² ACSR Conductor ( Rabbit)
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvanized Nuts and Bolts
Danger Plates with Clamp
Anti Climbing Devices with clamps
Earthing Complete by GI Pipe 40mm dia or GI Rod 20mm ,2.5 mtrs long through GI Strip
Stone Pad (300mmx300 mmx75mm)
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Laying of LT line on 8 Mtrs.PCC poles with ACSR Weasel Conductor 3 Phase 4 wire at Kalyanpur on Turnkey Basis by way of Supply, Erection/Installation, Testing, commissioning etc of the following material: (Dismantlled transformer and usefull allied material shall be returned to Divisional Stores at kathua)
8 Mtr. Long Pole(PCC WL-200Kg )
GI U-Clamp for Shackle insulators
30 mm² ACSR Conductor weasel
16 KN Polymer Shackle insulators
Galvanized Nuts and Bolts
Danger Plates with Clamp
Anti climbing Devices with Clamp
Earthing Complete by GI Pipe 40mm dia or GI Rod 20mm ,2.5 mtrs long through GI Strip
Stone Pad (300mmx300 mmx75mm)
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Augmentation of Existing Transformer from 100-250 KVA At village Naroli
Augmentation of Existing Transformer from 100-250 KVA At village Naroli on Turnkey Basis by way of Supply, Erection/Installation, Testing, commissioning etc of the following material: (Dismantlled transformer and usefull allied material shall be returned to Divisional Stores at kathua)
11/0.433 KV 3 Phase Distribution Transformer 250 KVA with Bimetallic Terminal Connector Energy Level-2(Copper Wound) and with LV Cable box having detachable Aluminium Gland plate
185 mm² (2Ckt) Single Phase Cable,1.1K V Grade, PVC Insulated Stranded Conductor FRLS type
GI Channel/Angle/Flat of sizes including clamps
50mm2 ACSR Rabbit conductor
Gapless Surge Arrestor,9 kV ,10 KA ,LA with polymer housing, Stn. Type
9 Mtr PCC poles (WL 300 KG)
Pre febricated LT switch 2 Ckts
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Galvinized Nuts and Bolts.
Laying of HT line on 9 Mtrs.PCC poles with ACSR Weasel Conductor at Naroli on Turnkey Basis by way of Supply, Erection/Installation, Testing, commissioning etc of the following material: (Dismantlled transformer and usefull allied material shall be returned to Divisional Stores at kathua)
9 Mtr. Long Pole(WL-300 Kg )
GI V cross-arm with top Bracket including clamp
GI Channel x-arm including clamps and braces
50 mm² ACSR Conductor ( Rabbit)
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvanized Nuts and Bolts
Danger Plates with Clamp
Anti Climbing Devices with clamps
Earthing Complete by GI Pipe 40mm dia or GI Rod 20mm ,2.5 mtrs long through GI Strip
Stone Pad (300mmx300 mmx75mm)
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Laying of LT line on 8 Mtrs.PCC poles with ACSR Weasel Conductor 3 Phase 4 wire at Naroli on Turnkey Basis by way of Supply, Erection/Installation, Testing, commissioning etc of the following material: (Dismantlled transformer and usefull allied material shall be returned to Divisional Stores at kathua)
8 Mtr. Long Pole(PCC WL-200Kg )
GI U-Clamp for Shackle insulators
30 mm² ACSR Conductor weasel
16 KN Polymer Shackle insulators
Galvanized Nuts and Bolts
Danger Plates with Clamp
Anti climbing Devices with Clamp
Earthing Complete by GI Pipe 40mm dia or GI Rod 20mm ,2.5 mtrs long through GI Strip
Stone Pad (300mmx300 mmx75mm)
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Laying of HT line on 9 Mtrs.PCC poles with ACSR Weasel Conductor at Mirpur Jago on Turnkey Basis by way of Supply, Erection/Installation, Testing, commissioning etc of the following material: (Dismantlled transformer and usefull allied material shall be returned to Divisional Stores at kathua)
9 Mtr. Long Pole(WL-300 Kg )
GI V cross-arm with top Bracket including clamp
GI Channel x-arm including clamps and braces
50 mm² ACSR Conductor ( Rabbit )
PG Clamps for Weasel Conductor
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvanized Nuts and Bolts
Danger Plates with Clamp
Anti Climbing Devices with clamps
Earthing Complete by GI Pipe 40mm dia or GI Rod 20mm ,2.5 mtrs long through GI Strip
Stone Pad (300mmx300 mmx75mm)
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Laying of LT line on 8 Mtrs.PCC poles with ACSR Weasel Conductor 3 Phase 4 wire at Mirpur Jago on Turnkey Basis by way of Supply, Erection/Installation, Testing, commissioning etc of the following material: (Dismantlled transformer and usefull allied material shall be returned to Divisional Stores at kathua)
8 Mtr. Long Pole(PCC WL-200Kg )
GI U-Clamp for Shackle insulators
30 mm² ACSR Conductor weasel
16 KN Polymer Shackle insulators
Galvanized Nuts and Bolts
Anti climbing Devices with Clamp
Earthing Complete by GI Pipe 40mm dia or GI Rod 20mm ,2.5 mtrs long through GI Strip
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
M/S SINGH ELECTRICAL CONTRACTOR AND SUPPLIERS
M/S APR CONSTRUCTIONS
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .