Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.4 LAccepted-AOC 113 F BLOCK HOUSE NUMBER 113 F BLOCK PANKI KANPUR NAGAR UTTAR PRADESH 208020 | KANPUR NAGAR | UTTAR PRADESH | 208020 | L1 | Accepted-AOC Ist Lowest | |
| 2 | L2₹1.4 L+₹3,380 (2.45%)Rejected-AOC 16F 1K NEW MARKET BAMRAULI NEAR BAMRAULI RAILWAY STATION ALLAHABAD UTTAR PRADESH 211012 | PRAYAGRAJ | UTTAR PRADESH | 211012 | L2 | Rejected-AOC IInd Lowest | |
| 3 | L3₹1.4 L+₹6,040 (4.38%)Rejected-AOC 222 346 LUKERGANJ LUKERGANJ LUKERGANJ ALLAHABAD UTTAR PRADESH 211003 | PRAYAGRAJ | UTTAR PRADESH | 211003 | L3 | Rejected-AOC IIIrd Lowest |
Tender Value
₹1.4 L
EMD Value
₹1,400
Closing Date
9 Sept 2024, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Superintending Engineer
Superintending Engineer, Electricity Transmission Circle-II, U.P. Power Transmission Corporation Ltd. 57- George Town, Prayagraj.
26/ETC-II(P)/2024-2025
2024_UPTCL_951039_1
26/ETC-II(P)/2024-2025
Open Tender
Electrical Works
Item Rate
60 days
132 KV S/S SIRATHU
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
Executive Engineer Electy. Trans. Div. Naini Alld.
₹1,400
10 Dec 2024
2 Sept 2024
10 Sept 2024
2 Sept 2024
9 Sept 2024
2 Sept 2024
Amount
The Following work is required for smooth operation of cooling fan installed on 40 MVA T/F-II at 132 KV S/S Sirathu, Kaushambi. The details of work listed below.
Supply and fixing of winding temperature indicator (analog type) of temp range from (0-150) OC, 5A, AC/DC both and consist of two flexible capillary tubes of 05 meter long and 04 no mercury bulb switch for alarm, trip and cooling control system of power Transformer of standard make. Work includes fixing of capillary inside the temperature sensing element within the tank and proper termination of connection at both ends.
Supply and fixing of Oil temperature indicator (analog type) of temp range from (0-150) OC, SA, AC/DC both and consist of two flexible capillary tubes of 05 meter long and 02 no mercury bulb switch for alarm & trip of power Transformer of standard make. Work includes fixing of capillary inside the temperature sensing element within the tank and proper termination of connection at both ends. This work also include replacement of damage oil temp indicator mounted on radiator tank. (including all supply).
Supply and fixing of 01 no main switch of 3P/IW, 415V, 16A rating and 01 no MCB of 4 pole, 415 V.16A rating for 3 phase incoming supply for cooling fans.
Supply and fixing of 01 no 415 volt, 16 A, 4 No, contactor for main supply of cooling fans installed on 20 MVA T/F work includes proper connection of contactor with ACDB or AC cubical installed in the switchyard.
Supply and fixing of 04 no fan control contactors of rating 230v, 9A, 08 NO, for auto function of cooling fans and 03 no relays of rating 230 V. 9A, 02 NO-02 NC for supply monitoring for cooling fans.
Fixing of 08 no, 3 pole MCB of rating 230 V, 2A on the rail fixed on the front side of marshaling box (MCB provided by department free of cost).
Supply and Fixing of 08 no overload relay (Type 3US5000) of rating (0.5-1A) for cooling fan of transformer on the front side of the marshaling box.
Supply and fixing of 10 no fan control switches for on/off control of fans (ON/OFF) of ratings 415 V 10A of standard make.
Supply and fixing of 02 no fan control contactors of type 3TS30 and rating 230 V, 9A, 6NO-2NC for control operating of cooling fans of standard make.
Preparation of Interconnection drawing & Modification in marshaling box, wiring for new control and switching eqipment to be installed in the cubical box. The work includes submission of drawing. Connection/Termination as approved by department (in 3 copy).
Supply and fixing of 10 no tap position indicator of push off type with the rating 230 V, 2A, and 01 no panel lamp (LED) of 230 V, 8W suitable for RTCC panel of said T/F.
R.S.ASSOCIATE
M/S New Sharma Electricals
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .