Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.9 LAccepted-AOC BALTIKURI INDUSTRIAL ESTATE PLOT NO A 01 DASNAGAR HOWRAH 711113 | HOWRAH | HOWRAH | WEST BENGAL | 711113 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹8.4 L+₹1.4 L (20.8%)Rejected-Finance 103 1A RAJA DINENDRA STREET KOLKATA 700006 | KOLKATA | KOLKATA | WEST BENGAL | 700006 | L2 | Rejected-Finance Higher rate quoted | |
| 3 | L3₹8.8 L+₹1.9 L (26.9%)Rejected-Finance | L3 | Rejected-Finance Highest rate quoted |
Tender Value
Refer Docs
EMD Value
₹13,500
Closing Date
28 Oct 2024, 1:00 pmClosed
EE-I,WKED,PWDte.
New Secretariat Building, C Block, 4th floor 1, K.S Roy Road, Kolkata-700001
Arrangement of Air-conditioning system and Electrical Installation work in the Training - cum -Conference Hall at the 9th floor of Block- B of New Secretariat Building, Kolkata.
2024_WBPWD_760966_1
WBPWD/EE-WKED/NIQ-15/2024-25
Open Tender
A/C ORG
Item Wise
15 days
New Sectt. Building
Please refer Tender documents.
5 documents required · 5 mandatory
₹13,500
8 Apr 2025
1 Oct 2024
30 Oct 2024
1 Oct 2024
28 Oct 2024
1 Oct 2024
Amount
Supply & delivery of 240V split Air-conditioner machine having cooling capacity not less than 10000W, ISSER 3.37 to 4.1, Noise level not more than 53db. This Split Air Conditioning machine should be fitted with Rotary compressors, LCD remote & all other accessories suitable for Refrigerant-R32/R410A. (Make-O-General/ Mitsubishi Electric/Mitshubishi Heavy Industries/Hitachi/Daikin as per approved by EIC/authority).
Installation, testing & commissioning of the above-said split ACs incl. supply & fixing required Angle Iron Structure on wall for placing outdoor unit & mending good the damages as per direction of E.I.C.
Supply & Installation of Extra Add-on items- HVAC grade 5/8"(for suction) & 3/8"(for discharge) copper refrigerant pipe with 9mm thick nitrile rubber insulation including shaddle,screw, insulation tape, fastner etc for above AC machine as per direction of EIC.
Supply & Laying of 4core 2.5sq.mm 1.1 KV insulation grade sheathed Cu cable with gas line as per direction of EIC for making interconnection/communication between Indoor to Outdoor unit of Split type AC m/c. (Polycab/Gloster/Finolex/KEI/ Havells /RR Cable as approved by E.I.C)
Supply and laying 20mm hard PVC pipe (heavy type) for water drainage.
Supplying, fabrication & fixing 2 Nos. M.S. Angle of size (50 mm x 50 mmx6mm) for making platform for installation of outdoor unit of 3.0 TR Split AC incl. drilling 2 nos holes in each Angle including cutting holes into the wall & grouting the same with cement concrete (1:1 ½ :3) etc. fabricated with horizontal angle of 25 mm x 25 mm x 6 mm including supporting angle 40 mm x40mm x 6 mm in each platform in outer edge for transmitting the load centrally through 2Nos. (40 mm x 40 mm x 6 mm) Angle inserted into the exiting wall. The entire structure should be baricated & safe for ODU maintenance. Area of the platform is 2Mtr. x 1Mtr. or as per Machine configuration & load with adequate service access as per direction of EIC
Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment.
2+14 way Enclosure [Make: Legrand /L&T/Siemens as approved by E.I.C] [D-9, D-10/13]
Supplying and fixing 240/415V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection (Make: Legrand/Siemens/L&T as approved by E.I.C) [D-6/7]
(a) 6-32 Amps SP MCB
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection.(Make: Legrand/Siemens/L&T as approved by E.I.C) [D-5/6]
(a) 40 Amp FP Isolator
Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Legrand: Myrius/Arterior/L&T/ABB as approved by E.I.C) fixed on Modular GI switch board with top cover plate and 2 no. suitable size “Ph & N” copper bar & earthing attachment fixed on wall incl. mending good damages to original finish.[Avg Run-10 mtr.] [E-24/1]
a) Avg. Run-8mtr [E-24/1(c)]
b) Avg. Run-10mtr [E-24/1(e)]
c) On board[E-24/3/(a)]
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene/PVC rigid pipe and by the prelaid GI fish wire and making necy. connection as required [E-9/1]
i)3 x 22/0.3 (1.5 sqmm) [ E-9/1(b)]
ii)2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC [ E-9/1(s)]
iii) 2x56/0.3 (4 sqmm) + 2x36/0.3 (2.5 sqmm) as ECC [ E-9/1(v)]
iv) 2x84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC [ E-9/1(y)]
Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] of following sizes on wall, ceiling with saddles and other accessories as required and mending good damages to building works [E-16/7]
a) 20mm size [E-16/7(a)]
b) 25mm size [E-16/7(a)]
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. [F-9]
i) 2.5sqmm [F-5/9(i)]
ii) 4 sqmm [F-5/9(ii)]
iii) 6 sqmm [F-5/9(iii)]
Supplying & Fixing GI Modular Switch Board of the following sizes complete with three no. suitable size Copper bar with holes (for Ph, N & E) fixed on bakelite/Hard Rubber insulator over the MS welded chairs incl. top cover flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works. [E-17/1]
2 Row 12 Module [E-17/1(e)]
6 Module [E-17/1(b)]
4 Module [E-17/1(a)]
Supply & Fixing 240 V 6 A Modular type switch (Legrand: Myrius/Arterior /L&T/ABB approved by EIC) on existing GI Modular type switch board having top cover plate and making necessaryconnections as required. [E-17/3(a)]
Supply & Fixing 240 V 16 A Modular type switch (Legrand: Myrius/Arterior or equivalent model of Crabtree/ROMA approved by EIC) on GI Modular type switch board having top cover plate and making necessary connections as required [E-17/3(b)]
Supply & Fixing 240 V, 6A, 5 pin Modular type plug socket (Legrand: Myrius/Arterior/L&T/ABB approved by EIC), without switch & plug top, on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E-17/4(a)]
Supply & Fixing 240 V, 6/16 A, 5 pin Modular type plug socket (Legrand: Myrius/Arterior/L&T/ABB approved by EIC), without plug top and switch, on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E-17/4(b)]
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with suitable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length [C-2/17]
Supply of 4'ft LED Twin batten/Metal frame fittings incl. 2nos. 18W Polycarbonate/Aluminium LED tube having luminoius efficacy of 100lm/W [Philips/Crompton Greaves/ Wipro or manufacturer with own NABL accredited Lab with valid Test certificate as approved by E.I.C]
S&F recessed mounting 2ftx2ft square 36 Watt LED luminaire of warm-white or cool day light(as per choice of the authority/E.I.C) with glare-free illumination having luminous efficacy- 100lm/W and complete with all accessories (Make : Crompton /Phillips / Wipro or manufacturers with own NABL acreedited Lab having valid Test certificate as approved by E.I.C] incl. inter connection & necy. fixing arrangement as per direction of EIC.
Supply & Fixing 240V 18''(450 mm) Sweep heavy duty best quality AC Wall Bracket Full metal body Fan (Make : Orient/Crompton/Usha as approved by E.I.C) complete with all accessories incl. inter connection on wooden board on wall incl. S&F wooden board of suitable size as per direction of EIC
S&F Timer Control Unit for single phase Split type AC machine assembled with following accessories: - i)12-way double-door(Metal door) SPNDB Box (L & T cat no.-DBSPN012DD or equivalent model of Legrand/ Siemens as approved by E.I.C)-1 no. ii)25A DP 30mA RCCB (Make: L&T Cat no.-BG202503 or equivalent model of Legrand /Siemens ) - 1 no. iii)Digital 24 hour time switch (Make-L&T Cat no.-67DDT0 or equivalent model of GIC/Siemens) -1no. iv)25A 2-pole power contactor (L&T: Type- MU25 ; Cat no.-CS90118 or equivalent model of Siemens/ABB)-1no. v)Melamine terminal block-2 nos. vi)LED indicating lamp (L&T: SIL R 240V)-1 no. vii) ON/OFF Push = 2 nos viii) 6 amp auto mannual toggle switch (Make- L&T or equivalent make as approved by E.I.C) ix) S&F Thermal overload Relay(13-22A) (Make-L&T cat no.-CS90207OODO or equivalent model of Siemens/ABB)- 1no. All control circuit wiring would be made by 1x1.5 sqmm FRLS stranded Cu wire(Brand approved by E.I.C) and the I/C & O/G circuit with 1x4sqmm copper wire of suitable length maintaining colour code incl taping, socketing to complete the work.
Supply & fixing automatic single phase AC starter of 25Amp capacity equipped with Timecheck, Voltcheck & Ampcheck and 3-digit display (Make- Electron-model no.-OPL-3+ or equivalent model of LT/Legrand as per dierction of E.I.C) to be fixed on wall with all fixing accessories complete as to G.S
Supply & laying 1.1 KV grade 3 core 4 sqmm flexible copper Cable with screw, saddle,drill machine nut bolt etc all necessary items needed for connection. (from starter to A.C outdoor Connection)(make: Havels/KEI/Polycab/Finolex as per approved by EIC)
Disconnection & dismantling existing old Electrical installation, Switch-board, wiring, Electrical fitting/fixtures etc with owns tools & takles incl. mending good damages as per GS and clearing/removing from the site.
Add. G.S.T.@ 18% on total value.
Add. LWC.@ 1% on total value
S.R. REFRIGERATION AND APPLIANCES (BID ID -5727676)
UNIVERSAL SALES (BID ID -5727380)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .