Loading…
Loading…
| # | Company | Amount | Status |
|---|---|---|---|
| 1 | ₹12.3 Laccepted-finance | accepted-finance |
Tender Value
₹11.8 L
EMD Value
₹24,000
Closing Date
25 Nov 2025, 11:00 pmClosed
Krishna Bhagya Jala Nigam Limited
Manjunath Nagaral
Supplying And Fixing of 3 Nos Lighting Arester ,Serviceing of 3 Nos PT And 3 Nos CT And 1 Nos 10 MVA Transformer of 110/6.6 KV Sub-station of Ramathal (Marol) 1st Stage pump house
KBJNL/2024-25/OW/WORK_INDENT1550/CALL-5
KBJNL/2024-25/OW/WORK_INDENT1550/CALL-5
Open
Other Works
Electronic Documents, First(One Cover)
KBJNL Division ARBC Division Hunagunda
6 documents required · 6 mandatory
₹500
₹24,000
25 Nov 2025
17 Nov 2025
24 Nov 2025
Supplying And Fixing of 3 Nos Lighting Arester ,Serviceing of 3 Nos PT And 3 Nos CT And 1 Nos 10 MVA Transformer of 110/6.6 KV Sub-station of Ramathal (Marol) 1st Stage pump house
Repair and overhauling of OLTC each Divertor switch including change of oil, lubrication and replacement of gaskets and other parts which are locally available of 110/33-11 kV Class - 110/11 kV Class...
Testing the Transformer for routine tests as per IS 2026-1983 for 33kv voltage class(5/6.3/8/10MVA)Transformer:Testing : 1. Ratio Test ,2. SC Test, 3. Excitation Current Test/ Highpot Test, 4. Magne...
Filtration of oil using filter set of the contractor to bring the insulation value to I.E. specification with All Lead and Lift As directed by the Engineer incharge of the work.
Supply of new EHV Grade transformer Oil as per IS-335 :1993 for 5 MVA &10 MVA Transformers etc complete as per specification with all lead and lift and as directed by the engineer incharge of ...
Testing of Breaker:Test for insulation level/IR Value,gas leakage,testing for travel time(C,O &CO,OC),trip and close timings,local trip close test,remote trip and close test,tripping through relays,op...
Reconditioning of RTCC Panel and modification for SCADA compatability, replacement of all types switches, indicating lamps, annunciator windows, ROTI, RWTI, Tap position indicator etc., if required 11...
Reconditioning of accessories like radiators,conservators by hot air circulation along with pressure test of radiators and reconditioning of transformer mounted mechanical relays 110kv and below volta...
Testing and commissioning of CTs:Insulation istance,polarity,Ratio,excitation core identification,tan-delta &capacitance testas per specification with all lead and lift and as directed by the engineer...
Testing and commissioning of PTs:Insulation resistance, polarity,Ratio, excitation, core identification, tan delta,and capacitance test as per specification with all lead and lift and as directed by...
Testing of C&R Panel:Testing for for insulation level,testing of relay,control operations for closing triping etc.interlock,alarm annunciation and indication checks(without SAS).as per specification w...
Testing and commissioning of battery set and charger Testing:AC supply voltage phase sequence,testing of output DC Voltage in boost/float/trickle/variations as per order,testing for repel factor.cage ...
Supplying And fixing Surge Arrester Rated 96 KV Class-3 As per specification With All Lead and Lift As directed by the Engineer incharge of the work.
Measuring Equipment CT PT Operated ETV Meter 0.2s Accuracy Class with ABT feature and DLMS protocal with ToD with RS 232 Port UNIDIRACTIONAL (Used for HT Installation, LT Metering Cubicle 50-150 KW As...
Supplying and installation of RUBBER MAT1mtrx1mtr-10 mm thick. complete including cost of materials, labour, usage charges of machinery complete as per specifications.
Tools & Plant Rubber Hand gloves 15 kV, SEAMLESS Confirming to ISS Sample to be verified for seamless before approval) for electrical purpose as per specification with all lead and lift and as direct...
Control Cables and UG Cables:Supplying & Laying cable trays including welding, fixing of supports Cable tray of 600 mm width as per specification with all lead and lift and as directed by the engin...
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
KW-1Transformer DTP.doc
Tender Document • 1.65 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .