Executive Engineer Electric Division UdhampurJPDCL
Executive Engineer Electric Division UdhampurJPDCL
Creation of 25 KVA SS along HT.LT line at hamlet Barnekh village Sarar on turnkey basis
2023_PDD_202261_1
ED/UDH/102 of 2022-23 dt. 11-01-2023
Open Tender
Electrical Works
Turn-key
45 days
In District Udhampur
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
Executive Engineer Electric Division UdhampurJPDCL
₹66,100
11 Feb 2023
11 Jan 2023
25 Jan 2023
11 Jan 2023
24 Jan 2023
11 Jan 2023
11 Jan 2023 - 23 Jan 2023
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of HT line on 9 mtr long ST poles alongwith 30 mm sq. ACSR Weasel Conductor for Creation of 25 KVA at Hamlet Barnekh village Sarar.
9 mtr. Long ST Pole (ST-410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Braces
30 Sq. mm ACSR Weasel Conductor
PG Clamps for 30 mm² ACSR Conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting of 9 mtr ST poles including crossarms/clamps with two coat of Aluminium Paint.
Al. Jointing sleeves
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 25 KVA at Hamlet Barnekh village Sarar.
11/0.433kV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11kV GO, Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A
95 mm² 1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST-410 SP33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
LT switch with 50x6mm angle iron, 50x6mm Aluminium strip fixed on Bus bar insulators
Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line 3 phase 4 wire LT 30mm sq. On 8 mtr long ST poles alongwith ACSR Weasel Conductor at Hamlet Barnekh Village Sarar.
8 mtr. Long ST Pole (ST-410 SP15)
G.I M Clamps for Shackle Insulator
30 sq. mm ACSR Weasel Conductor
Shackle Insulator
Galvinized Nuts and Bolts.
Danger Plates with Clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip25X3 mm
Painting of 9 mtr ST poles with two coat of Aluminium Paint.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line 1phase 2 wire LT 30mm sq. On 8 mtr long ST poles alongwith ACSR Weasel Conductor at Hamlet Barnekh Village Sarar.
8 mtr. Long ST Pole (ST-410 SP15)
G.I M Clamps for Shackle Insulator
30 sq. mm ACSR Weasel Conductor
Shackle Insulator
Galvinized Nuts and Bolts.
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip25X3 mm
Painting of 9 mtr ST poles including crossarms/clamps with two coat of Aluminium Paint.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Supply of Electrical Safety shoes as per ISI
Supply of Safety gloves (Insulating Electric Hand Gloves)ISI marked33000/7500 V
Supply of11kV GO, Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
Supply of 11KV Earthing /Discharge Rod (as per relevant IS ) for earthing of line at site (Set of 3)
Supply of Al ladder 20 feet long Heavy Duty
Supply of Safety Helmets ISI Marked ISI 2925
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
Supply of 11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Supply of Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
M/s R.S CONSTRUCTIONS
M/S VAISHNO TRADERS
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .