Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹7.3 L
EMD Value
₹15,000
Closing Date
22 Jan 2026, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
XEN Electrical Division No. 1 Shimla
The Executive Engineer Electrical Division No-1 HPPWD Shimla-9
CO Balance work of Consumer Forum Building at Solan HP (SH Providing E.I therein).
2026_PWD_125703_5
Electrical Division-I dated 05.01.2026
Open Tender
Electrical Works
Percentage
90 days
SHIMLA
As per bidding document
12 documents required · 12 mandatory
₹350
₹15,000
30 Jan 2026
16 Jan 2026
23 Jan 2026
16 Jan 2026
22 Jan 2026
16 Jan 2026
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group-C
Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 4 sq. mm + 1 X 4 sq. mm earth wire
4 X 4 sq. mm + 2 X 4 sq. mm earth wire
2 X 10 sq. mm + 1 X 6 sq. mm earth wire
4 X 10 sq. mm + 2 X 6 sq. mm earth wire
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
3x1.5 Sq. mm.
3x4.0 Sq. mm.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.:-25 mm. dia
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required.
S/E of LED Batten with polycarboante body and diffuser The fitting should be installed on existing surface/recess The job includes carriage, erection, making connections testing and commissioning of the fittings.Specification of LED fittings:
Wattage of LED fittings-As per following parameter.
Total lumens of the fittings.-as below
Diffuser - Polycarbonate diffuser/PMMA
Operating voltage =140 V to 270 V, AC supply or better.
Input frequency =50 Hz + 1 Hz
Power factor =Minimum 0.90
Luminaire efficacy =>100 lm/w
Color rendering index=CRI shall be greater than 80
Working/ operating temperature =00 to + 450c or better
Color temperature =60000K + 10%
Electronic Driver
Drive current (LED)=As per OEM.
Operating voltage =140 V to 270 V, AC supply or better.
Type of driver =Constant current output driver
THD =Less than 10%
Surge Protection =2.5 KV minimum
Efficiency Driver=>85%
Protection=Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver =2 years against manufacturing defect.
Fixture =Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 25,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED=25000 burning hours at 70% lumen maintenance
Lumen output of the fitting=>2000 Lumens
S/E of LED bulk head IP 66 rated with aluminium body/PDC housing The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings.
Wattage of LED fittings-As per following parameter.
Total lumens of the fittings.-as below
Diffuser - Polycarbonate diffuser/PMMA
Operating voltage =140 V to 270 V, AC supply or better.
Input frequency =50 Hz + 1 Hz
Power factor =Minimum 0.90
Luminaire efficacy =>80 lm/w
Color rendering index=CRI shall be greater than 80
Working/ operating temperature =0o to + 45oc or better
Color temperature =60000K + 10%
Electronic Driver
Drive current (LED)=As per OEM.
Operating voltage =140 V to 270 V, AC supply or better.
Type of driver =Constant current output driver
THD =Less than 10%
Surge Protection =2 KV minimum
Efficiency Driver=>85%
Protection=Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver =2 years against manufacturing defect.
Fixture =Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED=50000 burning hours at 70% lumen maintenance
Lumen output of the fitting=>800 Lumens
S/E of LED Downlighter surface square with CRCA/PDC body and diffuser The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings.
Wattage of LED fittings-As per following parameter.
Total lumens of the fittings.-as below
Diffuser - Polycarbonate diffuser/PMMA
Operating voltage =140 V to 270 V, AC supply or better.
Input frequency =50 Hz + 1 Hz
Power factor =Minimum 0.90
Luminaire efficacy =>85 lm/w
Color rendering index=CRI shall be greater than 80
Working/ operating temperature =0 o to + 45 oc or better
Color temperature =60000K + 10%
Electronic Driver
Drive current (LED)=As per OEM.
Operating voltage =140 V to 270 V, AC supply or better.
Type of driver =Constant current output driver
THD =Less than 10%
Surge Protection =2.5 KV minimum
Efficiency Driver=>85%
Protection=Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver =2 years against manufacturing defect.
Fixture =Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED=50000 burning hours at 70% lumen maintenance
Lumen output of the fitting=>1500 Lumens
Lumen output of the fitting=>2000 Lumens
Lumen output of the fitting=>2400 Lumens
Supplying and fixing of LED street light versatile pressure die-cast alluminium housing with UV stablized PC IP diffuser for better light distribution alongwith electronic driver,complete with all accessories including making connections, testing etc. as required. Make:- C&S, Wipro, Bajaj,Havells, Panasonic, or any other approved by Engineer-in-Charge.
LED street light 30 W
Supplying and erection of street light bracket made of G.I. pipe 'A' class of suitable length and dia, the pipe bended to give an angle of 100 to 110 degree fitted with bolt & nuts at the top of existing pole or wall including painting the pipe with two coats of approved paint over priming coat complete in all respects as required:- 32 mm dia. G.I. pipe, heavy class
Supply, Installation, Testing and Commissioning of following sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.85, Air delivery minimum 215 CMM, 300 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote/ BLDC electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
Ceiling Fan 1200 mm sweep
Ceiling Fan 1400 mm sweep
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Installation of ventilatinmg /exhaust fan in the existing opening, including making good BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor the damage, connection, testing, commissioning etc. as required.Supply & Erection of Ventilating Fan ) following size complete with motor,, with minimum power consumption, rigid frame with rubber mounting for silent operation, in the existing opening including cost of making the hole to suit the size of above fan making good the damage, Carriage Charges connection, testing, commissioning etc. as required to complete the job to the entire satisfaction of EIC.
Exhaust Fan, 250 mm sweep
Providing and installation exhaust fan of following sizes in the existing opening, Double ball bearing type metal frame including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required: of Approved Make Heavy Duty type.
Exhaust Fan, Heavy duty, 300 mm sweep (900/1400rpm)
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
12 way , Double door
Supplying and fixing following rating, followings poles 10ka 240/415v 'C' curves miniature circuit braker suitable for inductive load of following poles in the exsisting MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Supplying and erection of sub- panel 63 Amp. cubical panel enclosure DMC/SMC Insulator supports control wiring with thimble power wiring with thimble terminal block & short links door locks & hings rubber gasket heat shrinkable sleeves colour coded engraved name plate indoor type wall mounted complete with locking arrangement to house 63 Amp. MCCB with 100 Amp Copper busbar Phase indication lamps RYB. The cubical panel shall have cable entry at two sides complete in all respects including the cost of switchgears.
Providing & Laying of one number aluminium conductor, PVC insulated and PVC sheathed armoured/ XLPE power cable, 1.1 KV grade of following sizes on wall surface as required.
Armoured cable 25 sq. mm (3.5 core)
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required.
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.48 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.37 MB
DeclarationNEW.pdf
Additional Documents • 0.01 MB
SBD_11_Balance.pdf
Tender Documents • 3.75 MB
BOQ_185270.xls
BOQ • 0.36 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .