GE NORTH PUNE
Garrison Engineer North General Cariappa Marg Camp Pune - 411001
GE (N) P/TOKEN- 97 OF 2025-2026 REPAIR MAINT OF DG SETS AND ALLIED INFRA AT VARIOUS E/M INSTALLATIONS IN THE AREA OF AGE E/M (N) UNDER GE (N) PUNE
2026_MES_755819_1
GE (N) P/TOKEN- 97 OF 2025-2026
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
GE NORTH PUNE
Refer tender documents.
8 documents required · 8 mandatory
₹500
GE NORTH PUNE
₹80,000
Yes
13 May 2026
10 Mar 2026
2 Apr 2026
10 Mar 2026
31 Mar 2026
24 Mar 2026
11 Mar 2026 - 17 Mar 2026
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel ((TTA Panels complying to IEC 61439)) CPRI approved double door floor mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15 mm thick of outer body of suitable size with Copper bus bar 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Kahun Road).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 250 Amp (01 Nos), adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN2 (CM99830OOOO)-01 Nos, Spreaders Terminal DN1, DN2-04 Pole (set of 8) (CM92007OOOO)-01 Nos), Phase Barrier -01 Nos, Auxiliary 1 C/o+TAC 1 C/O DN2, DN3B, DN3, DN4-Right 01 (nos) -01 Nos, 250/5 DIN Type Cl-1 VA-5CT-03 Nos
(b) Copper bus bar of suitable size 500 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B &R-G-O)) complete - 01 Set
Outgoing
(a) MCCB 3 pole, 100 Amp (DN0-100C) (CM91162OOKO)-01 Nos,adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN0 (CM97896OOOO)-01 Nos, Spreaders Terminal DN0-3 Pole (Set of 6) (CM97785OOO)-01 Nos, Phase Barrier- 01 Nos, Auxiliary 1 c/o +TAC 1 C/O DN0, Dn1-Right-01 (R-G-O Indication Lamp-01 Nos), 6A SP 'c' MCB -LK BB10060C-02 Nos
(b) MCCB 3 pole, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 18 KA (DU100D) (04 Nos) CM90517OOHO)at 415 volts Ics=100% Icu With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle, Spreaders Terminal DU100D/DU100H-3 Pole (set of 6)-04 Nos (CM97785OOO), Phase Barrier- 04 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI ((TTA Panels complying to IEC 61439)) approved double door floor mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15 mm thick of outer body of suitable size with Copper bus bar 600 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Vishwamithra Marg Near Main Gate ).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 400 Amp (DN3B-400D) (CM98403OORO of L &K) 01 Nos, adjustable type Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu - With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN3B, DN3-01 Nos, Spreaders terminal DN3B/DN3-400- 4 Pole (set of 08)-01 Nos (ST98066OOOO), Phase Barrier01 No, Auxiliary 1 c/o +TAC1 C/O DN2, DN3, DN4,-Right
(b) Copper bus bar of suitable size 600 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B &R-G-O) complete with bakalite fuse fitting - 01 Set
(f) 400/5 Ring Type Cl-1 VA-15 CT-03 Nos
(g) 6A SP'C' MCB (Lk) (BB10060C)-08 Nos
Outgoing
(a) MCCB 3P, 200 Amp (DN1-250C) (CM90638OONO)-03 Nos, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle Dn1--03 Nos, Spreaders terminal DN1, DN2-3 Pole (set of 6) (ST98053OOOOO)-03 nos), Phase Barrier 03 Nos, Auxiliary 1 c/o +TAC1 C/O DN2, DN3, DN4,-Right, R-G-O indication Lamp-03 nos, 6A SP'C' MCB (LK)-06 nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
(d) Automatic timer switch with switches ON/OFF the street lights base on lux level of natural light current rating 40 Amps, 220 Volts, 50 Hz - 01 No.
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI ((TTA Panels complying to IEC 61439)) approved double door floor mounted and wall/pole mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body and inner compartments/ Protective door of 2.00 mm of suitable size with Copper bus bar 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Bldg No.133 Ghorpadi).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 250 Amp, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu - With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle, Spreaders, Phase Barrier01 No
(b) Copper bus bar of suitable size 500 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3P, 100 Amp, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle, Spreaders, Phase Barrier 02 Nos
(b) MCB TPN 63 Amp, 16 KA, 415 V AC - 04 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar CPRI ((TTA Panels complying to IEC 61439)) approved panel single door floor mounted and wall/pole mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body and 2.00mm for inner compartments of suitable size with Copper bus bar 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Near Bldg No T-1 Old Sapper Line).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 320 Amp, with Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 50 KA at 415 volts Ics=100% Icu -01 No
(b) Copper bus bar of suitable size 500 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3 pole, 125 Amp, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu - 03 Nos
(b) MCB TPN 63 Amp, - 02 Nos
(b) MCB DP 32 Amp, - 02 Nos
(d) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar CPRI ((TTA Panels complying to IEC 61439)) approved panel single door floor mounted and wall/pole mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body and 2.00mm for inner compartments of suitable size with Copper bus bar (50 x 10 mm) 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Golf main office).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 300 Amp, with Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 50 KA at 415 volts Ics=100% Icu -01 No
(b) Copper bus bar of suitable size 500 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3 pole, 100 Amp, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu - 01 Nos
(b) MCB TPN 63 Amp, - 04 Nos
(b) MCB DP 32 Amp, - 04 Nos
(d) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Supply, fixing and commissioning of CPRI Approved AMF panel of IP 65 rating for existing DG set of Capacity 82.5 KVA made from CRCA sheet 3.15.mm thick Outdoor pedestal type supported on MS iron channel 75 x 40mm/suitable size at required, totally enclosed with front and rear opening, hinged doors with projected a raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 copper bus bars with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 125 A Capacity complete and Powder coating, necessary internal electric connection as required and provision of the following: - Loc - Old Telephone Exchange - 82.5 KVA DG Set
(a) 125A, 3P, 25kA, MCCB ATM (TM) Release, Type: Winbreak-1-1.00 Nos (C & S CSE1M125ATM3 P-125) with Extended Rotary Handle CSE1- 01 Nos (C &S EHW 125), 80-125A, 3P, Spreader Terminals, CSE1, CSC1, CSC2, CSC3 WiNbreak1 -02 Nos ( C & S CSET2033)
(b) Wire Wound CT 125/5A, CL-01, 5VA- 01 Nos (Make & CAT No Amol CT125)
(c) Digital meter 3Ph, 4W kWh meter, LCD type, Dir Base Mounting 240V 5- 30 A Acc 1-01 Nos (Make and CAT No WR301BC4D20 of L &T)
(d) 3 PH Digital Ammter 230V, AC Aux Supply -01 Nos (Secure)
(e) Digital Voltmeter 3 PH- 01 Nos (Secure)
(f) 150A, 3P, Exceed Power Contactor with AC coil, 235V-02 Nos (For mains and DG supply) (C & S LC1FDP150AEC5W)
(g) Line Voltage Monitor Relay , 2 Changeover,220V- 01 Nos (Proton VMR3)
(h) Control Relay 2 C/O 24V DC- 03 Nos (salzer MSP2P24)
(j) Closed Terminals Socket for MSP - 2 Pole - 03 Nos (Salzer MSP 08C)
(k) Red, Yellow, Blue Indicating lamp with integral LED metallic suaitable for operating at 110V, 240V, 220V, 48V, 24V, 12V AC/DC- 03 Nos (C &S RCB7-IVL74, RCB7-IVL78, RCB7-IVL76)
(l) 6A, 1P, 10kA, C Curve Inductive Load With Surge Current-Motor Circuit Applications MCB-05 Nos (C & S CSMBS1C6)
(m) 10A, 2P, 10kA, C Curve Inductive Load With Surge Current-Motor Circuit Applications MCB-02 Nos ( C &S CSMBS2C10
(n) 4 mm, Feed Thru Screw Clamp Terminal-12 Nos (Connectwell-CTS4UN)
(O) 10 mm Slide Link Disconnect Screw Clamp TB (Connectwell-CDTTU)-03 Nos
(p) End Plate for EPCDTTU (Connectwell EPCDTTU)-01 Nos
(q) Battery Charger,24V,DC,10A-01 Nos (NHP BATC)
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Supply, fixing and commissioning of CPRI Approved AMF panel of IP 65 rating for existing DG set of Capacity 100 KVA made from CRCA sheet 3.15.mm thick Outdoor pedestal type supported on MS iron channel 75 x 40mm/suitable size at required, totally enclosed with front and rear opening, hinged doors with projected a raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 copper bus bars with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 160 A Capacity complete and Powder coating, necessary internal electric connection as required and provision of the following: - Loc - Old Telephone Exchange - 100 KVA DG Set
(a) 160A, 3P, 25kA, MCCB ATM (TM) Release, Type: Winbreak-1-1.00 Nos (C & S CSE2M250ATM3 P-160) with Extended Rotary Handle CSE2- 01 Nos (C &S EHW 1-250), 160-250A, 3P, Spreader Terminals, CSE2, CSC4, WiNbreak1 -02 Nos ( C & S CSET2033)
(b) Wire Wound CT 160/5A, CL-01, 5VA- 01 Nos (Make & CAT No Amol CT160)
(c) Digital meter 3Ph, 4W kWh meter, LCD type, Dir Base Mounting 240V 5- 30 A Acc 1-01 Nos (Make and CAT No WR301BC4D20 of L &T)
(d) 3 PH Digital Ammter 230V, AC Aux Supply -01 Nos (Secure)
(e) Digital Voltmeter 3 PH- 01 Nos (Secure)
(f) 185A, 3P, Exceed Power Contactor with AC coil, 235V-02 Nos (For mains and DG supply) (C & S LC1FDP185AEC5W)
(g) Line Voltage Monitor Relay , 2 Changeover,220V- 01 Nos (Proton VMR3)
(h) Control Relay 2 C/O 24V DC- 03 Nos (salzer MSP2P24)
(j) Closed Terminals Socket for MSP - 2 Pole - 03 Nos (Salzer MSP 08C)
(k) Red, Yellow, Blue Indicating lamp with integral LED metallic suaitable for operating at 110V, 240V, 220V, 48V, 24V, 12V AC/DC- 03 Nos (C &S RCB7-IVL74, RCB7-IVL78, RCB7-IVL76)
(l) 6A, 1P, 10kA, C Curve Inductive Load With Surge Current-Motor Circuit Applications MCB-05 Nos (C & S CSMBS1C6)
(m) 10A, 2P, 10kA, C Curve Inductive Load With Surge Current-Motor Circuit Applications MCB-02 Nos ( C &S CSMBS2C10
(n) 4 mm, Feed Thru Screw Clamp Terminal-12 Nos (Connectwell-CTS4UN)
(o) 10 mm Slide Link Disconnect Screw Clamp TB (Connectwell-CDTTU)-03 Nos
(p) End Plate for EPCDTTU (Connectwell EPCDTTU)-01 Nos
(q) Battery Charger,24V,DC,10A-01 Nos (NHP BATC)
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Supply, fixing and commissioning of CPRI Approved AMF panel of IP 65 rating for existing DG set of Capacity 110 KVA made from CRCA sheet 3.15.mm thick Outdoor pedestal type supported on MS iron channel 75 x 40mm/suitable size at required, totally enclosed with front and rear opening, hinged doors with projected a raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 copper bus bars with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 160 A Capacity complete and Powder coating, necessary internal electric connection as required and provision of the following: - Loc - Old Telephone Exchange - 110 KVA DG Set
(a) 160A, 3P, 25kA, MCCB ATM (TM) Release, Type: Winbreak-1-1.00 Nos (C & S CSE2M250ATM3 P-160) with Extended Rotary Handle CSE2- 01 Nos (C &S EHW 1-125), 160-250A, 3P, Spreader Terminals, CSE2, CSC4, WiNbreak1 -02 Nos ( C & S CSET2033)
(b) Wire Wound CT 160/5A, CL-01, 5VA- 01 Nos (Make & CAT No Amol CT160)
(c) Digital meter 3Ph, 4W kWh meter, LCD type, Dir Base Mounting 240V 5- 30 A Acc 1-01 Nos (Make and CAT No WR301BC4D20 of L &T)
(d) 3 PH Digital Ammter 230V, AC Aux Supply -01 Nos (Secure)
(e) Digital Voltmeter 3 PH- 01 Nos (Secure)
(f) 185A, 3P, Exceed Power Contactor with AC coil, 235V-02 Nos (For mains and DG supply) (C & S LC1FDP185AEC5W)
(g) Line Voltage Monitor Relay , 2 Changeover,220V- 01 Nos (Proton VMR3)
(h) Control Relay 2 C/O 24V DC- 03 Nos (salzer MSP2P24)
(j) Closed Terminals Socket for MSP - 2 Pole - 03 Nos (Salzer MSP 08C)
(k) Red, Yellow, Blue Indicating lamp with integral LED metallic suaitable for operating at 110V, 240V, 220V, 48V, 24V, 12V AC/DC- 03 Nos (C &S RCB7-IVL74, RCB7-IVL78, RCB7-IVL76)
(l) 6A, 1P, 10kA, C Curve Inductive Load With Surge Current-Motor Circuit Applications MCB-05 Nos (C & S CSMBS1C6)
(m) 10A, 2P, 10kA, C Curve Inductive Load With Surge Current-Motor Circuit Applications MCB-02 Nos ( C &S CSMBS2C10
(n) 4 mm, Feed Thru Screw Clamp Terminal-12 Nos (Connectwell-CTS4UN)
(O) 10 mm Slide Link Disconnect Screw Clamp TB (Connectwell-CDTTU)-03 Nos
(p) End Plate for EPCDTTU (Connectwell EPCDTTU)-01 Nos
(q) Battery Charger,24V,DC,10A-01 Nos (NHP BATC)
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Supply, fixing and commissioning of CPRI Approved AMF panel of IP 65 rating for existing DG set of Capacity 125 KVA made from CRCA sheet 3.15.mm thick Outdoor pedestal type supported on MS iron channel 75 x 40mm/suitable size at required, totally enclosed with front and rear opening, hinged doors with projected a raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 copper bus bars with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 200 A Capacity complete and Powder coating, necessary internal electric connection as required and provision of the following: - Loc - Old Telephone Exchange - 125 KVA DG Set
(a) 200A, 3P, 25kA, MCCB ATM (TM) Release, Type: Winbreak-1-1.00 Nos (C & S CSE2M250ATM3 P-200) with Extended Rotary Handle CSE2- 01 Nos (C &S EHW 1-250), 160-250A, 3P, Spreader Terminals, CSE2, CSC4, WiNbreak1 -02 Nos ( C & S CSET2033)
(b) Wire Wound CT 200/5A, CL-01, 5VA ID-50mm - 01 Nos (Make & CAT No Amol CT200 5A-5VA)
(c) Digital meter 3Ph, 4W kWh meter, LCD type, Dir Base Mounting 240V 5- 30 A Acc 1-01 Nos (Make and CAT No WR301BC4D20 of L &T)
(d) 3 PH Digital Ammter 230V, AC Aux Supply -01 Nos (Secure)
(e) Digital Voltmeter 3 PH- 01 Nos (Secure)
(f) 225A, 3P, Exceed Power Contactor with AC coil, 235V-02 Nos (For mains and DG supply) (C & S LC1FDP225AEC5W)
(g) Line Voltage Monitor Relay , 2 Changeover,220V- 01 Nos (Proton VMR3)
(h) Control Relay 2 C/O 24V DC- 03 Nos (salzer MSP2P24)
(j) Closed Terminals Socket for MSP - 2 Pole - 03 Nos (Salzer MSP 08C)
(k) Red, Yellow, Blue Indicating lamp with integral LED metallic suaitable for operating at 110V, 240V, 220V, 48V, 24V, 12V AC/DC- 03 Nos (C &S RCB7-IVL74, RCB7-IVL78, RCB7-IVL76)
(l) 6A, 1P, 10kA, C Curve Inductive Load With Surge Current-Motor Circuit Applications MCB-05 Nos (C & S CSMBS1C6)
(m) 10A, 2P, 10kA, C Curve Inductive Load With Surge Current-Motor Circuit Applications MCB-02 Nos ( C &S CSMBS2C10
(n) 4 mm, Feed Thru Screw Clamp Terminal-12 Nos (Connectwell-CTS4UN)
(O) 10 mm Slide Link Disconnect Screw Clamp TB (Connectwell-CDTTU)-03 Nos
(p) End Plate for EPCDTTU (Connectwell EPCDTTU)-01 Nos
(q) Battery Charger,24V,DC,10A-01 Nos (NHP BATC)
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Supply, fixing and commissioning of CPRI Approved AMF panel of IP 65 rating for existing DG set of Capacity 200 KVA made from CRCA sheet 3.15.mm thick Outdoor pedestal type supported on MS iron channel 75 x 40mm/suitable size at required, totally enclosed with front and rear opening, hinged doors with projected a raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 copper bus bars with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 320 A Capacity complete and Powder coating, necessary internal electric connection as required and provision of the following: - Loc - Old Telephone Exchange - 200 KVA DG Set
(a) 320A, 3P, 25kA, MCCB ATM (TM) Release, Type: Winbreak-1-1.00 Nos (C & S CSE3M400ATM3 P-320) with Extended Rotary Handle CSE3- 01 Nos (C &S EHW 1-400-630), 320-350-400A, 3P, Spreader Terminals, CSE3 WiNbreak1 -02 Nos ( C & S CSET3033)
(b) Wire Wound CT 300/5A, CL-01, 5VA- 01 Nos (Make & CAT No Amol CT300)
(c) Digital meter 3Ph, 4W kWh meter, LCD type, Dir Base Mounting 240V 5- 30 A Acc 1-01 Nos (Make and CAT No WR301BC4D20 of L &T)
(d) 3 PH Digital Ammter 230V, AC Aux Supply -01 Nos (Secure)
(e) Digital Voltmeter 3 PH- 01 Nos (Secure)
(f) 185A, 3P, Exceed Power Contactor with AC coil, 235V-02 Nos (For mains and DG supply) (C & S LC1FDP185AEC5W)
(g) Line Voltage Monitor Relay , 2 Changeover,220V- 01 Nos (Proton VMR3)
(h) Control Relay 2 C/O 24V DC- 03 Nos (salzer MSP2P24)
(j) Closed Terminals Socket for MSP - 2 Pole - 03 Nos (Salzer MSP 08C)
(k) Red, Yellow, Blue Indicating lamp with integral LED metallic suaitable for operating at 110V, 240V, 220V, 48V, 24V, 12V AC/DC- 03 Nos (C &S RCB7-IVL74, RCB7-IVL78, RCB7-IVL76)
(l) 6A, 1P, 10kA, C Curve Inductive Load With Surge Current-Motor Circuit Applications MCB-05 Nos (C & S CSMBS1C6)
(m) 10A, 2P, 10kA, C Curve Inductive Load With Surge Current-Motor Circuit Applications MCB-02 Nos ( C &S CSMBS2C10
(n) 4 mm, Feed Thru Screw Clamp Terminal-12 Nos (Connectwell-CTS4UN)
(O) 10 mm Slide Link Disconnect Screw Clamp TB (Connectwell-CDTTU)-03 Nos
(p) End Plate for EPCDTTU (Connectwell EPCDTTU)-01 Nos
(q) Battery Charger,24V,DC,10A-01 Nos (NHP BATC)
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Supply, fixing and commissioning of CPRI Approved AMF panel of IP 65 rating for existing DG set of Capacity 62.5 KVA made from CRCA sheet 3.15.mm thick Outdoor pedestal type supported on MS iron channel 75 x 40mm/suitable size at required, totally enclosed with front and rear opening, hinged doors with projected a raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 copper bus bars with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 100 A Capacity complete and Powder coating, necessary internal electric connection as required and provision of the following: - Loc - MES IB & Victoria Road Pump House - 62.5 KVA DG Set
(a) 100A, 3P, 25kA, MCCB ATM (TM) Release, Type: Winbreak-1-1.00 Nos (C & S CSE1M125ATM3 P-100) with Extended Rotary Handle CSE2- 01 Nos (C &S EHW 1-250), 80-125A, 3P, Spreader Terminals,CSE1, CSC1,CSC2, CSC3 WiNbreak1 -02 Nos ( C & S CSET1033C)
(b) Tape Wound CT 100/5A, CL-01, !5VA, ID-30mm- 01 Nos (Make & CAT No Amol CT100-15VA)
(c) Digital meter 3Ph, 4W kWh meter, LCD type, Dir Base Mounting 240V 5- 30 A Acc 1-01 Nos (Make and CAT No WR301BC4D20 of L &T)
(d) 3 PH Digital Ammter 230V, AC Aux Supply -01 Nos (Secure)
(e) Digital Voltmeter 3 PH- 01 Nos (Secure)
(f) 115A, 3P, Exceed Power Contactor with AC coil, 235V-02 Nos (For mains and DG supply) (C & S LC1FDP115AEC5W)
(g) Line Voltage Monitor Relay , 2 Changeover,220V- 01 Nos (Proton VMR3)
(h) Control Relay 2 C/O 24V DC- 03 Nos (salzer MSP2P24)
(j) Closed Terminals Socket for MSP - 2 Pole - 03 Nos (Salzer MSP 08C)
(k) Red, Yellow, Blue Indicating lamp with integral LED metallic suaitable for operating at 110V, 240V, 220V, 48V, 24V, 12V AC/DC- 03 Nos (C &S RCB7-IVL74, RCB7-IVL78, RCB7-IVL76)
(l) 6A, 1P, 10kA, C Curve Inductive Load With Surge Current-Motor Circuit Applications MCB-05 Nos (C & S CSMBS1C6)
(m) 10A, 2P, 10kA, C Curve Inductive Load With Surge Current-Motor Circuit Applications MCB-02 Nos ( C &S CSMBS2C10
(n) 4 mm, Feed Thru Screw Clamp Terminal-12 Nos (Connectwell-CTS4UN)
(O) 10 mm Slide Link Disconnect Screw Clamp TB (Connectwell-CDTTU)-03 Nos
(p) End Plate for EPCDTTU (Connectwell EPCDTTU)-01 Nos
(q) Battery Charger,24V,DC,10A-01 Nos (NHP BATC)
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Supply, fixing and commissioning of CPRI Approved AMF panel of IP 65 rating for existing DG set of Capacity 50 KVA made from CRCA sheet 3.15.mm thick Outdoor pedestal type supported on MS iron channel 75 x 40mm/suitable size at required, totally enclosed with front and rear opening, hinged doors with projected a raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 copper bus bars with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 125 A Capacity complete and Powder coating, necessary internal electric connection as required and provision of the following: - Loc - GE (N) Pune - 50 KVA DG Set
(a) 125A, 3P, 25kA, MCCB ATM (TM) Release, Type: Winbreak-1-1.00 Nos (C & S CSE1M125ATM3 P-125) with Extended Rotary Handle CSE1- 01 Nos (C &S EHW 1-125), 80-125A, 3P, Spreader Terminals,CSE1, CSC1,CSC2, CSC3 WiNbreak1 -02 Nos ( C & S CSET1033C)
(b) Wire Wound CT 125/5A, CL-01, 5VA, - 01 Nos (Make & CAT No Amol CT125)
(c) Digital meter 3Ph, 4W kWh meter, LCD type, Dir Base Mounting 240V 5- 30 A Acc 1-01 Nos (Make and CAT No WR301BC4D20 of L &T)
(d) 3 PH Digital Ammter 230V, AC Aux Supply -01 Nos (Secure)
(e) Digital Voltmeter 3 PH- 01 Nos (Secure)
(f) 150A, 3P, Exceed Power Contactor with AC coil, 235V-02 Nos (For mains and DG supply) (C & S LC1FDP150AEC5W)
(g) Line Voltage Monitor Relay , 2 Changeover,220V- 01 Nos (Proton VMR3)
(h) Control Relay 2 C/O 24V DC- 03 Nos (salzer MSP2P24)
(j) Closed Terminals Socket for MSP - 2 Pole - 03 Nos (Salzer MSP 08C)
(k) Red, Yellow, Blue Indicating lamp with integral LED metallic suaitable for operating at 110V, 240V, 220V, 48V, 24V, 12V AC/DC- 03 Nos (C &S RCB7-IVL74, RCB7-IVL78, RCB7-IVL76)
(l) 6A, 1P, 10kA, C Curve Inductive Load With Surge Current-Motor Circuit Applications MCB-05 Nos (C & S CSMBS1C6)
(m) 10A, 2P, 10kA, C Curve Inductive Load With Surge Current-Motor Circuit Applications MCB-02 Nos ( C &S CSMBS2C10
(n) 4 mm, Feed Thru Screw Clamp Terminal-12 Nos (Connectwell-CTS4UN)
(O) 10 mm Slide Link Disconnect Screw Clamp TB (Connectwell-CDTTU)-03 Nos
(p) End Plate for EPCDTTU (Connectwell EPCDTTU)-01 Nos
(q) Battery Charger,24V,DC,10A-01 Nos (NHP BATC)
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Supply, fixing and commissioning of CPRI Approved AMF panel of IP 65 rating for existing DG set of Capacity 380 KVA made from CRCA sheet 3.15.mm thick Outdoor pedestal type supported on MS iron channel 75 x 40mm/suitable size at required, totally enclosed with front and rear opening, hinged doors with projected a raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 copper bus bars with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 630 A Capacity complete and Powder coating, necessary internal electric connection as required and provision of the following: - Loc - SCSR - 380 KVA DG Set
(a) 630A, 3P, 36kA, MCCB ATM (TM) Release, Type: Winbreak-1-1.00 Nos (C & S CSE4NN630ATM3 P-630) with Extended Rotary Handle CSE3- 01 Nos (C &S EHW 1-400-630), 500-630A, 3P, Spreader Terminals, CSE4 WiNbreak1 -02 Nos ( C & S 4033-WB1)
(b) Wire Wound CT 600/5A, CL-01, 5VA- 01 Nos (Make & CAT No Amol CT600)
(c) Digital meter 3Ph, 4W kWh meter, LCD type, Dir Base Mounting 240V 5- 30 A Acc 1-01 Nos (Make and CAT No WR301BC4D20 of L &T)
(d) 3 PH Digital Ammter 230V, AC Aux Supply -01 Nos (Secure)
(e) Digital Voltmeter 3 PH- 01 Nos (Secure)
(f) 630A, 3P, Exceed Power Contactor with AC coil, 235V-02 Nos (For mains and DG supply) (C & S LC1FDP630AEC5W)
(g) Line Voltage Monitor Relay , 2 Changeover,220V- 01 Nos (Proton VMR3)
(h) Control Relay 2 C/O 24V DC- 03 Nos (salzer MSP2P24)
(j) Closed Terminals Socket for MSP - 2 Pole - 03 Nos (Salzer MSP 08C)
(k) Red, Yellow, Blue Indicating lamp with integral LED metallic suaitable for operating at 110V, 240V, 220V, 48V, 24V, 12V AC/DC- 03 Nos (C &S RCB7-IVL74, RCB7-IVL78, RCB7-IVL76)
(l) 6A, 1P, 10kA, C Curve Inductive Load With Surge Current-Motor Circuit Applications MCB-05 Nos (C & S CSMBS1C6)
(m) 10A, 2P, 10kA, C Curve Inductive Load With Surge Current-Motor Circuit Applications MCB-02 Nos ( C &S CSMBS2C10
(n) 4 mm, Feed Thru Screw Clamp Terminal-12 Nos (Connectwell-CTS4UN)
(O) 10 mm Slide Link Disconnect Screw Clamp TB (Connectwell-CDTTU)-03 Nos
(p) End Plate for EPCDTTU (Connectwell EPCDTTU)-01 Nos
(q) Battery Charger,24V,DC,10A-01 Nos (NHP BATC)
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Supply, laying and testing in replacement of cable XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 Volts grade cross sectional area 3.5 core x 240 Sq mm. complete all as specified and as directed. Note : Provision of suitable double crimpped lugs and glands deemed to be included in quoted rates.
'-ditto- all as per item No 14 above but 3.5 core 185 sqmm
'-ditto- all as per item No 14 above but 3.5 core 120 sqmm
'-ditto- all as per item No 14 above but 3.5 core 95 sqmm
'-ditto- all as per item No 14 above but 3.5 core 70 sqmm
'-ditto- all as per item No 14 above but 3.5 core 50 sqmm
'-ditto- all as per item No 14 above but 4 core 35 sqmm
'-ditto- all as per item No 14 above but 4 core 25 sqmm
M&L for Boring of holes under road, pavement,hard standing by trenchless technology using ultra sound technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and as directed.
Supply and lay in trenches /under roads/ crossing or fixed to wall/ pole, GI tubing light grade of size 50mm bore for protection of UG cables complete all as specified and as directed.
All as per Item No. 23 above but 80 mm
Excavation in trenches n exc 1.5 wide and n exc 1.5 m in depth for foundation etc or for laying cable etc n exc 10 Sqm on plan and n exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and as directed.
Returning filling in including spreading, leveling, watering and well ramming in layers n exc 25 cm complete all as specified and as directed.
Removal of excavated material/surplus soil to a distance n exc 50m and depositing where directed at a level n exc 50m above the starting point complete all as specified and as directed.
Supply and laying 40mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Supply and laying 50mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Supply and laying 63mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Supply and laying 75mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
M&L for Maintenance Free Grounding Solution set earthing comprising of High tensile low carbon steel rod of 3 Mts length & 17.2 mm dia with 250micron ( average ) molecularly bonded copper on the outer surface along with Back-fill compound strictly be a Carbon based conductive concrete type which has a resistivity of less than 0.12 Ohm Mtr. Back-fill compound should be electronically conductive ( Like in metals ) and should not depend on moisture for conduction. Back-fill compound should be environment friendly, should solidify when mixed with water and set like concrete and should not leach / diffuse into the ground. Make: JEF Technology or equivalant in True power earthings Note:- a) Test certificate from the OEM has to be produced by the contractor for the material used in earthing. b) If the test result obtain from earthing is not less than 3 Ohms then earthing has to be done again at no extra cost. c) Rates for Excavation and earthwork in any type of soil/strata, testing on completion, copper clad steel conductor wire 4 mm dia and 15 mm dia protection pipe upto 7.5 mtr from Electrode is deemed to be included in rate quoted.)
S&F Earth conitnuity Copper clad steel conductor or main earthing lead fixed to wall on batten or reccess or chases or burried in ground or drawn in conduit/pipe or fixed to pole or any other indicated situation for loop earthing etc as required 8 mm dia after taking down the old one any type.
Note : 1. Performance security:- Refer Condition 22 of Special Conditions. 2. Quoted Contract Sum shall be arrived at after deducting the amount of Credit Schedule (refer Schedule of Credit in pdf form for quantity, rate and amount etc.) for old unserviceable materials retrieved from site.
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.24 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.30 MB
tenderdocuemnts97.pdf
Tender Documents • 0.84 MB
BOQ_846593.xls
BOQ • 10.97 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .